Effluent disposal report
3.3 Soil Classification
BORE HOLE #1 BORE HOLE #2
Depth Texture Structure Colour CAT Depth Texture Structure Colour CAT
0- 0- Loamy Sand Weakly Grey
Loamy Sand Weakly Grey 2 2
500 500
500- 500-
Loamy Sand Weakly Grey 2 Loamy Sand Weakly Grey 2
900 900
Moist N Water No Rock No Moist Y Water No Rock No
Soil Classification Adopted - Conservative Rate due to fair exposure
Borehole Nos 1&2
Soil Category Adopted 3
Indicative Drainage Well Drained
Structure Weakly
Texture Loamy Sand
Indicative Permeability P (m/d) as Ksat* 0.5 - 1.5
Recommended DIR (AS/NZS 1547 / 2012 - Table M1) 4
4.0 Recommendations:
4.1 Treatment Facility:
The on-site treatment facility is to be a Wastewater Treatment System consistently producing Advanced Secondary
Quality Effluent with a capacity of no less than 10 Equivalent Persons (10EP).
The owner has indicated their preferred system is the Earth Safe D10 Advanced Secondary (Concrete) system - TPA #
03/2019. A tall tank and possible riser ring may be required. The chosen systems approvals meet the Effluent Quality
and Equivalent Person recommendations for this site. Failure to comply may require the system to be removed from
site.
All wastewater from the new dwelling and any future amenities in the shed are to be directed to the Wastewater
Treatment Plant.
Position of the proposed Land Application Area is shown on the Site Plan. All works must comply with the Qld
Plumbing and Wastewater Code and be performed by a licenced plumber.
5.0 Design Calculation
The serviceable life of the Land Application Area will be compromised if the design flow is exceeded. Any
proposed changes to the position of the Land Application Area, System Type or House Design will require a
reassessment of this site. For our calculations we have assessed the design flow as follows:
Design Calculation
DIR (mm/d) (secondary quality effluent) 4
Hydraulic load (lt/day/person) Tank Water / 5 bedrooms 120
Design Flow Q (lt/day) PE: 8 960
Design sizing calculation Ai = (Q)/DIR
= (960)/4
Disposal area A+B (square metres) AS/NZS1547:2012 Min 240m2
Nominated Configuration (metres) 24m x 10.2m
A new Advanced Secondary HSTP is required: 10 EP
C Copyright Lance Picton 2019 design & content. 3/8