Attachment B - Proposed Plans · MCU19/0049.01
Plans and drawings: the text below has words only, no drawings.
MECHANICAL - ELECTRICAL - HYDRAULIC - FIRE - ENERGY - NABERS - STORMWATER - SECTION J - BEEC
BUILDING SERVICES ENGINEERS
Fire Hydrant Services
EDEN PRIVATE HOSPITAL
50 MAPLE STREET, COOROY QUEENSLAND
About Marline Engineering Newcastle
Trusted Expertise Since 19 5 As industry leaders with engineers registered across all DRAWING SCHEDULE
States and Territories, we certify designs across all building classes under the National
Construction Code. FH-00-000 COVER PAGE
FH-00-001 LEGEND & NOTES
Tailored, Innovative Designs We craft cost-effective, practical solutions aligned with
Australian Standards and regulations; turning your vision into reality with designs we FH-10-001 LOWER FLOOR – FIRE HYDRANT LAYOUT
would be proud to own ourselves. FH-10-002 GROUND FLOOR – FIRE HYDRANT LAYOUT
FH-10-002 UPPER FLOOR – FIRE HYDRANT LAYOUT
Comprehensive In-House Solutions Through seamless electrical, mechanical, hydraulic
energy and fire systems engineering, our designs are delivered in AutoCAD and Revit FH-30-001 DETAILS
for precise, reliable and buildable documentation.
Agile and Responsive Our capacity and flexibility ensures swift, personalised service,
adapting to your projects unique requirements.
Your artner in Success We pride ourselves on collaboration, high-quality workmanship
and reliable support to your projects to life.
Beyond Compliance Our Energy Team delivers cutting-edge Section J, BASIX and J1V3
alternative solutions, elevating sustainability and performance.
PROJECT No:
MN16443
CLIENT:
REAL ASSET MANAGEMENT PTY LTD
ARCHITECT:
FOR CONSTRUCTION
FIRE HYDRANT SERVICES
FH-00-000 A
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 5 pages
Page 2
NOTE: SOME ITEMS MAY NOT BE USED
LINETYPES KEY SYMBOLS - FIRE ABBREVIATIONS GENERAL NOTES
eCW COLD WATER AREA NOT COVERED BY BOOSTER ASSEMBLY DPH DOUBLE PILLAR HYDRANT. 1. ISOLATION VALVE AT WATER METER ASSEMBLY TO BE SECURED IN THE OPEN POSITION
HYDRANT OR HOSE REEL. e EXISTING. BY A PADLOCKED METAL STRAP AND AN ENGRAVED NON FERROUS METAL LABEL
eFH FIRE HYDRANT PUMP SET FH FIRE HYDRANT. ATTACHED. LABEL TO BE ENGRAVED WITH 8mm UPPER CASE WORDING: "FIRE SERVICE
FHR FIRE HOSE REEL. VALVE - CLOSE ONLY TO SERVICE FIRE HOSE REELS".
COLD WATER 10m EXCLUSION ZONE VALVE SET
FROM BUILDING 2. ALL SERVICES INSTALLED ADJACENT THE BUILDING ARE TO BE LOCATED OUTSIDE THE
FIRE HYDRANT TEST POINT ZONE OF INFLUENCE AS PER AS3500.
ALARM STROBE
FH 30m INTERNAL FIRE HYDRANT RUN HYDRANT BOOSTER IN LINE 3. ALL HYDRANT PIPEWORK TO BE BLUE BRUTE CLASS 16 INGROUND OR GALVANIZED
OF SIGHT OF FRONT ENTRY SINGLE PILLAR HYDRANT (INTERNAL) STEEL ABOVE GROUND TO COMPLY WITH AUSTRALIAN STANDARDS. ALL BLUE BRUTE
FH 60m EXTERNAL FIRE HYDRANT RUN
PIPEWORK TO BE SUPPORTED BY THRUST BLOCKS.
DOUBLE PILLAR HYDRANT (EXTERNAL)
10m FIRE HYDRANT SPRAY
4. WHERE PIPEWORK IS LIKELY TO BE EXPOSED TO FIRE IN AN AREA WITHIN A BUILDING
H STREET HYDRANT THAT IS NOT PROTECTED BY SPRINKLERS, PIPE-SUPPORTS SHALL BE INSTALLED WITH A
FHR 36m FIRE HOSE REEL RUN
MINIMUM FRL NOT LESS THAN 60/-/-. THE PIPE-SUPPORTS ARE REQUIRED TO HAVE A
FIRE HOSE REEL TEMPERATURE RESISTANCE OF NOT LESS THAN 500°C WHEN TESTED IN ACCORDANCE
4m FIRE HOSE REEL SPRAY
WITH AS1530.4.
