Attached to the e-mail MCU16/0098 & OPW16/0183 - Request to change existing approval - 21 Venture Drive NOOSAVILLE.
Original PDF page 15, section 1. The text section number identifies this passage in the reader.
Noosa Council documents
MCU16/0098
g. Certification by a suitably qualified person* that the plan design and/or
installation and operation of the mechanical exhaust ventilation system,
complies with AS1668 and the requirements of this Decision Notice must be
submitted to council. Completed Building Act 1975 Certificate Forms 15 and
Form 16 must also be provided prior to commencement of food preparation.
h. Horizontal hot air discharge from the mechanical exhaust ventilation system
in the direction of neighboring properties and/or the street precincts is not
desirable and may constitute an environmental nuisance under the
Environmental Protection Act 1994.
i. Toilets for customers and staff to be provided in accordance with the Building
Code of Australia. Design advice is to be obtained from a building certifier
on numbers and standards, including disabled access.
Rainwater/Detention Tanks
18. Any rainwater tanks/detention tanks must be constructed with mosquito proof
screens (made from either brass, copper, aluminium or stainless steel), and
constructed with a mesh size of no more than 1mm, and must be installed in a way
that does not accelerate corrosion. Tanks that contain flap valves must be installed
so that when closed, mosquitoes cannot pass through the valve.
19. Where it is intended to use rainwater for drinking purposes, a suitable treatment
system is required to be installed to disinfect or treat the water to microbiological
and physical standards as described in the current Australian Drinking Water
Guidelines to make it fit for drinking purposes.
7 PROPERTY NOTES
Not Applicable
8 PRELIMINARY APPROVAL OVERRIDING PLANNING SCHEME
Not Applicable
9 FURTHER DEVELOPMENT PERMITS REQUIRED
Development Permit for Building Works - ( All Building Works)
10 SELF ASSESSABLE CODES
The following codes for self-assessable development related to the development
approval issued under this Decision Notice must be complied with.
Advertising Devices Code
11 SUBMISSIONS
No properly made submissions were received about this application.
12 REASONS/GROUNDS FOR APPROVAL
The Assessment Manager considers that the café is ancillary and complementary to the
primary industrial use on-site and will not cause any reverse amenity issues and
therefore is sufficient grounds to justify the decision despite the conflict with the Planning
Scheme.
Page 15 of 18
Document Set ID: 20204040
Version: 1, Version Date: 22/11/2016 Print Date: 22 November 2016, 1:58 PM
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
Large file: the download may take up to a minute.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.