20013-001-Rev0 Flooded Gum Pl - geotech report
Mr Andrew Jensen 20013-001-Rev0
4 February 2020
5.0 SUMMARY & CONCLUSIONS
Based on the findings of our assessment we consider that there would be a Low Risk of slope instability
subject to implementation of the recommendations given in this report, in particular:
The proposed residence is to be supported on footings founded at least 300 mm in to weathered
rock.
Diversion drains are established above cut and fill batters
Ensuring that stormwater collected by drainage, including any overflow from tanks, is directed to
discharge at least 10 m down slope of any fill and structure.
All cut/fill is battered no steeper than 1V:2H or supported by retaining walls.
Vegetation must be established and maintained to prevent erosion of currently bare soils.
6.0 LIMITATIONS
Your attention is drawn to the document Limitations, which is attached to this letter report.
Please contact the undersigned should you wish to discuss any of the above matters.
Yours faithfully
TECTONIC GEOTECHNICAL PTY LTD
David Pollock BE(Civil) RPEQ14121
Senior Geotechnical Engineer
Attachments: Qualitative Terminology for Use in Assessing Risk to Property
Some Guidelines for Hillside Construction
Limitations