SWMP Technical Memo Climate Change as submitted with Further Advice response
ENGINEERING & PROJECT SERVICES
Sunshine Coast | Brisbane
www.recor.au | ABN 89 647 469 707
Figure 1 - DRAINS climate-adjusted 1% AEP model results (Full Unsteady hydraulic model)
The upper model branch reports the pre-development discharge of 0.151 m3/s. The middle branch reports
0.197 m3/s unmitigated. The lower detained branch reports two controlled outlet components of 0.088
and 0.060 m3/s, combining to 0.148 m3/s, with zero overflow.
P0478-26-001 | Cooroy Social Housing | RFI Item 4 Page 4 of 6