Original PDF page 1, section 1. The text section number identifies this passage in the reader.

 NOOSA VILLAS
    10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                     STRUCTURAL DRAWING LIST
                                                                                                                     DRAWING No.
                                                                                                                     S000
                                                                                                                     S001
                                                                                                                     S002
                                                                                                                     S003
                                                                                                                                         DRAWING NAME
                                                                                                                                         COVER SHEET
                                                                                                                                         NOTES SHEET - SHEET 1
                                                                                                                                         NOTES SHEET - SHEET 2
                                                                                                                                         SAFETY IN DESIGN ASSESSMENT
                                                                                                                     S005                SITE PLAN
                                                                                                                     S010                MASTER MEMBER SCHEDULES
                                                                                                                     S020                TYPICAL SLAB AND FOOTING DETAILS - SHEET 1
                                                                                                                     S021                TYPICAL SLAB AND FOOTING DETAILS - SHEET 2
                                                                                                                     S022                TYPICAL SLAB AND FOOTING DETAILS - SHEET 3
                                                                                                                     S023                TYPICAL SLAB AND FOOTING DETAILS - SHEET 4
                                                                                                                     S030                TYPICAL CONCRETE WALL DETAILS
                                                                                                                     S040                TYPICAL CONCRETE COLUMN SECTIONS AND DETAILS
                                                                                                                     S050                TYPICAL MASONRY DETAILS
                                                                                                                     S060                TYPICAL RETAINING WALL DETAILS
                                                                                                                     S070                TYPICAL FRAMING DETAILS - SHEET 1
                                                                                                                     S071                TYPICAL FRAMING DETAILS - SHEET 2
                                                                                                                     S080                TYPICAL BRACING WALL DETAILS
                                                                                                                     S100                K1, K2 & K3 VILLA BASEMENT GENERAL ARRANGEMENT PLAN
                                                                                                                     S105                K1, K2 & K3 VILLA BASEMENT SECTIONS - SHEET 1
                                                                                                                     S106                K1, K2 & K3 VILLA BASEMENT SECTIONS - SHEET 2
                                                                                                                     S110                K1, K2 & K3 VILLA GROUND FLOOR GENERAL ARRANGEMENT PLAN
                                                                                                                     S111                K1, K2 & K3 VILLA GROUND FLOOR BOTTOM REINFORCEMENT PLAN
                                                                                                                     S112                K1, K2 & K3 VILLA GROUND FLOOR TOP REINFORCEMENT PLAN
                                                                                                                     S115                K1, K2 & K3 VILLA GROUND FLOOR SECTIONS
                                                                                                                     S120                K1, K2 & K3 VILLA UPPER FLOOR GENERAL ARRANGEMENT PLAN
                                                                                                                     S121                K1, K2 & K3 VILLA UPPER FLOOR BOTTOM REINFORCEMENT PLAN
                                                                                                                     S122                K1, K2 & K3 VILLA UPPER FLOOR TOP REINFORCEMENT PLAN
                                                                                                                     S125                K1, K2 & K3 VILLA UPPER FLOOR SECTIONS
                                                                                                                     S130                K1, K2 & K3 VILLA ROOF FRAMING PLAN
                                                                                                                     S131                K1, K2 & K3 VILLA ROOF BOTTOM & TOP REINFORCEMENT PLANS
                                                                                                                     S135                K1, K2 & K3 VILLA ROOF SECTIONS
                                                                                                                     S200                K4, K5 & K6 VILLA GROUND FLOOR GENERAL ARRANGEMENT PLAN
                                                                                                                     S205                K4, K5 & K6 VILLA GROUND FLOOR SECTIONS - SHEET 1
                                                                                                                     S206                K4, K5 & K6 VILLA GROUND FLOOR SECTIONS - SHEET 2
                                                                                                                     S207                K4, K5 & K6 VILLA GROUND FLOOR SECTIONS - SHEET 3
                                                                                                                     S210                K4, K5 & K6 VILLA UPPER FLOOR GENERAL ARRANGEMENT PLAN
                                                                                                                     S211                K4, K5 & K6 VILLA UPPER FLOOR BOTTOM REINFORCEMENT PLAN
                                                                                                                     S212                K4, K5 & K6 VILLA UPPER FLOOR TOP REINFORCEMENT PLAN
                                                                                                                     S215                K4, K5 & K6 VILLA UPPER FLOOR SECTIONS
                                                                                                                     S220                K4, K5 & K6 VILLA ROOF FRAMING PLAN
                                                                                                                     S221                K4, K5 & K6 VILLA ROOF BOTTOM & TOP REINFORCEMENT PLANS
                                                                                                                     S225                K4, K5 & K6 VILLA ROOF SECTIONS
                                                                                                                     S300                N1 & N2 VILLA LOWER FLOOR GENERAL ARRANGEMENT PLAN
                                                                                                                     S305                N1 & N2 VILLA LOWER FLOOR SECTION
                                                                                                                     S310                N1 & N2 VILLA GROUND FLOOR GENERAL ARRANGEMENT PLAN
                                                                                                                     S311                N1 & N2 VILLA GROUND FLOOR BOTTOM REINFORCEMENT PLAN
                                                                                                                     S312                N1 & N2 VILLA GROUND FLOOR TOP REINFORCEMENT PLAN
                                                                                                                     S315                N1 & N2 VILLA GROUND FLOOR SECTIONS
                                                                                                                     S320                N1 & N2 VILLA UPPER FLOOR GENERAL ARRANGEMENT PLAN
                                                                                                                     S321                N1 & N2 VILLA UPPER FLOOR BOTTOM REINFORCEMENT PLAN
                                                                                                                     S322                N1 & N2 VILLA UPPER FLOOR TOP REINFORCEMENT PLAN
                                                                                                                     S325                N1 & N2 VILLA UPPER FLOOR SECTIONS
                                                                                                                     S330                N1 & N2 VILLA ROOF GENERAL ARRANGEMENT PLAN
                                                                                                                     S331                N1 & N2 VILLA ROOF BOTTOM REINFORCEMENT PLAN
                                                                                                                     S332                N1 & N2 VILLA ROOF TOP REINFORCEMENT PLAN
                                                                                                                     S335                N1 & N2 VILLA ROOF SECTIONS
                                                                                                                     Grand total: 56




                                                                                                                                                                   INFORMATION
                                                                                                                                                                       NOT FOR CONSTRUCTION
                                                                                     Client                              Status                                Title
                                                                                      MARK BAIN                           INFORMATION
                                                                                                                                                               COVER SHEET
                                                                                     Drawn By         Designed By        Approved By
                                                                                       JAL              JM                JO
                                                                                     Project No.      Discipline         Scale

                                                        [email protected]       20220173         STRUCTURAL                               (at A1)

                                                                                     Project Name
                                                        37 MARY ST NOOSAVILLE, QLD                                                                             Drawing No.                                      Revision
1     04.11.22 ISSUE FOR INFORMATION       JAL   JO                                   NOOSA VILLAS
                                                        07 5211 1003                                                                                            S000                                             1
Rev     Date   Description                 By    Chk                                  10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                  FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm
Full text of sections 2 to 11 (of 56)

