Appeal judgement 30-32 Doonella St Tewantin - MCU21-0013 OPW21-0013

of 105

Page text read automatically using OCR, there may be inaccuracies

Original PDF page 9, section 1. The text section number identifies this passage in the reader.

46.   A bin wash area is required with a cold-water tap, hose and drain outlet connected to
      sewer, via a bucket trap. The drain outlet is to be designed to prevent storm water entry
      to the sewerage system which can be achieved by a bunded area, with a nib wall height
      of 100mm maximum, enclosing a wash area of 700mm x 700mm minimum (max 0.7m²).
      Alternatively, the waste area can be roofed, or any other appropriate design approved
      by Council.
      Noise
47.   Written certification is required from a suitably qualified person confirming that sound
      pressure levels from all mechanical plant and equipment comply with the following:
      a.    Air-conditioning and Refrigeration
            • 7am to 10pm: Maximum level allowable = background + 5dB(A)
            • 10pm to 7am: Maximum level allowable = background + 3dB(A)
      b.      Pumps
            • 7am to 7pm: Maximum level allowable = background + 5dB(A)
            • 7pm to 10pm: Maximum level allowable = background + 3dB(A)
            • 10pm to 7am: No audible noise.
48.   The certification must be submitted to Council, which certifies that operational noise from
      any fixed plant and equipment complies with the requirements of this Decision Notice.
      Kitchen Exhaust (Food and drink outlet)
49.   Kitchen exhaust points for the Food and drink outlet must be located and operated in
      accordance with Australian Standard AS1668.2-2002 “The use of ventilation and air-
      conditioning in buildings” (specifically Section 5.10 – Air Discharges).
50.   The development must be constructed with reticulated ducting inside the building to
      transfer kitchen exhaust fumes to a discharge point on the roof.
51.   Submission of written certification must be provided from a suitably qualified person
      confirming that the kitchen exhaust is constructed, installed and is operating in
      accordance with Australian Standard AS1668.2-2002.
52.   The assessment and certification is required immediately after installation of the
      equipment and prior to any occupation of the building, and in a format approved by
      Council.
      Outdoor Lighting Devices
53.   Lighting associated with the use must be designed, sited, installed and tested to comply
      with Table 2.1 & 2.2 of Australian Standard AS4282-1997 “Control of the obtrusive
      effects of outdoor lighting” using a control level of 1.
54.   Certification must be submitted to Council from a qualified person which certifies that all
      outdoor lighting devices comply with the requirements of this Decision Notice at the time
      of commissioning.
      For the purpose of certifying outdoor lighting devices for the development, a qualified
      person is:
      a.    a Registered Professional Engineer of Queensland;
      b.    an environmental or electrical design consultant with a minimum of 3 years current
            experience in the field of outdoor lighting.




                                                 7

Log in to download the original (Appeal judgement 30-32 Doonella St Tewantin - MCU21-0013 OPW21-0013.pdf)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