THRUST BLOCK
FIRE FIRE FIRE FIRE WALL
FIP FIRE INDICATOR PANEL
SMOKE SMOKE SMOKE WALL
WATER PRESSURE - UNITYWATER
FIRE TRUCK (MUST BE LOCATED MINIMUM
10m FROM BUILDING & MAXIMUM 20m 150mm WATER MAIN IN TESTED: 29/01/26
FROM FEED HYDRANT).
SUMMARY RESULTS FLOW L/S PRESSURE kPa
STATIC PRESSURE (kPa) 0 296.45
0.66 295.87
5 291.55
10 285.27
20 265.45
30 245.74
MAXIMUM FLOW OBTAINED
DURING TEST: 56.5 158.13
(litres/second)
STATEMENT IS VALID UNTIL: JANUARY 2027
FIRE HYDRANT SERVICE DESIGN
FIRE HYDRANT COVERAGE IS ACHIEVED COMPLETELY VIA ON-SITE EXTERNAL
ATTACK HYDRANTS.
BUILDING CLASSIFICATION 9a
RISE IN STOREY >2
FIRE COMPARTMENT FLOOR AREA 4,760m2
PRESSURE REQUIRED 250kPa
WATER REQUIRED 20L/s
MINIMUM PRESSURE IN MAIN 265kPa
LENGTH OF RUN 100m
PIPING PRESSURE LOSS 75kPa
LOSS THROUGH DDCA 70kPa
LOSS OF FITTINGS (20%) 50kPa
VERTICAL RISE LOSS 20kPa
TOTAL PRESSURE LOSS 215kPa
PRESSURE AT TOP HYDRANT 50kPa
A PUMP IS REQUIRED
MECHANICAL ELECTRICAL HYDRAULIC FIRE ENERGY NABERS STORMWATER SECTION J BEEC
This drawing is not to be used for any construction purpose unless noted Project Drawing Title Discipline Scale N.T.S @ A1
otherwise in the issue column. Marline Newcastle pty ltd. accept no responsibility
EDEN PRIVATE HOSPITAL LEGEND & NOTES
for any unauthorised use of drawings issued on a "information and discussion"
only basis. A 13.04.26 FOR CONSTRUCTION ZM CB DW
50 MAPLE STREET, COOROY QUEENSLAND FIRE HYDRANT SERVICES
This drawing is copyright and is the property of Marline Newcastle pty ltd and must
2 27.01.26 REVISED AS REQUESTED ZM CB
not be retained, copied or used without written consent of marline newcastle. Job No. Drawing No. Rev
1 16.12.25 100% ISSUE FOR REVIEW ZM CB
[email protected] www.marline.com.au (02) 4925 9300 0 25mm
50mm 100mm ON A1 ORIGINAL
Rev Date Reason for Issue Drawn Design Verify MN16443 FH-00-001 A
Page 3
m
66
FH1
FH1
FH1 FH1
FH1
FH1
m
41
FH1
FH1
69
.5m
FH
1
FH1
FH-10-002
m
69
FH1
FH
-10
-00
FH1
2
FH
1
FH
1
FH1
MECHANICAL ELECTRICAL HYDRAULIC FIRE ENERGY NABERS STORMWATER SECTION J BEEC
This drawing is not to be used for any construction purpose unless noted Project Drawing Title Discipline Scale 1:200 @ A1
otherwise in the issue column. Marline Newcastle pty ltd. accept no responsibility
EDEN PRIVATE HOSPITAL LOWER FLOOR
for any unauthorised use of drawings issued on a "information and discussion"
only basis. A 13.04.26 FOR CONSTRUCTION ZM CB DW
50 MAPLE STREET, COOROY QUEENSLAND FIRE HYDRANT LAYOUT FIRE HYDRANT SERVICES
N
This drawing is copyright and is the property of Marline Newcastle pty ltd and must
2 27.01.26 REVISED AS REQUESTED ZM CB
not be retained, copied or used without written consent of marline newcastle. Job No. Drawing No. Rev
1 16.12.25 100% ISSUE FOR REVIEW ZM CB
[email protected] www.marline.com.au (02) 4925 9300 0 25mm
50mm 100mm ON A1 ORIGINAL
Rev Date Reason for Issue Drawn Design Verify MN16443 FH-10-001 A
Page 4
FH-10-003
69
m
1
FH
66m
FH2
FH2
INSTALL A NEW
FH2 BALCONY GATE.
