Based on a visual inspection of the building, a review of the original building design drawings and a
review of the letter provided by the original design Engineer of the building, SCSE advises that
removing this wall will not have an adverse impact on the original structural design intent of the
building relevant to this location.
SCSE understands the proposed new wall is to be a double cavity 90/90 brick wall. SCSE advises that
provided this wall is constructed in accordance with the relevant Australian Standards, NCC and BCA
requirements suitable to that of an N2 wind location (after taking into account shielding
considerations), that the construction of this new wall in the location as shown in the below Figure 2
will not have an adverse impact on the original structural design intent of the building relevant to
this location.
Figure 2 - Proposed Wall Location
SCSE advises that the brick cavity wall is to have medium duty wall ties between the veneers with a
maximum vertical spacing of 600mm and a maximum horizontal spacing of 450mm. The wall ties are
also to be fixed into the floor, soffit of the slab over and adjacent wall ends to adequately restrain
the edges of the wall.
SCSE also advises that a 200x10 traditional ‘T’ bar Galintel is required over the door opening. Both
the wall ties and Galintel are to be installed in accordance with the manufacturer’s specifications and
recommendations.
SCSE has not carried out any further review of the building design then directly applicable for the
above review and has not carried out an dilapidation survey of the existing building.
Please feel free to contact the aforementioned should you wish to discuss any of this further.
Yours sincerely
Blake Scriven
Director
BEng (First Class Hons) RPEQ MIEAust
Sunshine Coast Structural Engineers
ABN 22 868 850 836
[email protected]
www.sunshinecoaststructuralengineers.com
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Attachment 3 - Engineering Report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 844 KB (small file)
- File type
No other editions are linked here.