Council archive · source document
Attachment B - Proposed Plans · MCU19/0049.01
Plans and drawings: the text below has words only, no drawings.
1048
442
EXHAUST OUTLET
65
90 MINUTE RATED
FIRE WALL
EXIT TOP VIEW
2000 2000
DOOR
FIXED FLAT PANEL
15
HINGED PANEL DISCHARGE
Ø2
80 DIA RG OR 65
3000
SCREWED DIA FIRE
HYDRANT VALVES
WITH CAP & CHAIN
ANGLED DOWN AT
35°
2200
1518
2275
DRAIN
Ø21
5
Ø 125
750 MIN.
100 x 65 REDUCER
100 TEE
3600 500 160
254
184
1300
150
GAL 100 DIA RISER
150
AS 1074 SUCTION
G.L. BACK VIEW LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW
300
400 x 400
SINGLE FIRE PUMP ENCLOSURE
WALL RATING TO EXTERNAL HYDRANTS NOTES:
1. PAINT ALL PIPEWORK & FITTINGS RED TO AS1345.
NOT TO SCALE 2. CENTRE OF SUCTION TO CENTRE OF BOOSTER 800mm. FEED HYDRANT (SUCTION OUTLET)
COMPLETE WITH STORZ CAP & CHAIN
NOTICE OF TEST/WORKING
PRESSURES
100mm GALVANISED TEE TEST COCK PRESSURE GUAGE
BOOST INLETS COMPLETE
ADJUSTABLE VANDAL ZURN DOUBLE DETECTOR CHECK TEST PRESSURE WITH STORZ CAP & CHAIN
100x65 REDUCING BUSH PROOF HYDRANT WITH VALVE, MODEL 350DA.
FIRE BRIGADE PADLOCKS
STANDARD FIRE HOSE DOUBLE CHECK VALVE ASSEMBLY
SPRING LOADED WITH FIELD TEST 100 OUTSIDE SCREW & YOKE- ISOLATING
COCK STORTZ
OR APPROVED BUTTERFLY VALVE
GATE VALVE LOCKED OPEN WHERE REQUIRED.
WITH CHAIN AND 3mm BRASS BLOCK PLAN
100
003 FIRE BRIGADE PADLOCKS PADLOCK
1200mm MAX
LOCKED OPEN
GUNMETAL STORTZ CAP
750mm
WITH 15mm BRASS FLANGE JOINT
750
SECURING CHAIN CI BEND
100
100
100mm GALVANISED PIPE
CONCRETE FC 20 MPa 28 1657mm
DAYS 500
FGL FGL
230
WELDED FLOW 100NB RG GEAR Ø TO Ø APPROX 520mm
STANDARD GALVANISED DIRECTION ARROW OPERATED
FLANGE. BUTTERFLY VALVE 100NB RG SWING CHECK VALVE
20mm DOUBLE CHECK
STANDARD BRASS FLANGE. DETECTOR BYPASS
METER ASSEMBLY
FIRE MAIN
SUPPORT BRACKETS 100mm NB TYPICAL BOOSTER ASSEMBLY & DDCV DETAIL
ALTERNATIVE DIRECTION OF
OUTLET TO BE INSTALLED AS
DIRECTED ON SITE.
35°
35°
TYPICAL DOUBLE PILLAR HYDRANT
DETAIL
NOTE: PAINT ALL PIPEWORK AND FITTINGS AS PER AS 1345.
MECHANICAL ELECTRICAL HYDRAULIC FIRE ENERGY NABERS STORMWATER SECTION J BEEC
This drawing is not to be used for any construction purpose unless noted Project Drawing Title Discipline Scale N.T.S @ A1
otherwise in the issue column. Marline Newcastle pty ltd. accept no responsibility
EDEN PRIVATE HOSPITAL DETAILS
for any unauthorised use of drawings issued on a "information and discussion"
only basis. A 13.04.26 FOR CONSTRUCTION ZM CB DW
50 MAPLE STREET, COOROY QUEENSLAND FIRE HYDRANT SERVICES
This drawing is copyright and is the property of Marline Newcastle pty ltd and must
2 27.01.26 REVISED AS REQUESTED ZM CB
not be retained, copied or used without written consent of marline newcastle. Job No. Drawing No. Rev
1 16.12.25 100% ISSUE FOR REVIEW ZM CB
[email protected] www.marline.com.au (02) 4925 9300 0 25mm
50mm 100mm ON A1 ORIGINAL
Rev Date Reason for Issue Drawn Design Verify MN16443 FH-30-001 A
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Attachment B - Proposed Plans.pdfRelated documentApplication case desk ↗
About this file
- File size
- 518 KB (small file)
- File type
No other editions are linked here.