Section 2

                                                                                                 CONCRETE NOTES                                                                       CONCRETE NOTES CONT.                                                                     STRUCTURAL STEEL NOTES                                                              STRUCTURAL STEEL NOTES CONT.
      GENERAL NOTES                                                                              C1   ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 3600 CURRENT       C29 ALL UNREINFORCED MASONRY WALLS ARE TO BE SEPARATED FROM ABUTTING                     S1 DESIGN CONFORMS TO AS 4100. FABRICATION & ERECTION SHALL BE CARRIED OUT IN        S20 FOR EACH GROUP OF ANCHOR BOLTS PROVIDE A TEMPLATE WITH SETTINGS OUT
       G1.     THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL ARCHITECTURAL AND                 EDITION WITH AMENDMENTS. ALL CONCRETE SHALL BE PLACED AND CURED IN                  CONCRETE WITH TWO LAYERS OF SUPER ALCOR.                                                ACCORDANCE WITH THE PROVISIONS OF AS 4100.                                            LINES CLEARLY MARKED FOR POSITIONING THE BOLTS WHEN CASTING IN
               OTHER CONSULTANTS DRAWINGS AND SPECIFICATIONS AND WITH SUCH OTHER                      ACCORDANCE WITH SECTION 19 AS 3600 WHERE CURING COMPOUND IS USED IT MUST BE
               WRITTEN INSTRUCTIONS AS MAY BE ISSUED DURING THE COURSE OF THE CONTRACT.               APPLIED: (A) ONTO SLABS WITHIN 2 HOURS OF FINISHING OPERATION. (B) ONTO WALLS   C30 MASONRY WALLS NOT COINCIDING WITH LOAD BEARING WALLS UNDER MUST NOT BE               S2 UNLESS NOTED OTHERWISE, ALL STEEL SHALL CONFORM WITH THE FOLLOWING                S21 GALVANISING SHALL BE TO AS 4680 (MEMBERS) OR AS 1214
               ALL DISCREPANCIES SHALL BE REFERRED TO THE ARCHITECT OR SUPERINTENDENT FOR             AND COLUMNS IMMEDIATELY AFTER REMOVAL OF FORMWORK (NB PVA CURING                    BUILT ON CONCRETE SLABS OR BEAMS UNTIL FORMWORK SUPPORTING SAME HAS                     AUSTRALIAN STANDARDS IN RESPECT OF GRADE & CONDITIONS OF SUPPLY
               DECISION BEFORE PROCEEDING WITH THE WORK.                                              COMPOUND IS NOT ACCEPTABLE, USE WAX OR RESIN EMULSION, POLYTHENE SHEETING           BEEN REMOVED. DISTRIBUTE MASONRY ON SLAB PRIOR TO CONSTRUCTING WALLS.                                                                                                            THREADED FASTENERS
                                                                                                      OR CONTINUOUS SPRAYS.) HORIZONTAL FORMWORK SHALL BE STRIPPED WHEN                                                                                                               ROLLED SECTIONS:            AS3679.1GRADE 300                                        COATING MASS: AVERAGE - 600 GRAMS PER SQ. METRE
       G2.     ALL DIMENSIONS RELEVANT TO SETTING OUT AND OFF SITE WORK SHALL BE VERIFIED             APPROVED BY THE ENGINEER.                                                       C31 FIRST SLAB BAR IS TO BE POSITIONED MAX 100mm FROM FACE OF BEAMS, R.C.C WALLS                WELDED SECTIONS:            AS3679.2GRADE 300
               BY THE CONTRACTOR BEFORE CONSTRUCTION AND FABRICATION IS COMMENCED. THE                                                                                                    AND SLAB THICKENINGS PARALLEL TO BAR. FIRST BEAM TIE TO BE PLACED MAXIMUM                   FLAT BARS:                  AS3679.1GRADE 300                                        MEMBERS
               ENGINEER'S DRAWINGS SHALL NOT BE SCALED. SEE ARCHITECTURAL DRAWINGS FOR           C2   LAPS TO REINFORCEMENT:                                                              50mm FROM FACE OF COLUMN OR SUPPORTING WALL UNDER.                                          PLATE/FLOOR PLATE:          AS3678GRADE 250                                          COATING MASS: MINIMUM - 550 GRAMS PER SQ. METRE
               ALL RELEVANT DIMENSIONS.                                                                  BAR           SLABS & WALL           BEAMS                                                                                                                                   HOLLOW SECTIONS             AS1163GRADE C300
                                                                                                         N12               550             700                                        C32 THE SUB CONTRACTOR SHALL GIVE AT LEAST 24 HOURS NOTICE SO THAT INSPECTION                   PURLINS & GIRTS             AS1397G450 Z350                                   S22 PROVIDE SURVEY CERTIFICATES RELATING TO ERECTED STEELWORK THAT CONFIRM
       G3.     DURING CONSTRUCTION THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING                   N16               750             950                                            MAY BE MADE OF THE FOLLOWING:                                                                                                                                                 THAT TOLERANCES COMPLY WITH SECTION 15 OF AS 4100.
               THE STRUCTURE IN A STABLE CONDITION AND ENSURING NO PART SHALL BE OVER                    N20               950             1300                                            - MEMBRANE INSTALLATION THE SUB BASE (WHERE APPLICABLE)                                 COPIES OF TEST CERTIFICATES CONFIRMING CONFORMANCE TO THE ABOVE
               STRESSED UNDER CONSTRUCTION ACTIVITIES.                                                   N24              1200              1550                                           - REINFORCEMENT & TENDONS FIXED IN PLACE                                                STANDARDS AND GRADES ISSUED BY SUPPLIER OF THE STEEL SHALL BE SUPPLIED TO        S23 REMOVE ALL TEMPORARY CLEATS ON COMPLETION AND RESTORE THE SURFACE IN
                                                                                                         N28              1450              1900                                           - CORES & EMBEDMENTS FIXED IN PLACE                                                     RECOR CONSULTING.                                                                    AN APPROVED MANNER.
       G4.     WHERE EXCAVATION WORK IS TO BE CARRIED OUT ADJACENT TO EXISTING FOOTINGS.                 N32              1700              2300                                           - NO CONCRETE SHALL BE PLACED UNTIL INSPECTION IS COMPLETED
               THE EXACT LEVEL OF THE UNDERSIDE OF THE FOOTING SHALL BE OBTAINED BY TEST                                                                                                                                                                                       S3 MEMBER SIZES SHALL BE AS SHOWN ON THE STRUCTURAL DRAWINGS.                        S24 GROUT UNDER ALL BASE PLATES. BEFORE GROUTING, SUPPORT BASE PLATES ON
               PITS PRIOR TO EXCAVATION UNDERPINNING AND SHORING OF THE STRUCTURE SHALL                8TM                 450                                                        C33 CONSTRUCTION SUPPORT PROPPING SHALL BE LEFT IN PLACE AS REQUIRED IN ORDER               NO SUBSTITUTION IS PERMITTED WITHOUT AGREEMENT OF RECOR CONSULTING.                   STEEL PACKERS OR WEDGES. GROUT UNDER BASE PLATES AND INTO CORED HOLES
               BE CARRIED OUT AS DETAILED AND THE EXISTING STRUCTURE SHALL BE MAINTAINED IN            11TM                 650                                                           TO AVOID OVERSTRESSING A COMPLETED FLOOR DUE TO CONSTRUCTION LOADING. ALL                                                                                                     WITH CONBEXTRA GP NON-SHRINK GROUT OR EQUIVALENT, MINIMUM COMPRESSIVE
               A STABLE AND UNDAMAGED              CONDITION.                                                                                                                             BACK PROPPING SHALL BE APPROVED BY RECOR CONSULTING.                                 S4 THE CONTRACTOR SHALL PREPARE WORKSHOP (SHOP DETAIL) DRAWINGS AND SHALL                STRENGTH 20MPa,MIN. THICKNESS 15mm, MAX. THICKNESS 40mm
                                                                                                 C3   CONCRETE STRENGTH GRADE & COVER FOR PARTICULAR ELEMENTS SHALL BE AS                                                                                                         SUBMIT EITHER AN ELECTRONIC PDF FILE OR TWO HARD COPIES OF EACH DRAWING FOR
       G5.     ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH THE RELEVANT                 FOLLOWS UNLESS NOTED OTHERWISE:                                                 C34 IF PLASTIC SHRINKAGE OF THE CONCRETE IS OBSERVED DUE TO RAPID DRYING OR                 EXAMINATION OF CONNECTION DETAILS. FABRICATION SHALL NOT COMMENCE UNTIL           S25 STRUCTURAL STEEL TO BE CONCRETE ENCASED SHALL BE UNPAINTED AND
               CURRENT S.A.A. CODES (INCLUDING ALL AMENDMENTS) AND THE LOCAL STATUTORY                                                                                                    OTHER CONDITIONS, APPLY A SINGLE SPRAY COAT OF ALIPHATIC ALCOHOL                        THE WORKSHOP DRAWINGS HAVE BEEN REVIEWED, A REVIEW WILL BE PROVIDED FOR               WRAPPED WITH SL41 FABRIC. THE GAP BETWEEN THE STRUCTURAL STEEL AND THE
               AUTHORITIES REQUIREMENTS. EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.                 ELEMENT                       COVER         CONCRETE STRENGTH GRADE               EVAPORATION RETARDANT ("MASTERKURE 111CF-CONFILM" BY MASTER BUILDERS OR                 MEMBER SIZES AND CONNECTION DETAILS, BUT WILL NOT EXTEND TO DIMENSIONS. ALL           FABRIC SHALL BE 25mm. THE MINIMUM COVER TO THE FABRIC SHALL BE 50mm.
                                                                                                        FOOTINGS                      50mm                   25 MPa                       EQUAL APPROVED) IMMEDIATELY AFTER SCREEDING. NOTE: "CONFILM" IS NOT A CURING            DIMENSIONS AND SETOUTS SHALL BE OBTAINED FROM ARCHITECTURAL DRAWINGS.
       G6.     ALL DIMENSIONS ARE IN MILLIMETERS UNLESS STATED OTHERWISE. ALL LEVELS ARE                SLAB ON GROUND                30mm                   32 MPa                       COMPOUND.                                                                               SHOULD VARIATIONS BE NECESSARY TO THE STRUCTURAL DETAILS PROVIDED, THESE          S26 ROOF AND/OR WALL SHEETING SHALL BE FIXED TO PURLINS OR GIRTS IN
               EXPRESSED IN METRES.                                                                     SUSPENDED SLAB - INTERNAL     30mm                   40 MPa                                                                                                               SHALL BE REFERRED TO RECOR CONSULTING FOR APPROVAL BEFORE BEING INCLUDED              ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
                                                                                                        SUSPENDED SLAB - EXTERNAL     40mm                   40 MPa                   C35 LOW HEAT CONCRETE SHALL BE USED FOR ALL BEAMS THAT ARE DEEPER THAN 700mm                ON SHOP DETAIL DRAWINGS. SHOP DETAILS SHALL PROVIDE FOR FIXING OR SUPPORT
       G7.     CONSTRUCTION OF ANY MASONRY WALLS OR OTHER PERMANENT LOADING MUST NOT                                                                                                      AND HAVE A WIDTH GREATER THAN 1200mm. LOW HEAT CONCRETE SHALL BE TESTED IN              OF ANY BUILDING ELEMENTS SHOWN ON ARCHITECTURAL DRAWINGS. SHOULD                  S27 ALL SUNDRY ITEMS SUCH AS GUTTER SUPPORTS, CEILING AND ARCHITECTURAL
               BE BUILT ON CONCRETE SLABS OR BEAMS UNTIL FORMWORK SUPPORTING SAME HAS                   MAX. AGGREGATE SIZE = 20mm SLUMP = 100mm +/- 15mm                                 ACCORDANCE WITH AS 1012 METHOD 22 PART B SEMI-ADIABATIC TEMPERATURE RISE                VARIATIONS BE NECESSARY TO THE STRUCTURAL DETAILS PROVIDED, THESE SHALL BE            ELEMENTS, FIXTURES ARE TO BE ALLOWED FOR IN THE PRICING BY THE TENDERER
               BEEN REMOVED. HOWEVER PROPS AND FORMWORK SHALL NOT BE REMOVED BEFORE                     (AT POINT OF DISCHARGE)                                                           OF CONCRETE. THE TEMPERATURE RISE IS TO BE LESS THAN 30°C. TRIAL MIXES WITH             REFERRED TO RECOR CONSULTING FOR APPROVAL BEFORE BEING INCLUDED ON SHOP               AS PER ARCHITECT'S DETAILS.
               THE MINIMUM TIME SPECIFIED. DISTRIBUTE    MASONRY EVENLY ON SLAB ADJACENT                                                                                                  TEST RESULTS ARE TO BE SUBMITTED FOR APPROVAL. LOW HEAT CONCRETE IS TO                  DETAIL DRAWINGS. SHOP DETAILS SHALL PROVIDE FOR FIXING OR SUPPORT OF ANY
               TO ITS FINAL POSITION PRIOR TO CONSTRUCTING WALLS.                                C4   MIX DESIGNS SHALL BE SUBMITTED FOR APPROVAL. THE USE OF BLENDED CEMENTS,            HAVE A DELIVERY TEMPERATURE OF LESS THAN 27°C. SECTIONS CAST WITH LOW HEAT              BUILDING ELEMENTS SHOWN ON ARCHITECTURAL DRAWINGS.                                S28 THE BUILDER SHALL PROVIDE ALL CLEATS AND HOLES FOR FIXING STEEL TO STEEL,
                                                                                                      FLYASH AND/OR CHEMICAL ADMIXTURES WILL NOT BE PERMITTED EXCEPT WITH PRIOR           CONCRETE ARE TO BE INSULATED BY USING PLYWOOD FORMWORK WHICH IS TO                                                                                                            TIMBER TO STEEL AND TIMBER TO TIMBER. AS REQUIRED BY ENGINEERING AND
       G8.     ALL NON LOAD BEARING WALLS SHALL BE KEPT CLEAR OF THE UNDERSIDE OF SLABS               APPROVAL OF RECOR CONSULTING IN WRITING. IF FLYASH IS USED WITH APPROVAL            REMAIN IN PLACE FOR A MINIMUM OF 5 DAYS AFTER PLACING. ALSO THE TOP SURFACE                                                                                                   ARCHITECTURAL INTENT WHETHER SHOWN OR NOT.
                                                                                                                                                                                                                                                                                      SHOP DETAIL DRAWINGS SHALL CLEARLY INDICATE:
               AND BEAMS BY 20mm UNLESS OTHERWISE SHOWN.                                              THEN THIS SHOULD NOT EXCEED 80KG/PER cu. m. CONCRETE AGGREGATE SHALL                OF THE BEAM IS TO BE INSULATED WITH TWO SHEETS OF FORMPLY OR SIMILAR                         : DIMENSIONS OF ITEMS, IDENTIFICATION, STEEL GRADE
                                                                                                      CONSIST OF CRUSHED RIVER GRAVEL OR BASALT IN ACCORDANCE WITH AS 2758.1. SLAG        APPROVED MATERIAL FOR A PERIOD OF 5 DAYS.                                                    : PROCEDURES NECESSARY FOR SHOP AND SITE ASSEMBLY                            S29 ALL STRUCTURAL STEELWORK BELOW GROUND TO BE ENCASED BY N25 75mm ALL
       G9.     REFER ARCHITECT'S DRAWINGS FOR ANY DEMOLITION REQUIREMENTS.                            AGGREGATES WILL NOT BE PERMITTED. CALCIUM CHLORIDE WILL NOT BE PERMITTED                                                                                                                                                                                          ROUND U.N.O.
                                                                                                                                                                                                                                                                                       : LOCATION, TYPE AND SIZE OF WELDS AND BOLTS
                                                                                                      AND SHALL NOT BE USED UNDER ANY CIRCUMSTANCE.                                                                                                                                    : ORIENTATION OF MEMBERS
                  DESIGN CRITERIA                                                                                                                                                                                                                                                                                                                                   S30 FOR GALVANISED COATINGS, REPAIR FIELD DAMAGE AND SITE WELDS WITH TWO
                                                                                                                                                                                                                                                                                       : CAMBER OR PRESET (IF ANY)
                  LIVE LOADS                                                                     C5   PROJECT ASSESSMENT SHALL BE IN ACCORDANCE WITH AS 1379 & AS 3600. ALL           TIMBER NOTES                                                                                     : LOCATION OF TEMPORARY CONNECTIONS AND BRACING                                  COATS OF A TWO PACK EPOXY POLYAMIDE ZINC-RICH PAINT CONTAINING A MINIMUM
                  ROOF                                0.25kPa                                         ORGANISATIONS RESPONSIBLE FOR TESTING AND ASSESSMENT OF CONCRETE AND            T1    ALL TIMBER FRAMING TO BE MIN. H3 TREATED. ALL HARDWOODS TO BE DURABILITY                                                                                                    OF 92% ZINC DUST IN THE DRY FILM WHICH SHALL BE BUILT UP TO 0.075mm MINIMUM.
                                                                                                                                                                                                                                                                                       : SURFACE PREPARATION METHOD AND COATING SYSTEM
                  INTERNAL FLOORS                     1.5kPa                                          CONCRETE MATERIALS SHALL BE NATA REGISTERED. SAMPLING AND TESTING SHALL BE            CLASS 1.                                                                                   : WELDING AND BOLTING CATEGORIES
