Noosa on Weyba Water Network Performance Assessment
Minimum pressure results identified during the maximum hour performance assessment are provided
below in Table 4-1.
Table 4-1: 2038 Maximum Hour Pressure Performance
Model NOOSA_ON_
NOOSA_ON_W
Junction ID NOON246 NTHWJ002615 NOON111 WEYBA_CON
EYBA_CONN1
N2
Connection #1 at Connection #2 at
Critical Connection #2
Location / the intersection Connection #1 the intersection
junction at
Description of Eenie Creek at development of Lake Entrance
within development
Road and Walter boundary Boulevard and
NIDMA boundary
Hay Drive Attenuatta Place
Pressure
Units metres
Without
Proposed 47.09 64.78 - 64.6 -
Development
Option 1 39.83 57.28 54.81 - -
Option 2 39.19 56.62 54.16 57.12 57.12
Option 3 40.15 57.68 55.92 - -
PASS / FAIL PASS PASS PASS PASS PASS