                                             Noosa on Weyba Water Network Performance Assessment




1           Introduction
MWH have been engaged by Unitywater to undertake a water network performance assessment of the
proposed Noosa on Weyba development. Three initial supply options have been developed and are
included within the assessment brief prepared by Cardno (refer to Appendix A).
The proposed development is located off Old Hollett Road near Walter Hay Drive. It will be serviced
from within the existing Noosa Industrial DMA (NIDMA) with storage provided at the Tewantin
Reservoirs. Option 1 is to connect a 300 mm diameter main into the existing 375 mm diameter trunk
main along Eenie Creek Road and serve as the primary connection to the development site. Options two
and three assessed the potential for a secondary 200 mm diameter connection from the existing
150 mm diameter main in Lake Entrance Boulevard. Details of the network layout for the three supply
options assessed can be found in the Cardno Report (Appendix A).

1.1         Methodology
The assessment has applied the following methodology:
     •    The assessment has been carried out using H2OMAP Water.
     •    The demands (EPs) for the Noosa on Weyba development site were developed by Cardno and
          adopted for use in the ‘Unitywater Planning Model – Water’. Demand was distributed to
          junction/s at the boundary of the development.
     •    The water network within the NIDMA was reviewed against the latest pipe GIS layer and the
          model was updated to reflect the existing water network.
     •    Fire flow demands were added to junctions within NIDMA and a fire flow assessment was run to
          determine the critical fire flow junction.
          The model was used to assess the water supply network performance for the three supply
          options. The network was assessed with and without the proposed development under
          maximum hour and fire flow demand conditions during the Ultimate planning horizon.

1.2         Assumptions
The performance assessment of the water supply network has been undertaken assuming the following:
     •    The development demands for assessment were provided by Cardno along with calculations,
          and assumptions. MWH have confirmed that demand conversion factors used are inline with the
          Noosa Planning Scheme Policy and no revision is necessary.
     •    Along with the “no-development” scenario, the three options proposed within the assessment
          brief were the only options assessed.
     •    Only the full development solution was assessed.      No interim development stages were
          investigated.
     •    The assessment has provided results to the boundary of the development only. No internal
          water supply network was investigated and internal water supply network head losses were not
          assessed.




Status: Draft                                                                                         22/06/2012
Project number:                                  Page 1               Our ref: Noosa on Weyba WS Assessment.docx

Used in these records

About this file

File size
11.7 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Attachment 15- Amended Water Supply and Sewerage Analysis MCU12_0208.pdf · 11.7 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.