                  BATHROOMS                           2.0kPa                                          TO AS 1012. ACCEPTANCE CRITERIA - AVERAGE MUST EXCEED REQUIRED VALUE, NO        T2    EXPOSED FRAMING                                                                                                                                                         S31 FOR PAINT COATINGS, REPAIR FIELD DAMAGE AND SITE WELDS USING THE SAME
                  BALCONIES                           2.0kPa                                          SAMPLE TO BE LESS THAN 85% OF REQUIRED VALUE. SUBMIT TEST RESULTS OF PROJECT          (EXPOSED FRAMING REFERS TO ALL TIMBER FRAMING THAT MAY BE SUBJECT TO               S5 ALL WELDING SHALL BE CARRIED OUT IN ACCORDANCE WITH AS 1554.1. ELECTRODES             PARENT COATING SYSTEM. SUCCESSIVE PAINT LAYERS SHALL BE ABRADED TO A
                                                                                                      ASSESSMENT TO RECOR CONSULTING.                                                       PERIODIC WETTING)                                                                     SHALL BE TO AS 1553, AS1858 AS 2203 OR AS 2717 AS APPROPRIATE. WELDS FOR              FEATHERED EDGE OF APPROXIMATELY 25mm WIDTH PER LAYER. MECHANICALLY
                  WIND LOADS                                                                                                                                                                         - ALL EXPOSED FRAMING TO BE EITHER H3 PRESSURE TREATED OR DURABILITY                                                                                               GRIND SURFACES TO ACHIEVE SMOOTH AND BRIGHT METAL COMPARABLE TO CLASS
                                                                                                                                                                                                                                                                                  STRUCTURAL CONNECTIONS SHALL BE WELD CATEGORY SP UNLESS NOTED OTHERWISE
                  REGION                              B1                                         C6   SUPPLY OF READY MIXED CONCRETE SHALL COMPLY WITH AS 1379.                                        CLASS 1 (MINIMUM) SAWN TIMBER (U.N.O.)                                                                                                                           2.5. PAINT REINSTATEMENT SHALL FULLY COVER THE FEATHERED PART OF THE SAME
                  TERRAIN CATEGORY                    2.5 (N); 3 (S, E, W)                                                                                                                           - FRAMING MEMBERS EXPOSED TO MOISTURE (JOISTS, BEARERS, ETC.) ARE TO      S6 UNLESS OTHERWISE SHOWN, ALL CONNECTIONS SHALL BE AS SHOWN IN                          LAYER.
                  IMPORTANCE LEVEL                    2                                          C7   ALL CONCRETE SHALL BE MOISTURE CURED FOR (7) DAYS AFTER POURING, BY AN                           BE MALTHOID CAPPED AND PENETRATING NAILS SHOULD BE CONSTRUCTED TO          "STANDARDISED STRUCTURAL CONNECTIONS" PUBLISHED BY AUSTRALIAN STEEL
                  REGIONAL WIND SPEED                 V500(57m/s)                                     APPROVED METHOD.                                                                                 LIMIT MOISTURE PENETRATION ALONG NAIL SHANK.                                                                                                                 S32 ALL CANTILEVER MEMBERS TO BE PROPPED UNTIL FULLY FIXED AT SUPPORTS
                                                                                                                                                                                                                                                                                  INSTITUTE. FOR CONNECTIONS, WHERE NO STRUCTURAL DETAIL IS PROVIDED, 2/M20
                  Mz-CAT                              0.83                                                                                                                                           - MANUFACTURED TIMBER PRODUCTS, IF SPECIFIED, ARE TO BE MINIMUM H3           BOLTS IN 8.8/S CATEGORY SHALL BE USED AND ALL WELDS SHALL BE 6mm CONTINUOUS
                  Ms-SHIELDING                        1.0                                        C8   ALL FORMWORK SHALL CONFORM TO AS3610 (RESHORING NOT PERMITTED).                                  TREATED AND PROTECTED IN ACCORDANCE WITH MANUFACTURER'S                    FILLET WELDS USING E48XX ELECTRODES OR EQUIVALENT AND ALL CLEAT PLATES AND
                  Mt-TOPOGRAPHIC                      1.0                                                                                                                                              SPECIFICATION ( EG HYNE TECH DATA SHEETS 6 AND 8). USE A HIGH QUALITY
                  Vz (ULT)                            46m/s (N); 50m/s (S, E, W)                 C9   REINFORCEMENT SYMBOLS
                                                                                                                                                                                                                                                                                  STIFFENERS SHALL BE 10mm THICK.                                                  SCREW PILES
                                                                                                                                                                                                       EXTERIOR PAINT FINISH TO EXPOSED SURFACES.
                                                                                                                                                                                      T3    ALL FASTENERS TO BE HOT DIPPED GALVANISED. EXTERNAL ANCHORS WHERE SUBJECT          S7 BOLTING CATEGORIES ARE IDENTIFIED ON THE STRUCTURAL DRAWINGS IN THE
                  EARTHQUAKE LOADS                                                                      REINFORCEMENT TYPES ARE DESIGNATED AS FOLLOWS:-                                     TO SALT AIR TO BE STAINLESS STEEL.                                                    FOLLOWING MANNER:                                                                SP1.   ALL PILES TO BE DESIGNED, MANUFACTURED AND INSTALLED BY
                  EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH                             BAR REINFORCEMENT                                                                            - NAILS TO BE 2.8 mm DIA. x 30 mm LONG.
                  AS 1170 PART 4 BASED ON THE FOLLOWING:                                                                                                                                                                                                                                                                                                                  THE PILING CONTRACTOR. ALL PILES TO BE CERTIFIED (SUPPLY
                                                                                                        'R' DENOTES ROUND STEEL BAR.                                                                 - SCREWS TO BE No.14 TYPE 17 WITH 50mm EMBEDMENT (U.N.O.)                     BOLTING CATEGORY BOLT GRADE BOLT TO         METHOD OF STD.                             FORMS 15 & 16) FOR DESIGN AND INSTALLATION BY A PRACTICING
                                                                                                        'N' DENOTES DEFORMED STEEL BAR.                                                              - ALL JOIST HANGERS, FRAMING ANCHORS AND TRIPLE GRIPS TO BE                                    AUST. STD INSTALLATION TO AS 4100                                     PROFESSIONAL ENGINEER.
                  ANNUAL PROBABILITY OF EXCEEDANCE              1:500                                   'W' DENOTES HARD DRAWN DEFORMED WIRE.                                                          MANUFACTURED BY PRYDA OR EQUIVALENT. FULLY NAILED - 4 NAILS MINIMUM.           4.6/S    4.6     AS 1111     SNUG TIGHTENED                                                 NOTE THAT INSTALLATION INCLUDES TRIMMING AND
                  PROBABILITY FACTOR, KP                        1.0                                     MESH REINFORCEMENT                                                                             INSTALL PER MANUFACTURERS SPECIFICATION.                                       8.8/S    8.8     AS 1252     SNUG TIGHTENED                                                 REMOVING OF EXCESS
                  HAZARD FACTOR, Z                              0.08                                    'SL' DENOTES SQUARE WELDED MESH.                                              T4    WASHERS TO TIMBER TO BE:                                                                  8.8/TF    8.8    AS 1252     FULLY TENSIONED                                                LENGTHS AND INSTALLING DOWEL HEAD PINS).
                  SUB-SOIL CLASS                                Ce                                      'RL' DENOTES RECTANGULAR WELDED MESH.                                                        M12 BOLTS 55 SQ. X 3 THK                                                                               FRICTION - TYPE JOINT
                  EARTHQUAKE DESIGN CATEGORY                     I                                      TRENCH MESH REINFORCEMENT                                                                    M16 BOLTS 65 SQ. X 5 THK                                                         8.8/TB    8.8     AS 1252    FULLY TENSIONED                                 SP2.   EFFECTIVE LENGTH TO BE DETERMINED BY THE DESIGNER
                                                                                                        'TM' DENOTES TRENCH MESH WITH W8 LIGS AT 600.                                 T5    ALL BOLTS ARE TO BE HEX HEAD BOLTS WITH CORRECT SIZED WASHERS. DO NOT USE                                       BEARING - TYPE JOINT                                          (MINIMUM 3m).
       G10. CONSTRUCTION USING THE STRUCTURAL DRAWINGS SHALL NOT COMMENCE UNTIL A                       REINFORCEMENT GRADES ARE DESIGNATED AS FOLLOWS:-                                    CUPHEAD BOLTS.
            CONSTRUCTION CERTIFICATE IS ISSUED BY THE PRINCIPAL CERTIFYING AUTHORITY &                  BAR REINFORCEMENT GRADE 500 - NORMAL DUCTILITY                                T6    BOLTS TO BE INSTALLED INTO PRE-DRILLED HOLES OF DIAMETER NOT EXCEEDING 10% OF          COPIES OF TEST CERTIFICATES CONFIRMING CONFORMANCE TO THE RELEVANT              SP3.   PILES TO COMPLY WITH THE FOLLOWING:
            ONLY IF THE STRUCTURAL DRAWING IS DESIGNATED "ISSUE FOR CONSTRUCTION"                       MESH REINFORCEMENT GRADE 500 - LOW DUCTILITY                                        BOLT DIAMETER.                                                                         STANDARD AND BOLT GRADE ISSUED BY THE SUPPLIER OF THE BOLTS SHALL BE                           50mm MAXIMUM DESIGN ECCENTRICITY
                                                                                                        TRENCH MESH REIN. GRADE 500 - LOW DUCTILITY                                   T7    COACH SCREWS SHALL BE SCREWED INTO PRE-DRILLED HOLES AND NOT HAMMERED.                 SUPPLIED TO RECOR CONSULTING.                                                                  50mm MAXIMUM INSTALLATION TOLERANCES
       G11. THE CONTRACTOR SHALL GIVE AT LEAST 24 HOURS NOTICE OF ANY INSPECTIONS OF                                                                                                  T8    PRE-DRILLED HOLES FOR THE SHANK SHALL NOT BE LESS THAN THE SHANK DIAMETER
            STRUCTURAL WORK THAT ARE REQUIRED TO BE MADE BY ECOR CONSULTING.                                                                                                                AND SHALL NOT EXCEED IT BY MORE THAN 1mm.                                          S8 BOLTING CATEGORIES 8.8/TF & 8.8/TB REQUIRE TENSIONING IN ACCORDANCE WITH AS
                                                                                                 C10 SIZES OF CONCRETE ELEMENTS DO NOT INCLUDE THICKNESS OF APPLIED FINISHES.                                                                                                     4100. TENSIONING SHALL BE CARRIED OUT IN ACCORDANCE WITH CLAUSE 15.2.5 OF        SP4.   ALLOW FOR A MINIMUM CORROSION RATE OF 0.02mm / YEAR.
                                                                                                                                                                                      T9    PRE-DRILLED HOLES FOR THE THREADED PORTION SHALL NOT EXCEED THE ROOT
                                                                                                                                                                                            DIAMETER OF THE SCREW.                                                                AS 4100 BY EITHER THE PART-TURN METHOD OR THE DIRECT-TENSION INDICATOR
                                                                                                 C11 BEAMS SIZES ARE SHOWN DEPTH FIRST AND INCLUDE SLAB THICKNESS                                                                                                                 METHOD. THE TORQUE-CONTROL METHOD SHALL NOT BE USED. FOR BOLTING                 SP5.   PILES TO HAVE A DESIGN LIFE OF 50 YEARS.
                                                                                                                                                                                      T10   FIXINGS SHALL BE INSTALLED TO THE DIMENSIONS SHOWN IN DETAILS. IN ANY CASE, ALL
       G.12. WATERPROOFING                                                                                                                                                                  FIXINGS SHALL BE INSTALLED WITHIN MINIMUM EDGE DISTANCES, END DISTANCES AND           CATEGORY 8.8/TF, THE CONTACT SURFACES SHALL BE FREE FROM PAINT, LACQUER,
             ALL EXTERNAL SLABS, ROOF SLABS & RETAINING WALLS SHALL HAVE A WATERPROOF            C12 UNLESS NOTED OTHERWISE ALL FORMED EDGES AND CORNERS OF CONCRETE                                                                                                              GALVANISING OR OTHER APPLIED FINISH, UNLESS NOTED OTHERWISE ON THE               SP6.   ALL PILES TO BE CONCRETE CORE FILLED WITH A MINIMUM 32MPa
                                                                                                                                                                                            SPACINGS AS PER AS1720.1 (TYPICALLY 4d, 5d AND 5d RESPECTIVELY) U.N.O.                                                                                                        CONCRETE WITH 6mm AGGREGATE. PILES TO BE CUT OFF 150mm
             MEMBRANE APPLIED TO ARCHITECT'S & CONTRACTOR'S DETAILS. THE MEMBRANE WILL               MEMBERS SHALL HAVE 20mm CHAMFERS.                                                                                                                                            STRUCTURAL DRAWINGS. CONTRACTOR TO PROVIDE CERTIFICATION FOR BOLTING
                                                                                                                                                                                      T11   TIMBER BEARERS AND JOISTS WITH D / B >= 4                                                                                                                                     ABOVE UNDERSIDE OF PILE CAP AND PILES TO BE CLOSED ENDED
             BE THE PRIMARY METHOD OF WATERPROOFING. THE MEMBRANE SHALL BE DETAILED TO                                                                                                               - PROVIDE BLOCKING OVER SUPPORTS AT 1800 MAX. CRS IN                         CATEGORY ACHIEVED AS DETAILED ON STRUCTURAL DRAWINGS.
             ACCOMMODATE MOVEMENT AT EXPANSION JOINTS.                                           C13 PLACE CONCRETE IN LAYERS SUCH THAT EACH SUCCEEDING LAYER IS BLENDED INTO                                                                                                                                                                                             TYP.
                                                                                                                                                                                                       ACCORDANCE WITH AS1684.
                                                                                                     THE PRECEDING ONE BY THE COMPACTION PROCESS. SLABS AND BEAMS SHALL BE                                                                                                     S9 UNLESS NOTED OTHERWISE, HOLES SHALL BE 2mm LARGER THAN THE NOMINAL BOLT
                                                                                                                                                                                                     - FOR JOISTS WITH SPAN > 3000 AND BOTTOM OF JOIST                                                                                                             SP7.   ALL PILES TO HAVE A MINIMUM SHEAR CAPACITY OF 10kN.
               NOTES ON ALL DRAWINGS SHALL OVER-RIDE ALL GENERAL CONSTRUCTION NOTES AS               POURED TOGETHER. THE FINISHED CONCRETE SHALL BE A DENSE HOMOGENEOUS MASS                                                                                                     DIAMETER. WHERE SLOTTED OR OVERSIZE HOLES ARE PERMITTED ON THE
                                                                                                                                                                                                       UNRESTRAINED BY CEILING DIAPHRAGM;
               OUTLINED ON THIS PAGE.                                                                COMPLETELY FILLING THE FORMWORK AND THOROUGHLY EMBEDDING THE                                                                                                                 STRUCTURAL DRAWINGS, THEY SHALL COMPLY WITH AS 4100. HAND FLAME CUTTING
                                                                                                                                                                                                              - PROVIDE 1 ROW OF BLOCKING BETWEEN EACH JOIST                                                                                                       SP8.   PROVIDE "AS BUILT" DRAWINGS WITH SURVEYED FINAL LOCATIONS.
