Council archive · source document
Attachment 3 - Engineering Report · 51994.1391.01
21 November 2022 Job Number 22080 BY EMAIL Janine Mason 2/24 Edgar Bennet Ave, Noosa Heads Email: [email protected] Dear Janine RE PROPOSED WALL RELOCATION AT 2/24 EDGAR BENNET AVE, NOOSA HEADS Ms Janine Mason requested that Sunshine Coast Structural Engineers (SCSE) complete a structural inspection and provide structural advice as an RPEQ Engineer with regards to the proposed wall relocation as part of a room extension at 2/24 Edgar Bennet Ave, Noosa Heads. The proposed works consists of removing the existing wall to the rear balcony area from the study and reinstating a proposed wall approximately 1600mm further into the balcony area. The proposed works have been documented by JMF Design drawings Project Number Edgar Bennet 2022 dated 9/11/22. SCSE was also provided with the original structural design drawings and a letter of review by the original design Engineer of the building, Mr John Norden of John Norden & Associates dated 2/7/09. The building drawings and letter of review by Mr John Norden have been attached to this document for reference. SCSE understands that Mr John Norden has now retired and as such cannot provide further input on the matter. A visual inspection of the unit was carried out by Mr Blake Scriven of SCSE on 15th November 2022. A photograph of the proposed location has been provided in the below Figure 1. Figure 1 – Proposed Wall to be Relocated Sunshine Coast Structural Engineers ABN 22 868 850 836 [email protected] www.sunshinecoaststructuralengineers.com
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 6 pages
Page 2
Based on a visual inspection of the building, a review of the original building design drawings and a
review of the letter provided by the original design Engineer of the building, SCSE advises that
removing this wall will not have an adverse impact on the original structural design intent of the
building relevant to this location.
SCSE understands the proposed new wall is to be a double cavity 90/90 brick wall. SCSE advises that
provided this wall is constructed in accordance with the relevant Australian Standards, NCC and BCA
requirements suitable to that of an N2 wind location (after taking into account shielding
considerations), that the construction of this new wall in the location as shown in the below Figure 2
will not have an adverse impact on the original structural design intent of the building relevant to
this location.
Figure 2 - Proposed Wall Location
SCSE advises that the brick cavity wall is to have medium duty wall ties between the veneers with a
maximum vertical spacing of 600mm and a maximum horizontal spacing of 450mm. The wall ties are
also to be fixed into the floor, soffit of the slab over and adjacent wall ends to adequately restrain
the edges of the wall.
SCSE also advises that a 200x10 traditional ‘T’ bar Galintel is required over the door opening. Both
the wall ties and Galintel are to be installed in accordance with the manufacturer’s specifications and
recommendations.
SCSE has not carried out any further review of the building design then directly applicable for the
above review and has not carried out an dilapidation survey of the existing building.
Please feel free to contact the aforementioned should you wish to discuss any of this further.
Yours sincerely
Blake Scriven
Director
BEng (First Class Hons) RPEQ MIEAust
Sunshine Coast Structural Engineers
ABN 22 868 850 836
[email protected]
www.sunshinecoaststructuralengineers.com
Page 3
RABRINK PTY LTD trading as John Norden July 2, 2009 & Associates Structural / Civil Design Engineers ABN 47 312 012 117 our ref: 09/46 Mr Z Kivior John Norden 39 Swift Avenue CPEng, MIE Aust, RPEQ Dulwitch SA 5065 Dear Sir, Re: PROPOSED ALTERATIONS TO UNIT 2, “BELLE DE JOUR” 24 EDGAR BENNETT AVENUE, NOOSA HEADS | understand that you would like to relocate the external wall between the Study and the rear patio out into the patio area so that the new wall location would be in line with the rear wall of the adjacent bedroom. | undertook the original design of the building and have re-familiarised myself with the design using my original structural drawings. The wall is not a major supporting wall and can be removed and relocated without affecting the structural integrity of the building. The wall incorporates a sliding door and there appears to be a beam over the door. This beam is constructed from concrete block and can also be removed without affecting the structural integrity of the building. The patio area is higher than the finished internal floor. This difference in level has been created using a non-structural concrete topping and can be safely removed to ensure the new internal area is the same level as the current internal floor. It should be noted that underneath the existing sliding door location there is a concrete hob constructed integrally with the main structural slab. This hob is not structural and can also be removed. However, | would advise that a similar hob be constructed under the new location of the wall and door, with the new hob being well bonded to the existing slab and the finished hob and adjacent external surface treated with a suitable waterproof membrane before applying floor finishes and installing the door. Please contact me if you require any further assistance. CPEng; MiEAust, RPEQ Suite 16, Tewantin Plaza 113 Poinciana Avenue Tewantin PO Box 205 Tewantin Q. 4565 tel 07 5449 7137 fax 07 5449 7172 [email protected]
Page 4
FOOTING LAYQUT: =~. F \ \ \ | 58 585 5 59:5
Page 5
~ etek 125 SLAB v F72 TOP visitar | I j ce SD | a C LEVEL | SLAB LAYOUT carpark) 1:100 \¢? SS ; I NOTE:Heavily water and bona subgrade \ ~ r- t | 41 . bh! PEM — ConcRetTe COLUMNS Ea — comers oosxs WITH ADDITIONAL Reimroree Met.
Page 6
2 rc---c Ip F %* - Y12 a 300 TOP REINFORCEMENT 1.100 ED ~ concrete cavum GO -comceset] Giack ww ARO MTIGNaL REIN Foot
Page 7
ch OVER Lay 2NO) 1sT LAY STARS ArNe ESS REImrOoecemMenT SEE :- 26é/eo-'i- BOTTOM REINFORCEMENT ::100 LEVEL 2 SLAB LAYOUT (units 1&2) a -Y12 a 300 Ga -—- comceret BI - comcrere ADO MONA!
Used in these records
Attachment 3 - Engineering Report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 844 KB (small file)
- File type
No other editions are linked here.