FH1
FH1
FH2
FH2
FH1
62
FH1
m
60
m
FH2
1
FH FH1 FH1
FH1
FH-10-003
FH1
FH1
66
m
FH1
FH2
FH1
FH1 FH1
69.7
FH1 m
FH2
FH2
FH1
FH1
FH2
1
FH
FH2
FH1
FH1
1 FH1
1 FH
FH
69.5
m
H2
1
FH
1
FH2F
FH
m
53 DPH
FH1 FH1 FH1 FH1 FH1 21.6m
FH-10-001
DPH FH
1
FH1
FH1
10
100
0
FH1
FH FH1
1
100 100 FH1
H eCW eCW eCW eCW eCW eCW eCW eCW eCW eCW eCW eCW eCW H
FH1
FH1
eCW FH
SUPPLY & INSTALL A DOUBLE PILLAR SUPPLY & INSTALL A NEW DOUBLE PILLAR 1
HYDRANT TO BE INSTALLED NOT LESS THAN HYDRANT WITH A 4000mm WIDE x 3000mm eCW
10m FROM BUILDING HIGH 90/90/90 RATED FIRE WALL DIRECTLY eCW
BEHIND THE HYDRANT. REFER TO DETAIL. eCW FH1
APPROXIMATE LOCATION OF EXISTING TREE. 100
APPROXIMATE LOCATION OF EXISTING PROPOSED PUMPSET IS TO BE INSTALLED eCW
H 28.3m FH
AUTHORITY WATER MAIN. CLEAR OF TREE ROOT NETWORK. -10
-00
1
SUPPLY & INSTALL AN ALINE PREPACKAGED SINGLE eC
W
DIESEL FIRE HYDRANT PUMPSET WITHIN
ENCLOSURE. PUMP TO BE INSTALLED A MINIMUM OF eC
6m AWAY FROM ALL PARTS OF THE BUILDING. W
PUMP DUTY TO BE [email protected] ENCLOSURE 1200mm WIDE X 3600mm eC
W
LONG. PUMPSET TO BE LOCATED IN FIRST CARPARK.
SUPPLY & INSTALL A NEW 100mm FIRE
HYDRANT BOOSTER ASSEMBLY WITH A
100mm DOUBLE DETECTOR CHECK VALVE
WITH A 20mm BYPASS. BOOSTER TO BE
INSTALLED A MINIMUM OF 10m AWAY FROM
ALL PARTS OF THE BUILDING.
PLUMBING CONTRACTOR IS TO PROVIDE A
NEW 100mm CONNECTION TO THE
AUTHORITY'S WATER MAIN FOR FIRE WATER
SUPPLY.
MECHANICAL ELECTRICAL HYDRAULIC FIRE ENERGY NABERS STORMWATER SECTION J BEEC
This drawing is not to be used for any construction purpose unless noted Project Drawing Title Discipline Scale 1:200 @ A1
otherwise in the issue column. Marline Newcastle pty ltd. accept no responsibility
EDEN PRIVATE HOSPITAL GROUND FLOOR
for any unauthorised use of drawings issued on a "information and discussion"
only basis. A 13.04.26 FOR CONSTRUCTION ZM CB DW
50 MAPLE STREET, COOROY QUEENSLAND FIRE HYDRANT LAYOUT FIRE HYDRANT SERVICES
N
This drawing is copyright and is the property of Marline Newcastle pty ltd and must
2 27.01.26 REVISED AS REQUESTED ZM CB
not be retained, copied or used without written consent of marline newcastle. Job No. Drawing No. Rev
1 16.12.25 100% ISSUE FOR REVIEW ZM CB
[email protected] www.marline.com.au (02) 4925 9300 0 25mm
50mm 100mm ON A1 ORIGINAL
Rev Date Reason for Issue Drawn Design Verify MN16443 FH-10-002 A
Page 5
69.2
m
FH-10-002
FH1
m
58
FH2
2
FH
FH2
FH-10-002 FH2 FH2
FH2
FH
2
62
m
FH2
FH2
FH2
57m
MECHANICAL ELECTRICAL HYDRAULIC FIRE ENERGY NABERS STORMWATER SECTION J BEEC
This drawing is not to be used for any construction purpose unless noted Project Drawing Title Discipline Scale 1:200 @ A1
otherwise in the issue column. Marline Newcastle pty ltd. accept no responsibility
EDEN PRIVATE HOSPITAL UPPER FLOOR
for any unauthorised use of drawings issued on a "information and discussion"
only basis. A 13.04.26 FOR CONSTRUCTION ZM CB DW
50 MAPLE STREET, COOROY QUEENSLAND FIRE HYDRANT LAYOUT FIRE HYDRANT SERVICES
N
This drawing is copyright and is the property of Marline Newcastle pty ltd and must
2 27.01.26 REVISED AS REQUESTED ZM CB
not be retained, copied or used without written consent of marline newcastle. Job No. Drawing No. Rev