                                                                                                     REINFORCEMENT. FINISH TYPE SHALL BE AS SPECIFIED IN THE ARCHITECTURAL                                                                                                        OF BOLT HOLES IS NOT PERMITTED. ALL BOLT HOLES SHALL BE DRILLED. BOLTS TO BE
                                                                                                                                                                                                                AT MIDSPAN FOR SPANS < 4200.
                                                                                                     DRAWINGS.                                                                                                                                                                    INSTALLED WITH A HARDENED WASHER UNDER THE TURNED PART OVER THE HOLE.
                                                                                                                                                                                                              - PROVIDE 2 ROWS OF BLOCKING BETWEEN EACH JOIST
      FOUNDATION NOTES                                                                           C14 COMPACTION:
                                                                                                                                                                                                                AT MIDSPAN FOR SPANS > 4200.
                                                                                                                                                                                                                                                                               S10 UNLESS NOTED OTHERWISE, ALL BOLTS AND WASHERS SHALL BE GALVANISED.
       F1      THESE DRAWINGS ARE TO BE READ IN CONJUNCTION WITH THE GEOTECHNICAL REPORT             USE IMMERSION AND SCREED VIBRATORS ACCOMPANIED BY HAND METHODS AS
               22380-001-Rev0 BY TECTONIC GEOTECHNICAL. REFER TO THIS REPORT FOR GROUND              APPROPRIATE TO REMOVE AIR BUBBLES AND COMPACT THE MIX. USE FORM VIBRATORS                                                                                                 S11 UNLESS NOTED OTHERWISE, A CUT SURFACE SHALL HAVE A MAXIMUM ROUGHNESS
               CONDITIONS AND FOUNDATION RECOMMENDATIONS.                                            WHERE USE OF IMMERSION VIBRATORS IS IMPRACTICABLE. ENSURE CONCRETE IS FULLY                                                                                                   NOT EXCEEDING 25 MICROMETERS. ALL CUTTING SHALL BE CARRIED OUT IN
                                                                                                     COMPACTED AND ENTRAPPED AIR REMOVED, BUT AVOID OVER VIBRATION THAT MAY                                                                                                        ACCORDANCE WITH THE RECOMMENDATIONS OF AWRA TECHNICAL NOTE 5.
                                                                                                     CAUSE SEGREGATION. DO NOT USE VIBRATORS TO MOVE CONCRETE ALONG THE FORMS
       F2      DESIGN BEARING PRESSURES                                                                                                                                                                                                                                        S12 FABRICATION TOLERANCES SHALL COMPLY WITH AS 4100, SECTION 14 UNLESS NOTED
               ALL FOOTINGS MUST BE FOUNDED A MINIMUM OF 500mm INTO MEDIUM DENSE SAND WITH       C15 EXACT SIZE AND LOCATION OF PENETRATIONS ARE TO BE OBTAINED FROM WORKSHOP                                                                                                      OTHERWISE ON THE STRUCTURAL DRAWINGS.
               AN ALLOWABLE BEARING PRESSURE OF 150kPa. REFER TO GEOTECHNICAL ENGINEER FOR           DRAWINGS PRIOR TO SCHEDULING OF REINFORCEMENT AND ARE NOT TO EXCEED
               ON SITE CERTIFICATION THE ABOVE PARAMETERS ARE ACHIEVED.                              DIMENSIONS WHERE SHOWN ON STRUCTURAL DRAWINGS.                                                                                                                            S13 ALL BEAMS AND RAFTERS SHALL BE FABRICATED AND ERECTED WITH NATURAL
                                                                                                                                                                                                                                                                                   CAMBER UP. ANY ADDITIONAL CAMBER SHALL BE AS NOTED ON THE STRUCTURAL
       F3      CERTIFICATION AND CLEANING                                                        C16 NO CHASES, HOLES GREATER THAN 150mm DIAMETER, OR EMBEDMENT OF PIPES                                                                                                           DRAWINGS. PROVIDE STRUCTURAL MEMBERS IN SINGLE LENGTHS UNLESS SPLICES
               ALL FOUNDATION MATERIAL AND BEARING CAPACITIES SHALL BE APPROVED AND                  GREATER THAN 40mm DIAMETER OTHER THAN THOSE SHOWN ON THE STRUCTURAL                                                                                                           ARE SHOWN ON THE STRUCTURAL DRAWINGS. ANY WELDED SPLICES TO MAKE UP
               CERTIFIED BY A PRACTISING QUALIFIED GEOTECHNICAL ENGINEER. THE BASES OF ALL           DRAWINGS SHALL BE MADE IN THE CONCRETE SLABS. FOR ALL OTHER CONCRETE                                                                                                          MEMBER LENGTHS SHALL BE FULL PENETRATION BUTT WELDS.
               FOOTINGS SHALL BE CLEANED AND FREE OF WATER IMMEDIATELY BEFORE INSPECTION             MEMBERS NO PENETRATION, MADE IN THE CONCRETE SLABS. FOR ALL OTHER CONCRETE
               AND PLACEMENT OF CONCRETE.                                                            MADE WITHOUT PRIOR APPROVAL BY THE STRUCTURAL ENGINEER..                                                                                                                  S14 WELDING PERSONNEL SHALL BE QUALIFIED IN ACCORDANCE WITH CLAUSE 4.12 AS
                                                                                                                                                                                                                                                                                   1554.1.
       F4      FOOTINGS SHALL BE CONSTRUCTED & BACKFILLED AS SOON AS POSSIBLE FOLLOWING          C17 CONDUITS CAST INTO CONCRETE MEMBERS SHALL BE SPACED AT MAXIMUM DISTANCE
               EXCAVATION. FOUNDATION MATERIAL SHALL NOT BE PERMITTED TO SOFTEN OR DRY OUT.          POSSIBLE AND UNDER NO CIRCUMSTANCES CLOSER THAN A CLEAR SPACING OF TWICE                                                                                                      NON-DESTRUCTIVE WELD EXAMINATION SHALL BE AS FOLLOWS:
               IF CONCRETE IS NOT PLACED IMMEDIATELY AFTER EXCAVATION OF FOOTING, PROVIDE A          THE LARGER CONDUIT DIAMETER FROM PARALLEL REINFORCEMENT OR ANY OTHER
               50mm BLINDING LAYER OF WEAK (15MPa) CONCRETE TO THE BASE OF THE EXCAVATION            CONDUIT.                                                                                                                                                                      TYPE OF WELD    EXAMINATION METHOD EXTENT (% OF TOTAL
               FOUNDATION                                                                                                                                                                                                                                                          & CATEGORY                  LENGTH OF WELD TYPE)
                                                                                                 C18 REINFORCEMENT IS SHOWN DIAGRAMMATICALLY AND NOT NECESSARILY IN TRUE
       F5      SIDES OF FOOTINGS SHALL BE FORMED AS NECESSARY WHEN EXCAVATED FACE IS NOT             PROJECTION.                                                                                                                                                                   FILLET WELD, GP/SP VISUAL INSPECTION         100
               STABLE.                                                                                                                                                                                                                                                             BUTT WELD, GP     VISUAL INSPECTION        100
                                                                                                 C19 FOR OVERSIZE PENETRATIONS REFER TO ENGINEER FOR APPROVAL                                                                                                                      BUTT WELD, SP     VISUAL INSPECTION        100
       F6      ALL WALLS AND COLUMNS SHALL BE CONCENTRIC WITH SUPPORTING FOOTINGS UNLESS             I.E PENETRATIONS THAT DON'T FIT BETWEEN REINFORCEMENT SPACING.                                                                                                                BUTT WELD, SP     RADIOGRAPHIC OR        10 SHOP WELD
               OTHERWISE NOTED ON THE DRAWINGS.                                                                                                                                                                                                                                                 ULTRASONIC INSPECTION   25 FIELD WELD
                                                                                                 C20 DO NOT CUT REINFORCEMENT ON SITE TO CLEAR PENETRATIONS. DISPLACE
       F7      UNLESS APPROVED BY THE STRUCTURAL ENGINEER, EXCAVATIONS SHALL NOT EXTEND              REINFORCEMENT SLIGHTLY AS NECESSARY TO CLEAR BLOCK OUTS AND TRIM WITH 2-N12                                                                                               S15 RADIOGRAPHIC EXAMINATION: TO AS 1554, PART 1, CLAUSE 6.3.
               BELOW A LINE DIPPING AT 45 DEGREES AND AWAY FROM THE NEAREST UNDERSIDE                BARS EACH SIDE FOR ALL PENETRATIONS <300mm                                                                                                                                    ULTRASONIC EXAMINATION: TO AS 1554, PART 1, CLAUSE 6.4.
               CORNER OF ANY FOOTINGS, RETAINING WALLS OR EXISTING BUILDINGS                                                                                                                                                                                                       TESTING SHALL BE PERFORMED BY AN INDEPENDENT TESTING AUTHORITY AND THE
                                                                                                 C21 SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN THE POSITIONS SHOWN, UNLESS                                                                                                    RELEVANT TEST REPORT SHALL BE SUBMITTED TO RECOR CONSULTING.
       F8      WHERE FOUNDATION MATERIAL DIFFERS FROM THAT DESCRIBED IN THE SITE                     APPROVED BY THE STRUCTURAL ENGINEER.
               INVESTIGATION REPORT OR LOCALISED SOFT SPOTS ARE FOUND, THE ENGINEER SHALL                                                                                                                                                                                      S16 THE SUBCONTRACTOR SHALL GIVE NOTICE OF AT LEAST 48 HOURS SO THAT
               BE NOTIFIED AND IF NECESSARY THE MATERIAL SHALL BE EXCAVATED AND BACKFILLED       C22 WELDING OF REINFORCEMENT IS NOT PERMITTED.                                                                                                                                    INSPECTION MAY BE MADE BY EITHER RECOR CONSULTING (IF REQUIRED) OR THE
               WITH WEAK MIX CONCRETE.                                                                                                                                                                                                                                             SUBCONTRACTORS NOMINATED INSPECTION ORGANISATION AT THE FOLLOWING
                                                                                                 C23 REINFORCEMENT SHALL BE BENT COLD IN ACCORDANCE WITH AS3600 EXCEPT WHERE                                                                                                       STAGES:
       F9      THE SITE IS TO BE STRIPPED AND ALL VEGETATION REMOVED FROM THE BUILDING AREA.         APPROVED BY THE STRUCTURAL ENGINEER. NO RE-BENDING SHALL BE PERMITTED.                                                                                                          : COMMENCEMENT OF WELDING PROCEDURE AND WELDER QUALIFICATIONS TESTS
               GRUB HOLES TO BE BACKFILLED IN LAYERS AS INDICATED ON NOTE BELOW.                                                                                                                                                                                                     : COMMENCEMENT OF WELDING
                                                                                                 C24 ALL REINFORCEMENT SHALL BE SECURELY SUPPORTED IN ITS CORRECT POSITION                                                                                                           : PRIOR TO THE PLACEMENT OF THE ROOT RUNS OF COMPLETE PENETRATION BUTT
       F10     FILLED BUILDING PLATFORMS SHALL BE BUILT UP IN LAYERS OF 150mm MAXIMUM DEPTH          DURING CONCRETING BY APPROVED PLASTIC TIPPED BAR CHAIRS, SPACERS OR                                                                                                           WELDS
               AND UNIFORMLY COMPACTED TO A MINIMUM OF 98% OF THE STANDARD MAXIMUM DRY               SUPPORT BARS. MAXIMUM CENTRES OF SUPPORTING CHAIRS SHALL BE 800mm FOR                                                                                                           : COMPLETION OF FABRICATION PRIOR TO SURFACE PREPARATION
               DENSITY AS RECOMMENDED IN A.S.3798 5.1. RANGE OF -4.0% TO +0.5% OF THE STANDARD       FABRIC, 600mm FOR BARS UP TO 12mm DIAMETER, 900mm FOR BARS 16mm AND GREATER.                                                                                                    : COMMENCEMENT OF SURFACE PREPARATION PRIOR TO PROTECTIVE COATING
               OPTIMUM MOISTURE CONTENT.                                                                                                                                                                                                                                             : COMPLETION OF PROTECTIVE COATING PRIOR TO DELIVERY TO SITE
                                                                                                 C25 MINIMUM LAP FOR ALL FABRICS SHALL BE ONE MESH + 30mm. U.N.O.                                                                                                                    : STEELWORK ON SITE PRIOR TO ERECTION
       F11     SITE PREPARATION : ALL EARTHWORKS TO BE CARRIED OUT IN ACCORDANCE WITH AS                                                                                                                                                                                             : COMPLETION OF ERECTION PRIOR TO ENCASING OR FIXING CLADDING
               3798 GUIDELINES ON EARTHWORKS FOR COMMERCIAL AND RESIDENTIAL DEVELOPMENTS.        C26 WHERE NO STEEL IS SHOWN ON THE DRAWING AT RIGHT ANGLES TO MAIN
                                                                                                     REINFORCEMENT PLACE N12-300 ON THE SIDE OF THE MAIN REINFORCEMENT REMOTE                                                                                                  S17 SURFACE TREATMENT AND PAINTING OF STEELWORK TO BE AS PER ARCHITECTURAL
       F12     SLAB ON GROUND: THE SUBGRADE UNDER SLABS SHALL BE PREPARED BY STRIPPING ALL           FROM THE OUTSIDE OF THE CONCRETE. ALL OPENINGS AND RE-ENTRANT ANGLES IN THE                                                                                                   SPECIFICATION. SURFACE TREATMENT SHALL BE CARRIED OUT IN ACCORDANCE WITH
               VEGETATION AND PROOF ROLLING THE SURFACE. ANY SOFT AREAS SHALL BE REMOVED             CONCRETE SHALL HAVE 2/N12 TOP AND BOTTOM ALONG THE ENCLOSING EDGE AND                                                                                                         AS 1627. (SEE ALSO ITEM S8) PROVIDE SEAL PLATES TO ALL HOLLOW SECTIONS, WITH
               AND REPLACED WITH APPROVED COMPACTED MATERIAL. MATERIAL UNDER SLAB SHALL              PROJECTING 350 PAST CORNERS.                                                                                                                                                  BREATHER HOLES IF MEMBERS ARE TO BE HOT DIPPED GALVANISED
               HAVE A MINIMUM SAFE BEARING CAPACITY OF 100kPa WITH A MAXIMUM LINEAR
               SHRINKAGE OF 8% AND A PLASTIC INDEX NOT EXCEEDING 16. ALL FILLING AND             C27 CONSTRUCTION BREAK, JOINT LOCATIONS AND DETAILS SHALL BE APPROVED BY THE                                                                                                  S18 ERECTION TOLERANCES SHALL COMPLY WITH AS 4100 SECTION 15 UNLESS NOTED
               BACKFILLING SHALL BE COMPACTED IN MAXIMUM 150mm THICK LAYERS BY MECHANICAL            STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION.                                                                                                                                    OTHERWISE ON THE STRUCTURAL DRAWINGS.
               COMPACTION TO 98% OF THE MAXIMUM DRY DENSITY (STANDARD) AS
               DETERMINED BY AS 1289 TEST E 1.1                                                  C28 THE FACE OF ALL CONCRETE AGAINST WHICH NEW CONCRETE IS TO BE CAST IS TO BE                                                                                                S19 ALL STEELWORK SHALL BE TEMPORARILY BRACED IN A SECURE MANNER IN ORDER
                                                                                                     THOROUGHLY MECHANICALLY SCABBLED, FULLY EXPOSING THE AGGREGATE MATRIX.                                                                                                        TO STABILISE THE STRUCTURE DURING ERECTION. DETAILS TO BE PROVIDED BY SUB
       F13     PLACE A 50mm THICK LAYER OF BEDDING SAND OVER SUBGRADE MATERIAL.                                                                                                                                                                                                    CONTRACTOR.

