Attachment 3 - Engineering Report · 51994.1391.01

of 7

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

21 November 2022                            Job Number 22080



BY EMAIL

Janine Mason

2/24 Edgar Bennet Ave, Noosa Heads

Email:                     [email protected]

Dear Janine

RE  PROPOSED WALL RELOCATION AT 2/24 EDGAR BENNET AVE, NOOSA
HEADS
Ms Janine Mason requested that Sunshine Coast Structural Engineers (SCSE) complete a structural
inspection and provide structural advice as an RPEQ Engineer with regards to the proposed wall
relocation as part of a room extension at 2/24 Edgar Bennet Ave, Noosa Heads.

The proposed works consists of removing the existing wall to the rear balcony area from the study
and reinstating a proposed wall approximately 1600mm further into the balcony area. The proposed
works have been documented by JMF Design drawings Project Number Edgar Bennet 2022 dated
9/11/22.

SCSE was also provided with the original structural design drawings and a letter of review by the
original design Engineer of the building, Mr John Norden of John Norden & Associates dated 2/7/09.
The building drawings and letter of review by Mr John Norden have been attached to this document
for reference. SCSE understands that Mr John Norden has now retired and as such cannot provide
further input on the matter.

A visual inspection of the unit was carried out by Mr Blake Scriven of SCSE on 15th November 2022.
A photograph of the proposed location has been provided in the below Figure 1.




                                             Figure 1 – Proposed Wall to be Relocated
Sunshine Coast Structural Engineers
ABN 22 868 850 836
[email protected]
www.sunshinecoaststructuralengineers.com
Full text of the other 6 pages

Page 2

Based on a visual inspection of the building, a review of the original building design drawings and a
review of the letter provided by the original design Engineer of the building, SCSE advises that
removing this wall will not have an adverse impact on the original structural design intent of the
building relevant to this location.

SCSE understands the proposed new wall is to be a double cavity 90/90 brick wall. SCSE advises that
provided this wall is constructed in accordance with the relevant Australian Standards, NCC and BCA
requirements suitable to that of an N2 wind location (after taking into account shielding
considerations), that the construction of this new wall in the location as shown in the below Figure 2
will not have an adverse impact on the original structural design intent of the building relevant to
this location.




                                            Figure 2 - Proposed Wall Location

SCSE advises that the brick cavity wall is to have medium duty wall ties between the veneers with a
maximum vertical spacing of 600mm and a maximum horizontal spacing of 450mm. The wall ties are
also to be fixed into the floor, soffit of the slab over and adjacent wall ends to adequately restrain
the edges of the wall.

SCSE also advises that a 200x10 traditional ‘T’ bar Galintel is required over the door opening. Both
the wall ties and Galintel are to be installed in accordance with the manufacturer’s specifications and
recommendations.

SCSE has not carried out any further review of the building design then directly applicable for the
above review and has not carried out an dilapidation survey of the existing building.

Please feel free to contact the aforementioned should you wish to discuss any of this further.



Yours sincerely



Blake Scriven
Director
BEng (First Class Hons) RPEQ MIEAust

Sunshine Coast Structural Engineers
ABN 22 868 850 836
[email protected]
www.sunshinecoaststructuralengineers.com

Page 3

RABRINK PTY LTD trading as

John Norden
July 2, 2009 & Associates

Structural / Civil Design Engineers

ABN 47 312 012 117

our ref: 09/46

Mr Z Kivior John Norden
39 Swift Avenue CPEng, MIE Aust, RPEQ
Dulwitch

SA 5065

Dear Sir,

Re: PROPOSED ALTERATIONS TO UNIT 2, “BELLE DE JOUR”
24 EDGAR BENNETT AVENUE, NOOSA HEADS

| understand that you would like to relocate the external wall between the Study and
the rear patio out into the patio area so that the new wall location would be in line
with the rear wall of the adjacent bedroom.

| undertook the original design of the building and have re-familiarised myself with
the design using my original structural drawings. The wall is not a major supporting
wall and can be removed and relocated without affecting the structural integrity of
the building. The wall incorporates a sliding door and there appears to be a beam
over the door. This beam is constructed from concrete block and can also be
removed without affecting the structural integrity of the building.

The patio area is higher than the finished internal floor. This difference in level has
been created using a non-structural concrete topping and can be safely removed to
ensure the new internal area is the same level as the current internal floor. It should
be noted that underneath the existing sliding door location there is a concrete hob
constructed integrally with the main structural slab. This hob is not structural and
can also be removed. However, | would advise that a similar hob be constructed
under the new location of the wall and door, with the new hob being well bonded to
the existing slab and the finished hob and adjacent external surface treated with a
suitable waterproof membrane before applying floor finishes and installing the door.

Please contact me if you require any further assistance.

  

CPEng; MiEAust, RPEQ

Suite 16, Tewantin Plaza
113 Poinciana Avenue Tewantin
PO Box 205 Tewantin Q. 4565

tel 07 5449 7137
fax 07 5449 7172
[email protected]

Page 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FOOTING LAYQUT: =~.

F
\ \ \ |
58 585 5 59:5

Page 5

~ etek

 

 

 

125 SLAB v
F72 TOP

 

 

 

 

 

 

 

visitar

 

|
I
j ce SD | a C

 

 

 

 

 

 

 

 

LEVEL | SLAB LAYOUT carpark) 1:100

 

 

 

\¢?

 

SS ;
I NOTE:Heavily water and bona subgrade

\ ~ r- t |
41 . bh!

PEM — ConcRetTe COLUMNS

Ea — comers oosxs
WITH ADDITIONAL
Reimroree Met.

 

 

Page 6

 

  

2
rc---c

Ip
F

 

 

 

 

 

 

 

 

 

 

 

 

 

%* - Y12 a 300

 

 

TOP REINFORCEMENT 1.100 ED ~ concrete cavum

GO -comceset] Giack ww
ARO MTIGNaL REIN Foot

Page 7

 

ch OVER

Lay 2NO)

 

1sT

LAY

 

 

 

STARS ArNe ESS
REImrOoecemMenT
SEE :- 26é/eo-'i-

 

 

 

 

 

 

 

 

   

BOTTOM REINFORCEMENT ::100

 

 

 

 

 

LEVEL 2 SLAB LAYOUT (units 1&2)

 

 

 

a -Y12 a 300
Ga -—- comceret
BI - comcrere

ADO MONA!

Used in these records

About this file

File size
844 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Attachment 3 - Engineering Report.pdf · 844 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.