1 16.12.25 100% ISSUE FOR REVIEW ZM CB
[email protected] www.marline.com.au (02) 4925 9300 0 25mm
50mm 100mm ON A1 ORIGINAL
Rev Date Reason for Issue Drawn Design Verify MN16443 FH-10-003 A
Page 6
1048
442
EXHAUST OUTLET
65
90 MINUTE RATED
FIRE WALL
EXIT TOP VIEW
2000 2000
DOOR
FIXED FLAT PANEL
15
HINGED PANEL DISCHARGE
Ø2
80 DIA RG OR 65
3000
SCREWED DIA FIRE
HYDRANT VALVES
WITH CAP & CHAIN
ANGLED DOWN AT
35°
2200
1518
2275
DRAIN
Ø21
5
Ø 125
750 MIN.
100 x 65 REDUCER
100 TEE
3600 500 160
254
184
1300
150
GAL 100 DIA RISER
150
AS 1074 SUCTION
G.L. BACK VIEW LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW
300
400 x 400
SINGLE FIRE PUMP ENCLOSURE
WALL RATING TO EXTERNAL HYDRANTS NOTES:
1. PAINT ALL PIPEWORK & FITTINGS RED TO AS1345.
NOT TO SCALE 2. CENTRE OF SUCTION TO CENTRE OF BOOSTER 800mm. FEED HYDRANT (SUCTION OUTLET)
COMPLETE WITH STORZ CAP & CHAIN
NOTICE OF TEST/WORKING
PRESSURES
100mm GALVANISED TEE TEST COCK PRESSURE GUAGE
BOOST INLETS COMPLETE
ADJUSTABLE VANDAL ZURN DOUBLE DETECTOR CHECK TEST PRESSURE WITH STORZ CAP & CHAIN
100x65 REDUCING BUSH PROOF HYDRANT WITH VALVE, MODEL 350DA.
FIRE BRIGADE PADLOCKS
STANDARD FIRE HOSE DOUBLE CHECK VALVE ASSEMBLY
SPRING LOADED WITH FIELD TEST 100 OUTSIDE SCREW & YOKE- ISOLATING
COCK STORTZ
OR APPROVED BUTTERFLY VALVE
GATE VALVE LOCKED OPEN WHERE REQUIRED.
WITH CHAIN AND 3mm BRASS BLOCK PLAN
100
003 FIRE BRIGADE PADLOCKS PADLOCK
1200mm MAX
LOCKED OPEN
GUNMETAL STORTZ CAP
750mm
WITH 15mm BRASS FLANGE JOINT
750
SECURING CHAIN CI BEND
100
100
100mm GALVANISED PIPE
CONCRETE FC 20 MPa 28 1657mm
DAYS 500
FGL FGL
230
WELDED FLOW 100NB RG GEAR Ø TO Ø APPROX 520mm
STANDARD GALVANISED DIRECTION ARROW OPERATED
FLANGE. BUTTERFLY VALVE 100NB RG SWING CHECK VALVE
20mm DOUBLE CHECK
STANDARD BRASS FLANGE. DETECTOR BYPASS
METER ASSEMBLY
FIRE MAIN
SUPPORT BRACKETS 100mm NB TYPICAL BOOSTER ASSEMBLY & DDCV DETAIL
ALTERNATIVE DIRECTION OF
OUTLET TO BE INSTALLED AS
DIRECTED ON SITE.
35°
35°
TYPICAL DOUBLE PILLAR HYDRANT
DETAIL
NOTE: PAINT ALL PIPEWORK AND FITTINGS AS PER AS 1345.
MECHANICAL ELECTRICAL HYDRAULIC FIRE ENERGY NABERS STORMWATER SECTION J BEEC
This drawing is not to be used for any construction purpose unless noted Project Drawing Title Discipline Scale N.T.S @ A1
otherwise in the issue column. Marline Newcastle pty ltd. accept no responsibility
EDEN PRIVATE HOSPITAL DETAILS
for any unauthorised use of drawings issued on a "information and discussion"
only basis. A 13.04.26 FOR CONSTRUCTION ZM CB DW
50 MAPLE STREET, COOROY QUEENSLAND FIRE HYDRANT SERVICES
This drawing is copyright and is the property of Marline Newcastle pty ltd and must
2 27.01.26 REVISED AS REQUESTED ZM CB
not be retained, copied or used without written consent of marline newcastle. Job No. Drawing No. Rev
1 16.12.25 100% ISSUE FOR REVIEW ZM CB
[email protected] www.marline.com.au (02) 4925 9300 0 25mm
50mm 100mm ON A1 ORIGINAL
Rev Date Reason for Issue Drawn Design Verify MN16443 FH-30-001 A