       F14     PLACE 0.2mm THICK POLYETHYLENE FILM VAPOUR BARRIER TO NCC UNDER SLAB WITH
               ALL JOINTS SEALED.



                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       INFORMATION
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           NOT FOR CONSTRUCTION
                                                                                                                                                                                                                                                                                                                                                                                                                                          Client                             Status                                Title
                                                                                                                                                                                                                                                                                                                                                                                                                                           MARK BAIN                          INFORMATION
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   NOTES SHEET - SHEET 1
                                                                                                                                                                                                                                                                                                                                                                                                                                          Drawn By         Designed By       Approved By
                                                                                                                                                                                                                                                                                                                                                                                                                                            JAL              JM               JO
                                                                                                                                                                                                                                                                                                                                                                                                                                          Project No.      Discipline        Scale

                                                                                                                                                                                                                                                                                                                                                                  [email protected]                                                  20220173         STRUCTURAL         1:1                  (at A1)

                                                                                                                                                                                                                                                                                                                                                                                                                                          Project Name
                                                                                                                                                                                                                                                                                                                                                                  37 MARY ST NOOSAVILLE, QLD                                                                                                                       Drawing No.                                      Revision
1     04.11.22 ISSUE FOR INFORMATION                                                                                                JAL       JO                                                                                                                                                                                                                                                                                           NOOSA VILLAS
                                                                                                                                                                                                                                                                                                                                                                  07 5211 1003                                                                                                                                      S001                                             1
Rev     Date      Description                                                                                                         By      Chk                                                                                                                                                                                                                                                                                          10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm

