Headland Drive Road Reserve. Roof runoff from existing dwellings appears to be a mixture of
discharging directly to ground level & via kerb adaptors to Headland Drive.
The total impervious areas have been estimated using the detailed site survey and was found to be
approximately 1521m2 which equates to approximately 22% of Impervious Area for (Cat A) & 41% of
Impervious Area for (Cat B) respectively.
The existing site catchments are as follows.
Catchment A
- Area – 0.4833 Ha
- Tc – 15 mins
- Fraction Impervious (Fi) – 0.21
Catchment B
- Area – 0.1485 Ha
- Tc – 13 mins
- Fraction Impervious (Fi) – 0.41
Peak flow rates for the median design storm for the existing site are given in Table 6.3
Table 6.3 – Existing Site Peak Flow Rates (L/s) (At year 2100)
Storm Event Q1 Q2 Q5 Q10 Q20 Q50 Q100
(1EY) (0.5EY) (0.2EY) (10%AEP) (5%AEP) (2%AEP) (1%AEP)
Cat A 79 119 160 186 218 259 287
Existing PFR
Cat B 27 39 52 59 69 83 91
Existing PFR
(PFR – Peak Flow Rate)
6.1.3 Proposed Site
The development consists of the construction of mixed residential townhouse/ unit development along
with a shared access driveway and ground level landscaping/ courtyards & a community pool area. The
total pervious area for the site was calculated to be approximately 1368m2.
SCG Consulting Engineers Page 17 SCG Ref: 33132(SWMP).RevC