Section 3

      GENERAL SAFETY NOTES                                                                    HAZARDOUS SUBSTANCES                                                                   SAFETY HAZARDS
      GS1 IT IS THE CLIENTS RESPONSIBILITY TO PROVIDE THIS 'SAFETY IN DESIGN REPORT' TO THE   HS1   ASBESTOS                                                                         SH1   FALLING OBJECTS
          PRINCIPLE CONTRACTOR / BUILDER IN ACCORDANCE WITH THE WORK HEALTH AND                     FOR ALTERATIONS OR ADDITIONS TO AN EXISTING BUILDING:                                  CONSTRUCTION, MAINTENANCE OR DEMOLITION WORK ON OR AROUND THIS BUILDING IS
          SAFETY ACT 2011 AND REGULATIONS. BELOW LISTS POTENTIAL CONSTRUCTION HAZARDS               CONSTRUCTED PRIOR TO 1990 - IT MAY CONTAIN ASBESTOS PRODUCTS.                          LIKELY TO INVOLVE PERSONS WORKING ABOVE GROUND LEVEL. WHERE THIS OCCURS
          ASSOCIATED WITH IMPLEMENTING THE DESIGN AS DOCUMENTED.                                    CONSTRUCTED PRIOR TO 1986 - IT IS LIKELY TO CONTAIN ASBESTOS PRODUCTS.                 ONE OR MORE OF THE FOLLOWING MEASURES MUST BE UNDERTAKEN TO AVOID
                                                                                                    ASBESTOS MAY BE CONTAINED IN CLADDING MATERIALS OR IN INSULATING MATERIALS,            OBJECTS FALLING FOR THE WORK AREAS ON TO AREAS BELOW.
      GS2 IT IS THE CONTRACTORS RESPONSIBILITY TO BUILD IN ACCORDANCE WITH PROJECT                  THE CONTRACTOR MUST CHECK AND IF NECESSARY TAKE APPROPRIATE ACTION BEFORE              •       PREVENT OR RESTRICT ACCESS TO BELOW AREA AS SUITABLE
          DOCUMENTATION AND NOT MAKE VARIATIONS TO THE CONSTRUCTION WITH SPECIFIC                   DEMOLISHING, CUTTING, SANDING, DRILLING OR OTHERWISE DISTURBING THE MATERIAL.          •       PROVIDE TOE BOARDS AND HOARDING TO SCAFFOLD OR OTHER WORK
          WRITTEN APPROVAL. IF THESE DESIGN DRAWINGS ONLY DOCUMENT PART OF THE                                                                                                                     PLATFORMS.
          PROJECT WORKS, THE CONTRACTOR IS TO ENSURE ALL DESIGN DRAWINGS ARE CO-              HS2   POWDERED MATERIALS                                                                     •       PROVIDE PROTECTIVE STRUCTURES OVER THE WORK AREA BELOW
          ORDINATED BETWEEN ALL CONSULTANTS.                                                        MANY MATERIALS USED IN THE CONSTRUCTION OF THIS BUILDING CAN CAUSE HARM IS             •       ENSURE ALL WORKERS HAVE SUITABLE PERSONAL PROTECTIVE EQUIPMENT
                                                                                                    INHALED IN POWDER FORM. PERSONS WORKING ON OR IN THE BUILDING DURING                           (PPE)
      GS3 THE DESIGN HAS BEEN DOCUMENTED IN ACCORDANCE WITH THE NATIONAL                            CONSTRUCTION, OPERATIONAL MAINTENANCE OR DEMOLITION SHOULD ENSURE GOOD
          CONSTRUCTION CODE, RELEVANT AUSTRALIAN STANDARDS, LOCAL AUTHORITY                         VENTILATION AND WEAR PERSONAL PROTECTIVE EQUIPMENT TO ENSURE PROTECTION          SH2   WORKING AT HEIGHTS
          REGULATIONS AND STANDARD BUILDING CODES OF PRACTICE UNLESS OTHERWISE                      AGAINST INHALATION WHILE USING EITHER POWDERED PRODUCT OF WHEN SANDING,                DURING CONSTRUCTION: WHEREVER POSSIBLE COMPONENTS FOR THIS BUILDING
          NOTED. EACH STAGE OF CONSTRUCTION SHOULD BE STRUCTURALLY COMPLETE AND                     DRILLING, CUTTING OR OTHERWISE DISTURBING OR CREATING POWDERED MATERIAL.               SHOULD BE PREFABRICATED OFF SITE OR AT GROUND LEVEL TO MINIMISE THE RISK OF
          INSPECTED BEFORE PROCEEDING TO THE NEXT STAGE TO ENSURE DESIGN COMPLIANCE                                                                                                        WORKERS FALLING MORE THAN TWO METERS. WHERE CONSTRUCTION WILL REQUIRE
          BY THE CERTIFYING AUTHORITY. THE CONTRACTORIS TO ENSURE THE WORK                    HS3   VOLATILE ORGANIC COMPOUNDS                                                             WORKERS TO ACCESS HEIGHTS WHERE A FALL OF TWO METERS IS POSSIBLE, THE
          PROGRAMMED IN A SAFE MANNER AND MUST HIGHLIGHT TO THE DESIGNER ANY ASPECTS                MANY TYPES OF GLUE, SOLVENTS, SPRAY PACKS, PAINTS, PROTECTIVE COATINGS AND             CONTRACTOR MUST PROVIDE A BARRIER OR SUITABLE SCAFFOLDING TO PREVENT
          OF THE WORK THAT MAY REQUIRE FURTHER CLARIFICATION OR ADVICE WITH REGARD TO               OR CLEANING PRODUCTS AND DISINFECTANTS CAN HAVE DANGEROUS EMISSIONS.                   INJURY FROM FALLS.
          THE HEALTH AND SAFETY OF THE PROJECT.                                                     AREAS WHERE THESE ARE USED SHOULD BE KEPT WELL VENTILATED WHILE THE
                                                                                                    MATERIAL IS BEING USED AND FOR A PERIOD AFTER INSTALLATION. PERSONAL                   DURING CONSTRUCTION, OPERATION AND MAINTENANCE: WHERE ACCESS ABOVE TWO
      GS4 THE PLANS SPECIFICALLY DETAIL REQUIREMENTS FOR THE COMPLETED STRUCTURE.                   PROTECTIVE EQUIPMENT MAY ALSO BE REQUIRED. THE MANUFACTURERS                           METERS IS REQUIRED, SCAFFOLDING, LADDERS, TRESTLES OR ELEVATED WORK
          FURTHER TEMPORARY SUPPORTS, BRACING, CONNECTIONS ETC MAY BE REQUIRED TO                   RECOMENDATIONS FOR USE MUST BE CAREFULLY CONSIDERED AT ALL TIMES.                      PLATFORMS SHOULD BE USED ONLY IN ACCORDANCE WITH RELEVANT CODES OF
          MAINTAIN THE STABILITY AND SAFETY DURING THE CONSTRUCTION PERIOD. THIS WILL                                                                                                      PRACTICE, REGULATIONS AND LEGISLATION. ALL SCAFFOLD AND FORMWORK TO BE
          VARY DEPENDING UPON THE CONTRACTORS CONSTRUCTION PROGRAM. ELEMENTS MAY              HS4   SYNTHETIC MINERAL FIBRE                                                                DESIGNED AND CERTIFIED BY A LICENCED CONTRACTOR TO COMPLY WITH RELEVANT
          INCLUDE BUT NOT LIMITED TO FABRICATED TIMBER AND STEELWORK ELEMENTS,                      FIBREGLASS, ROCKWOOL, CERAMIC AND OTHER MATERIAL USED FOR THERMAL OR                   AUSTRALIAN STANDARDS AND MAINTAINED IN GOOD WORKING ORDER. ANCHORAGE
          UNRESTRAINED WALLS, CONCRETE COLUMNS, BEAMS AND SLABS, PRECAST OR TILT UP                 SOUND INSULATION MAY CONTAIN SYNTHETIC MINERAL FIBRES WHICH MAY BE HARMFUL             POINTS FOR FALL ARREST DEVICE (IF ADOPTED) ARE TO BE INSTALLED, TESTED AND
          PANELS, MASONRY WALLS AND PIER ETCS WHICH WILL REQUIRE TEMPORARY SUPPORTS                 IS INHALED OR IF IT COMES IN CONTACT WITH THE SKIN, EYES OR OTHER PARTS OF THE         MAINTAINED BY A SPECIALIST LICENCED COMPANY AND OLY USED BY TRAINED
          OR PROPPING TO PREVENT BEING OVER STRESSED, EXCESSIVE DEFLECTIONS OR UNTIL                BODY. PERSONAL PROTECTIVE EQUIPMENT INCLUDING PROTECTION AGAINST                       PERSONNEL FAMILIAR WITH THE SYSTEM.
          FINAL STABILITY IS ACHIEVED BY THE COMPLETED STRUCTURE. THE DESIGNER IS TO BE             INHALATION OF HARMFUL MATERIAL SHOULD BE USED WHEN INSTALLING, REMOVING OR
          CONTACTED IF FURTHER ADVICE IS REQUIRED.                                                  WORKING NEAR BULK INSULATION MATERIAL.                                           SH3   SLIPS, TRIPS AND FALLS
                                                                                                                                                                                           THE CONTRACTOR IS TO ENSURE ALL AREAS AND WORK SURFACES ARE CLEAR AND
      GS5 IT IS THE CLIENT AND CONTRACTORS RESPONSIBILITY TO NOTIFY THE DESIGNER OF ANY       HS5   TIMBER FLOORS                                                                          FREE OF DEBRIS PROVIDING SAFE ACCESS IN AND AROUND THE WORK SITE INCLUDING
          SPECIFIC LOADING THAT THE STRUCTURE MAY BE SUBJECT TO. LOADING APPLIED                    THIS BUILDING MAY CONTAIN TIMBER FLOORS WHICH HAVE AN APPLIED FINISH. AREAS            ADEQUATE STAIRS, SCAFFOLDING, SECURE LADDER ACCESS, SAFE WORKING
          DURING DESIGN ARE IN ACCORDANCE WITH THE RELEVANT AUSTRALIAN STANDARDS,                   WHERE FINISHED ARE APPLIED SHOULD BE KEPT WELL VENTILATED DURING SANDING,              PLATFORMS, ACCESS FREE FROM FALLING OBJECTS WITH SUITABLE RAILING AND
          UNLESS NOTED OTHERWISE. NO SPECIFIC ALLOWANCE HAS BEEN MADE FOR THE                       PREPARATION AND FINISHING. PERSONAL PROTECTIVE EQUIPMENT MAY ALSO BE                   BALUSTRADING, FALL ARREST SAFETY POINTS OR SIMILAR
          STACKED MATERIALS, MACHINERY LOADS, LIFTING DEVICES, IMPACT / VIBRATION / CYCLIC          REQUIRED. THE MANUFACTURERS RECOMMENDATIONS FOR USE MUST BE CAREFULLY
          LOADS ETC. ANY SPECIFIC LOADING FOR ACCESS PLATFORMS, SCAFFOLDING, FURTHER                CONSIDERED AND FOLLOWED AT ALL TIMES.                                            SH4   EQUIPMENT
          MAINTENANCE HAS NOT BEEN SPECIFICALLY DESIGNED UNLESS NOTED OTHERWISE.                                                                                                           CONSTRUCTION, MAINTENANCE AND DEMOLITION OF THIS BUILDING MAY REQUIRE THE
                                                                                                                                                                                           USE OF PORTABLE TOOLS AND EQUIPMENT. THESE SHOULD BE CAREFULLY MAINTAINED
      GS6 ALL SUNDRY ITEMS INCLUDING BUT NOT LIMITED TO CLADDING DESIGN AND FIXINGS,                                                                                                       IN ACCORDANCE WITH MANUFACTURERES SPECIFICATIONS AND NOT USED IF FAULTY OR
          WINDOWS, BALUSTRADES, STAIRS, SUSPENDED CEILINGS, INTERNAL FIT OUTS, AND                                                                                                         (FOR ELECTRICAL EQUIPMENT) NOT CARRYING A CURRENY ELECTRICAL SAFETY TAG. ALL
          OTHER ELEMENTS NOT DETAILED ON OUR PLANS MUST BE DESIGNED AND INSPECTED             MATERIALS HANDLING                                                                           SAFETY GUARDS OR DEVICES SHOULD BE REGULARLY INSPECTED AND CHECKED TO
          WHERE REQUIRED BY THE SUPPLIER OR CERTIFIER.                                        MH1 MANUAL TASKS                                                                             ENSURE PROPER FUNCTION WITH CORRECT USE OF PERSONAL PROTECTIVE EQUIPMENT
                                                                                                  COMPONENTS WITHIN THIS DESIGN WITH A MASS IN EXCESS OF 25kg SHOULD BE LIFTED             AT ALL TIMES DURING USE. ALL CONTRACTORS ARE TO ENSURE SUITABLE SPACE AND
      GS7 THE CLIENT AND CONTRACTOR MUST INFORM THE DESIGNER OF ANY CHANGE TO                     BY TWO OR MORE WORKERS OR BY MECHANICAL LIFTING DEVICES, WHERE THIS IS NOT               VENTILATION IS AVAILABLE TO UNDERTAKE USE OF THE EQUIPMENT SAFELY.
          CONTRACTUAL ARRANGEMENTS WHICH MAY IMPACT ON THE DESIGN AND SAFETY OF THE               PRACTICABLE, SUPPLIERS OR FABRICATORS SHOULD LIMIT THE COMPONENT MASS AS
          DESIGN. THE CONSTRUCTION MUST BE UNDERTAKEN IN ACCORDANCE WITH DESIGN                   REQUIRED.                                                                          SH5   EXCAVATION
          DRAWINGS AND PROJECT DOCUMENTATION. IF CONSTRUCTION CEASES AT ANY STAGE,                                                                                                         CONSTRUCTION AND SOME MAINTENANCE ACTIVITIES MAY REQUIRE EXCAVATION AND
          THE DESIGNER MUST BE NOTIFIED TO ADVISE ON THE SAFETY OF THE PARTIALLY              MH2 PRODUCT STORAGE                                                                          INSTALLATION OF ITEMS WITH EXCAVATIONS. WHERE PRACTICABLE, INSTALLATION
          COMPLETED WORKS AT THAT TIME.                                                           ALL MATERIAL PACKAGING, BUILDING AND MAINTENANCE COMPONENTS SHOULD                       SHOULD BE CARRIED OUT USING METHODS THAT DO NOT REQUIRE WORKERS TO ENTER
                                                                                                  CLEARLY SHOW THE TOTAL MASS OF PRODUCTS AND WHERE PRACTICAL BE STORED ON                 THE EXCAVATION. WHERE THIS IS NOT POSSIBLE, ADEQUATE SUPPORT / SHORING
                                                                                                  SITE IN A WAY WHICH ALLOWS SAFE LIFTING PRACTICES. ADVICE SHOULD BE PROVIDED             SYSTEM FOR THE EXCAVAED AREA SHOULD BE PROVIDED TO PREVENT COLLAPSE.
                                                                                                  ON SAFE LIFTING METHODS IN AREAS WHERE LIFTING MAY BE REQUIRED.                          OTHER METHODS SUCH AS BENCING OR BATTERING IN ACCORDANCE WITH DIRECTION
      TRAFFIC MANAGEMENT                                                                                                                                                                   FROM THE PROJECT GEOTECHNICAL ENGINEER MAY BE ADOPTED. WARNING SIGNS AND
                                                                                              MH3 MECHANICAL LIFTING                                                                       BARRIERS TO PREVENT ACCIDENTAL OR UNAUTHORISED ACCESS TO ALL EXCAVATIONS
      TM1     MAJOR ROADS, NARROW OR STEEP SLOPING ROADS
                                                                                                  MECHANICAL LIFTING OF MATERIALS AND COMPONENTS DURING CONSTRUCTION,                      MUST BE PROVIDED.
              PARKING OF VEHICLES, LOADING AND OR UNLOADING VEHICLES ON THIS ROADWAY MAY
              CAUSE TRAFFIC HAZARDS. DURING CONSTRUCTION, MAINTENTANCE OR DEMOLITION OF           MAINTENANCE OR DEMOLITION PRESENTS A RISK OF FALLING OBJECTS. CONTRACTORS
                                                                                                  SHOULD ENSURE ONLY APPROPRIATE LIFTING DEVICES ARE USED BY TRAINED                 SH6   SMALL ENCLOSED OR CONFINED SPACES
              THIS BUILDING DESIGNATED PARKING FOR WORKERS AND LOADING AREAS SHOULD BE
                                                                                                  PERSONNEL AND THAT LOADS ARE PROPERLY SECURED WITH THE WORK AREA SUITABLY                FOR STRUCTURES WITH ENCLOSED SPACES WHERE MAINTENANCE OR OTHER ACCESS
              PROVIDED. TRAINED TRAFFIC MANAGEMENT PERSONNEL SHOULD BE RESPONSIBLE FOR
                                                                                                  RESTRICTED TO PREVENT ACCESS BELOW LIFTING OPERATIONS.                                   MAY BE REQUIRED: ENCLOSED SPACES WITH THIS BUILDING MAY PRESENT A RISK TO
              THE SUPERVISION AND CONTROL OF THESE AREAS.
                                                                                                                                                                                           PERSONS ENTERING FOR CONSTRUCTION, MAINTENANCE OR ANY OTHER PURPOSE. THE
                                                                                                                                                                                           AREA MUST BE SUITABLY SIGNED AND BARRIERS PROVIDED TO PREVENT UNAUTHORISED
      TM2     WHERE ON SITE LOADING / UNLOADING IS RESTRICTED
                                                                                                                                                                                           ACCESS. THESE SHOULD BE MAINTAINED THROUGHOUT THE LIFE OF THE BUILDING.
              CONSTUCTION, MAINTENANCE AND DEMOLITION WILL REQUIRE LOADING AND UNLOADING
                                                                                                                                                                                           ACCESS TO THESE AREAS SHOULD ONLY BE BY SUITABLY TRAINED PERSONNEL WITH AIR
              OF MATERIALS ON THE ROADWAY (SUBJECT TO APPROVAL BY LOCAL AUTHORITIES).
                                                                                                                                                                                           TESTING AND BREATHING APPARATUS USED WHERE REQUIRED. MANUAL LIFTING AND
              DELIVERIES MUST BE WELL PLANNED TO AVOID CONGESTION OF LOADING AREAS WITH
                                                                                                                                                                                           OTHER MANUAL ACTIVITIES SHOULD BE RESTRICTED IN THESE PLACES WHERE
              TRAINED TRAFFIC PERSONNEL USED TO SUPERVICE, MANAGE AND CONTROL THE
                                                                                                                                                                                           POSSIBLE.
              LOADING AND UNLOADING AREAS.
                                                                                                                                                                                     SH7   PUBLIC ACCESS
      TM3     ALL SITES
                                                                                                                                                                                           PUBLIC ACCESS TO CONSTRUCTION, MAINTENANCE AND DEMOLITION AREAS PRESENTS
              ALL SITES DURING CONSTRUCTION, MAINTENANCE AND DEMOLITION WILL PRESENT A
                                                                                                                                                                                           RISKS TO WORKERS AND THE PUBLIC. SUITABLE SECURE BARRIERS AND WARNING SIGNS
              RISK OF COLLISION WHERE DELIVERIES AND OTHER TRAFFIC ARE MOVING. A TRAFFIC
                                                                                                                                                                                           TO PREVENT UNAUTHORISED ACCESS SHOULD BE PROVIDED. WHERE ELECTRICAL
              MANAGEMENT PLAN DEVELOPED, SUPERVISED AND CONTROLLED BY TRAINED TRAFFIC
                                                                                                                                                                                           INSTALLATIONS, EXCAVATIONS, PLANT, LOOSE MATERIALS ETC ARE PRESENT THEY
              MANAGEMENT PERSONNEL SHOULD BE ADOPTED FOR THE WORKS WHERE APPLICABLE.
                                                                                                                                                                                           SHOULD BE SECURED WHEN NOT FULLY SUPERVISED.

                                                                                                                                                                                     SH8   TRAINED AND QUALIFIED WORKERS
                                                                                                                                                                                           THE CONTRACTOR IS TO ENSURE THAT THE WORKERS ARE SUITABLY QUALIFIED,
                                                                                                                                                                                           TRAINED AND INSURED FOR THE TASKS BEING PERFORMED ON SITE.

                                                                                                                                                                                     SH9   FALLING OBJECTS
                                                                                                                                                                                           RUPTURE OF SERVICES DURING EXCAVATIONS AND OTHER ACTIVITY CREATES A VARIETY
                                                                                                                                                                                           OF RISKS INCLUDING THE RELEASE OF HAZARDOUS MATERIAL. EXISTING SERVICES MAY
                                                                                                                                                                                           BE LOCATED ON OR AROUND THE SITE. WHERE COUNCIL SERVICES ARE KNOWN AT THE
                                                                                                                                                                                           TIME OF DESIGN THESE ARE SHOWN ON THE PLAN. THE EXACT LOCATION MUST BE
                                                                                                                                                                                           CONFIRMED ON SITE AS THEIR LOCATION MAY VARY. SERVICES SHOULD BE LOCATED
                                                                                                                                                                                           USING AN APPROPRIATE SERVICE (SUCH AS DIAL BEFORE YOU DIG), APPROPRIATE
                                                                                                                                                                                           EXCAVATION PRACTICE SHOULD BE USED AND WHERE NECESSARY, SPECIALIST
                                                                                                                                                                                           CONTRACTORS SHOULD BE USED.

                                                                                                                                                                                           LOCATIONS WITH UNDERGROUND POWER: UNDERGROUND POWER MAY BE LOCATED IN
                                                                                                                                                                                           OR AROUND THIS SITE. ALL UNDERGROUND POWER LINES MUST BE DISCONNECTED OR
                                                                                                                                                                                           CAREFULLY LOCATED AND ADEQUATE WARNING SIGNS USED PRIOR TO ANY
                                                                                                                                                                                           CONSTRUCTION, MAINTENANCE OR DEMOLITION COMMENCING.

                                                                                                                                                                                           LOCATIONS WITH OVERHEAD POWER LINES: OVERHEAD POWER LINES MAY BE NEAR OF
                                                                                                                                                                                           ON THIS SITE. THESE POSE A RISK OF ELECTROCUTION IF STRUCK OR APPROACHED BY
                                                                                                                                                                                           LIFTING DEVICES, OTHER PLANT AND PERSONS WORKING ABOVE GROUND LEVEL. WHERE
                                                                                                                                                                                           THERE IS A DANGER OF THIS OCCURING, POWER LINES SHOULD WHERE PRACTICAL BE
                                                                                                                                                                                           DISCONNECTED AND OR RELOCATED. WHERE THIS IS NOT PRACTICAL, ADEQUATE
                                                                                                                                                                                           WARNINGS WITH PROTECTIVE BARRIERS, BRIGHT COLOURED TAPE AND SIGNAGE ETC
                                                                                                                                                                                           MAY BE SUITABLE.

                                                                                                                                                                                     SH10 OTHER HAZARDS
                                                                                                                                                                                          THE CLIENT AND CONTRACTOR MUST MAKE THE DESIGNER AWARE OF ANY OTHER
                                                                                                                                                                                          INFORMATION RELATING TO HAZARDS AND RISKS WHERE CONSTRUCTION WORKS ARE
                                                                                                                                                                                          CARRIED OUT. THIS INCLUDES BUT NOT LIMITED TO THE LOCATION OF UNDERGROUND
                                                                                                                                                                                          AND ABOVE GROUND SERVICES, IDENTIFICIATION OF CONTAMINATED SOILS AND OTHER
                                                                                                                                                                                          MATERIALS OR THE PRESENCE OF DANGEROUS MATERIALS INCLUDING ASBESTOS. THE
                                                                                                                                                                                          CONTRACTOR MUST PROTECT NEIGHBOURING PROPERTIES AND SERVICES FROM NOISE,
                                                                                                                                                                                          DUST, RADIATION, GROUND VIBRATIONS AND OTHER CONSTRUCTION HAZARDS IN
                                                                                                                                                                                          ACCORDANCE WITH RELEVANT GUIDELINES, CODES OF PRACTICE AND RELEVANT LOCAL
                                                                                                                                                                                          AUTHORITY REQUIREMENTS. CONDITION REPORTS ON NEIGHBOURING PROPERTIES AND
                                                                                                                                                                                          STRUCTURES ARE RECOMMENDED PRIOR TO CONSTRUCTION WHERE APPLICABLE.

                                                                                                                                                                                     SH11 SITE IDENTIFICATION
                                                                                                                                                                                          ALL NEW WORKS MUST BE CONTAINED WITHIN THE ALLOCATED BOUNDARIES. A
                                                                                                                                                                                          LICENCED SURVEYOR SHOULD BE USED TO CONFIRM BOUNDARY LOCATIONS AND
                                                                                                                                                                                          SETOUT AND ANY OTHER FEATURES FOR THE SITE. THE CONTRACTOR IS REQUIRED TO
                                                                                                                                                                                          VERIFY AND IF NECESSARY CONDUCT FURTHER SEARCHES TO LOCATE EASEMENTS,
                                                                                                                                                                                          SERVICES, BOUNDARIES, TRES, EXISTING STRUCTURES AND ANY OTHER OBSTRUCTIONS
                                                                                                                                                                                          PRIOR TO CONSTRUCTION. THE DESIGNER IS TO BE IMMEDIATELY NOTIFIED OF ANY
                                                                                                                                                                                          ELEMENTS NOT SHOWN ON THE APPORVED PLANS AND THE DESIGN AND SAFETY
                                                                                                                                                                                          REPORT MAY REQUIRE AMENDING

                                                                                                                                                                                     SH12 SITE MAINTENANCE
                                                                                                                                                                                          IT IS THE CONTRACTORS RESPONSIBILITY TO ENSURE THAT THE SITE IS MAINTAINED IN A
                                                                                                                                                                                          SAFE WORKING MANNER AND THAT ALL SITE PRACTICIES ARE IN ACCORDANCE WITH THE
                                                                                                                                                                                          CURRENT WORK HEALTH AND SAFETY ACT AND REGULATIONS.




                                                                                                                                                                                                                                                                                                                                                                                      INFORMATION
                                                                                                                                                                                                                                                                                                                                                                                          NOT FOR CONSTRUCTION
                                                                                                                                                                                                                                                                                                         Client                             Status                                Title
                                                                                                                                                                                                                                                                                                          MARK BAIN                          INFORMATION
                                                                                                                                                                                                                                                                                                                                                                                  NOTES SHEET - SHEET 2
                                                                                                                                                                                                                                                                                                         Drawn By         Designed By       Approved By
                                                                                                                                                                                                                                                                                                           JAL              JM               JO
                                                                                                                                                                                                                                                                                                         Project No.      Discipline        Scale

                                                                                                                                                                                                                                                                            [email protected]       20220173         STRUCTURAL         1:1                  (at A1)

                                                                                                                                                                                                                                                                                                         Project Name
                                                                                                                                                                                                                                                                            37 MARY ST NOOSAVILLE, QLD                                                                            Drawing No.                                      Revision
1      04.11.22 ISSUE FOR INFORMATION                                                                                                     JAL     JO                                                                                                                                                      NOOSA VILLAS
                                                                                                                                                                                                                                                                            07 5211 1003                                                                                           S002                                             1
Rev         Date   Description                                                                                                             By     Chk                                                                                                                                                     10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                                                                     FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm

Section 4

                                                                                                                                                             INFORMATION
                                                                                                                                                                 NOT FOR CONSTRUCTION
                                                                                Client                             Status                                Title
                                                                                 MARK BAIN                          INFORMATION
                                                                                                                                                         SAFETY IN DESIGN ASSESSMENT
                                                                                Drawn By         Designed By       Approved By
                                                                                  JAL              JM               JO
                                                                                Project No.      Discipline        Scale

                                                   [email protected]       20220173         STRUCTURAL                              (at A1)

                                                                                Project Name
                                                   37 MARY ST NOOSAVILLE, QLD                                                                            Drawing No.                                      Revision
1     04.11.22 ISSUE FOR INFORMATION   JAL   JO                                  NOOSA VILLAS
                                                   07 5211 1003                                                                                           S003                                             1
Rev     Date   Description             By    Chk                                 10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                            FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm

Section 5

                                                                                                                                                                                 S
                                                                                                                                                                          S
                                                                                                                                       K6 VILLA




                                                                                                                                                                 S
                                                                                                                  K5 VILLA




                                                                                                                                                         S
                                                                                   N2 VILLA


                                                                                                                                                                                                                   REFER S100 SERIES DRAWINGS




                                                                                                                                                   S
                                                                                                                                                                                                                   FOR K1, K2 & K3 VILLA DETAILS
              NATASHA AVENUE




                                                                                                                                            S
                                                                                                                                                                                     K2 VILLA



                                                                                   N1 VILLA                    K4 VILLA




                                                                                                                                      S
                                                                                                                                                                         K3 VILLA
                                                                                                                                                                                                                                  K1 VILLA




                                                                                                                             S




                                                                                                                                                                                                                                                                                                                       EET
                                                                                  REFER S300 SERIES DRAWINGS                     REFER S200 SERIES DRAWINGS




                                                                                                                                                                                                                                                                                                                   STR
                                                                                  FOR N1 & N2 VILLA DETAILS                      FOR K4, K5 & K6 VILLA DETAILS




                                                                                                                                                                                                                                                                                                                 A
                                                                                                                                                                                                                                                                                                              RIN
                                                                                                                                                                                                                                                                                                            HA
                                                                  SITE PLAN




                                                                                                                                                                                                                                                                                                        KAT
                                                                  SCALE 1 : 100




         1m               0          1000    2000   3000   4000
                                                                                                                                                                                                                                                                               INFORMATION
1 :100
                                                                                                                                                                                                                                                                                   NOT FOR CONSTRUCTION
                                                                                                                                                                                                  Client                             Status                                Title
                                                                                                                                                                                                   MARK BAIN                          INFORMATION
                                                                                                                                                                                                                                                                           SITE PLAN
                                                                                                                                                                                                  Drawn By         Designed By       Approved By
                                                                                                                                                                                                    JAL              JM               JO
                                                                                                                                                                                                  Project No.      Discipline        Scale

                                                                                                                                                                     [email protected]       20220173         STRUCTURAL         1 : 100              (at A1)

                                                                                                                                                                                                  Project Name
                                                                                                                                                                     37 MARY ST NOOSAVILLE, QLD                                                                            Drawing No.                                       Revision
1        04.11.22 ISSUE FOR INFORMATION                                                       JAL   JO                                                                                             NOOSA VILLAS
                                                                                                                                                                     07 5211 1003                                                                                           S005                                              1
Rev        Date                Description                                                    By    Chk                                                                                            10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                              FULL SIZE ON ORIGINAL    0           10    20   30   40    50   60   70   80        90    100 mm

Section 6

                    SCHEDULE OF CONCRETE ELEMENTS                                                                       SCHEDULE OF FRAMING ELEMENTS
                    SCREW PIERS                                                                                         STEEL COLUMNS
                     MARK          REMARKS                                                                              MARK       SIZE            DESCRIPTION  COMMENTS
                     SP1           200 kN SWL                                                                           SC1        89x89x5.0 SHS   STEEL COLUMN
                     SP2                                                                                                SC2        89x89x3.5 SHS   STEEL COLUMN
                    •    SCREW PIERS TO BE DESIGNED AND CERTIFIED BY OTHERS.



                    PILE CAPS                                                                                           STEEL FRAMING
                    MARK           LENGTH         WIDTH           DEPTH                                                 MARK       SIZE            DESCRIPTION        COMMENTS
                    PC1            4700           2600            450                                                   PP1        300x45 LVL 13   POLE PLATE         FIXED TO WALL WITH M16 CHEMICAL ANCHORS AT 900 MAX CRS
                    PC2            1800           1100            450                                                   PP2        140x45 MGP12    POLE PLATE         FIXED TO WALL WITH M16 CHEMICAL ANCHORS AT 900 MAX CRS
                    PC3            1100           1100            450                                                   PP3        200x45 LVL 13   POLE PLATE         FIXED TO WALL WITH M16 CHEMICAL ANCHORS AT 900 MAX CRS
                    PC4            1100           600             450                                                   PP4        120x45 MGP12    POLE PLATE         FIXED TO SLAB WITH M12 CHEMICAL ANCHORS AT 900 MAX CRS
                    PC5            3200           2200            450                                                   R1         300x45 LVL 13   RAFTER             AT 900 MAX CRS
                                                                                                                        R2         140x45 MGP12    RAFTER             AT 900 MAX CRS
                                                                                                                        R3         200x45 LVL 13   RAFTER             AT 900 MAX CRS
                    PAD FOOTINGS                                                                                        R4         90x45 MGP12     RAFTER             AT 900 MAX CRS
                    MARK           LENGTH         WIDTH           DEPTH                                                 R5         190x45 MGP12    RAFTER             AT 900 MAX CRS
                    PF1            1600           1600            450                                                   RB1        250 PFC         ROOF BEAM
                    PF2            1400           1400            450                                                   RB2        180 PFC         ROOF BEAM
                    PF3            1800           700             450                                                   VB1        89x89x5.0 SHS   VERTICAL BRACING
                                                                                                                        WH2        200 PFC         WALL HEAD
                    GROUND BEAMS                                                                                        WS1        89x89x5.0 SHS   WINDOW SILL
                    MARK               WIDTH          DEPTH       COMMENTS
                    GB1                 800            450
                    GB2                 500            450
                    GB3                 1100           400
                    GB4                 700            400
                    GB5                 500            400
                    GB6                 300            400


                    CONCRETE BEAMS
                    MARK           SIZE           COMMENTS
                    CB1            550dx400w
                    CB2            500dx400w


                    STRIP FOOTINGS
                    MARK           WIDTH          DEPTH
                    SF1            450            450
                    SF2            800            300

                    EDGE THICKENINGS
                    MARK           DESCRIPTION    REMARKS
                    ET1            200d x 250w


                    CONCRETE COLUMNS
                    MARK           SIZE           DESCRIPTION          COMMENTS
                    CC1            300x300        CONCRETE COLUMN
                    CC2            300Ø           CONCRETE COLUMN


                    WALL SCHEDULE
                    MARK          VERT REINF.    HORIZ REINF.   DESCRIPTION                    REMARKS
                    BC1              REFER         DETAIL       300 SERIES BLOCKWORK COLUMN
                    BU1             N12-400        N12-400      200 SERIES BLOCKWORK UPSTAND
                    BW1             N20-200        N16-400      300 SERIES BLOCKWORK
                    BW2             N16-200        N16-200      200 SERIES BLOCKWORK
                    BW3             N16-200        N12-200      200 SERIES BLOCKWORK
                    BW4             N12-400        N12-400      200 SERIES BLOCKWORK
                    BW5             N12-400        N12-400      150 SERIES BLOCKWORK
                    CW1            S12-200 EF     S12-200 EF    200 THICK CONCRETE             POOL WALLS




                                                                                                                                                                                                                                                                                                                                         INFORMATION
                                                                                                                                                                                                                                                                                                                                             NOT FOR CONSTRUCTION
                                                                                                                                                                                                                                                            Client                             Status                                Title
                                                                                                                                                                                                                                                             MARK BAIN                          INFORMATION
                                                                                                                                                                                                                                                                                                                                     MASTER MEMBER SCHEDULES
                                                                                                                                                                                                                                                            Drawn By         Designed By       Approved By
                                                                                                                                                                                                                                                              JAL              JM               JO
                                                                                                                                                                                                                                                            Project No.      Discipline        Scale

                                                                                                                                                                                                                               [email protected]       20220173         STRUCTURAL                              (at A1)

                                                                                                                                                                                                                                                            Project Name
                                                                                                                                                                                                                               37 MARY ST NOOSAVILLE, QLD                                                                            Drawing No.                                      Revision
1     04.11.22 ISSUE FOR INFORMATION                                                                        JAL   JO                                                                                                                                         NOOSA VILLAS
                                                                                                                                                                                                                               07 5211 1003                                                                                           S010                                             1
Rev     Date   Description                                                                                  By    Chk                                                                                                                                        10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                        FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm

Section 7

                                                                                                                                                                                                                             750
                                                                                                                                                                                                                                                                                            LAP LENGTH
                                                                                                                                                                                                                                     400                                                        TYP
                                                                                                                                                                                                                                                                                                                                                    'U' BARS TO
                                                                                                                                                                                                                                                                                                                                                    MATCH BEAM                                                          'L' BARS TO MATCH BEAM
                                                                                                                                                                                                                                                                                                                                                    REINF TOP & BTM                                                     REINF TOP & BTM.
                                                                                                                                                                                                                                                                                                                                                                                       LAP LENGTH




                                                                                                                                                                                                                                                                   400 MAX
                                                                                                                                                                                                                                                                   VARIES
                                                                                                                                                                                                                                                                                                                                                    USE N12 WHERE                                                       USE N12 WHERE BEAM REINF
                                                                                                                                                                                                                                                                                                                                                                                                                        IS TRENCH MESH                                                                             'U' BARS TO MATCH
                                                                                                                                                                                                                                                                                                                                                    BEAM REINF IS
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   BEAM REINF TOP & BTM.
                                                                                                                                                                                                                                                                                                                                                    TRENCH MESH                                                                                                                 LAP LENGTH                         USE N12 WHERE BEAM




                                                                                                                                                                    1200 MAX STEP
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    TYP                            REINF IS TRENCH MESH




                                                                                                                                                                                                                                                                   FTG / BEAM
                                                                           200 MAX.




                                                                                                                                                                       VARIES




                                                                                                                                                                                                                                                                     DEPTH
                                                                                                                                                                                                                                           SAME BAR DIAMETER                                                       SAME BAR DIAMETER
                                                                                                                                                                                                                                           & ARRANGEMENT AS                                                        & ARRANGEMENT AS
                                                                                                                                                                                                                                           MAIN REINFORCEMENT




                                                                                                                                                                                                      2 TIES
                                                                                                                                                                                                                                                                                                                   MAIN REINFORCEMENT




                                                                                                                                                                                                                                                                                                                                                                          300 COG
                                                                                                                                                                                                                                                                                                                                                                            TYP
                                                                                                                                                                                                                                                                                                                                                            LAP LENGTH
                                                                                                                                                                                                                                                                                            1.5 x DEPTH                                                                                                300




                                                                                                                                                                                                                                                                                                                                                                                                                                                  300 COG
                                                                                                                                                                                                                                     400




                                                                                                                                                                                                                                                                                                                                                                TYP




                                                                                                                                                                                                                                                                                                                                                                                                                                                    TYP
                                                                                                                                                                                                                                                                                STEP DETAIL - 400 MAX - ELEVATION                                                                                                  REFER DETAILS FOR SIZE
                                                                                                                    1                                                                                                                                                                                                                                                                                                                                                              'L' BARS TO MATCH BEAM
                                                                                                                                                                                                                                                                                                                                                                                                                   & ARRANGEMENT OF




                                                                                                                                                                    FTG / BEAM
                                                                                                         6                                                                                                                                                                                                                                                                                                                                                                         REINF TOP & BTM.
                                                                                                                                                                                                                                                                                                                                                                                                                   REINFORCEMENT TYP




                                                                                                                                                                      DEPTH
                                                                                                     (MAX. SLOPE)                                                                                                                                                                                                                                                                                                                                                                  USE N12 WHERE BEAM REINF
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   IS TRENCH MESH


                                                                                                                                                                                                                                                                                                                                                                                    CORNER DETAIL - PLAN                                                     INTERSECTION DETAIL UNO - PLAN
                                                                                                                                                                                                                  1.5 x DEPTH OF
                                                                                       SLOPED FOOTING DETAIL - ELEVATION
                                                                                                                                                                                                                   FTG OR BEAM
                                                                                                                                                                                                         STEP DETAIL - 1200 MAX - ELEVATION                                                                                                             TYPICAL STRIP FOOTING OR GROUND BEAM CORNER JUNCTION DETAILS
                                                                                                                                                                                                                                                                                                                                                           SCALE 1:20


                                                                                                                                                                            TYPICAL STRIP FOOTING AND GROUND BEAM STEP DETAILS U.N.O.
                                                                                                                                                                            SCALE 1:20                                                                                                                                                                                                                                                                                                      WALL OR COLUMN U.N.O.
                                                                                                                                                                                                                                                                                                                                               WALL OR COLUMN U.N.O.




                                                                                                                                                                                                                                                                                                                                                                         REFER DRG SXXX FOR
                                                                                                                                                                                                                                   HEAD PIN AND EMBEDMENT DESIGNED
                                                                                                        N12 'Z' BARS                                                 N12 'Z' BARS                                                                                                                                                                                        BLOCK WALL DETAILS                                                                                                                            WALL OR COLUMN
                                                                                                                                                                                                                                   AND CERTIFIED BY PILING CONTRACTOR
                                                                                                        AT 500 CRS                                                   AT 500 CRS                                                                                                                                        N12 'Z' BARS                                                                                                                  G.L.
                                                                                                        TYPICAL.                                                     TYPICAL.                                                                                                                                          AT 200 CRS
                                                                                                                                                                                                                                                                                                                       TYPICAL
                                                                                                       REINFORCEMENT 'B'                                                                                                      REINFORCEMENT 'B'
                                                                                                                                                                                                                                                                                                                                                                                                                                                             VARIES
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             PAD OR STRIP
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             FOOTING
                                                                                                                                                                                                                                                                                                                                                                                                                          SEWER OR
                                                                                                                                                                                                                                                                                                                                                                         REINFORCEMENT 'B'                                STORM WATER




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             VARIES
                                                                                                        REFER SCHEDULE                                                                                                        REFER SCHEDULE
                                                                  DEPTH




                                                                                                                                                                                     DEPTH




                                                                                                                                                                                                                                                                                                                                                                                               DEPTH
                                                                                                                                                                                                                                                                                                                                                                                                                          PIPE
                                                                                                                                                                                                                                                                                                                                                                         REFER SCHEDULE

                                                                                                                                                                                                                                                                                                                                                                         REINFORCEMENT 'A'                               PIPE INVERT
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 15 MPa MASS CONCRETE
                                                                                                        REINFORCEMENT 'A'                                                                                                     REINFORCEMENT 'A'
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 BLINDING LAYER




                                                                                                                                                                                                                                                                                                                                                                                                                                                                      30.00
                                                                                                                                                                                                                                                                                                                                                                                                                                            MIN
                                                                                                                                                                                                                                                                                                                                                                                                                                            300
                                    15 MPa BLINDING AS REQUIRED TO                                                                                                                                                                                                                  15 MPa BLINDING AS REQUIRED TO
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 LINE OF INFLUENCE BELOW PIPE INVERT
                                    ACHIEVE 150 SOCKET INTO NATURAL                                                                                                                                                                                                                 ACHIEVE 150 SOCKET INTO NATURAL




                                                                                                                                                                                                                                                                                                                                                                                                                                                                           °*
                                    MATERIAL WITH MINIMUM ALLOWABLE                     WIDTH                                                                                                                                                                                       MATERIAL WITH MINIMUM ALLOWABLE                         WIDTH                                                                                                                                            * TRENCH EXCAVATIONS SHALL NOT EXTEND BELOW A LINE
                                    BEARING CAPACITY AS SHOWN IN                                                                                                                                          WIDTH                                                                     BEARING CAPACITY AS SHOWN IN                                                                                                                                                                               DRAWN 30 DEGREES TO THE HORIZONTAL FOR SAND, OR 45
                                    FOUNDATION NOTES ON DRG. S001                                                                                                                                                                                                                   FOUNDATION NOTES ON DRG. S001                                                                                                                                                                              DEGREES TO THE HORIZONTAL FOR SILT OR CLAY
                                                                          GROUND BEAM WITHOUT SCREW PIERS                                                                                                                          PILES TO BE DESIGNED BY
                                                                                                                                                           STEEL SCREW
                                                                                                                                                           PILE. REFER PLAN FOR
                                                                                                                                                                                                                                   CONTRACTOR WITH REFERENCE
                                                                                                                                                                                                                                   TO THE GEOTECHNICAL REPORT                            STRIP FOOTING SCHEDULE
                                                                                                                                                                                                                                                                                                                                                                                                                                       DETAIL - FOOTING ADJACENT TO SEWER
                                                                                                                                                           DETAILS                                                                 TO ACHIVE THE GIVEN PILE LOAD
                                                                                                                                                                                                                                                                                                                    DIMENSIONS                                      REINFORCEMENT
                                                                                                                                                                                                                                                                                                                                                                                                                                       SCALE 1:20
                                                                                                                                                                                                                                                                                                                                                                                                                                                  OR STORMWATER PIPE
                                                                                                                                                                                                                                                                                         MARK                  WIDTH         DEPTH                   'A'                  'B'                 LIGS
                                                                                                                                                                                                                                                                                         SF1                    450            450                  3N12                 3N12                N12-300
                                                                                                                                                                                             GROUND BEAM WITH SCREW PIERS                                                                SF2                    800            300                  SL92                 SL92
                                                                                      GROUND BEAMS
                                                                                                            DIMENSIONS                     REINFORCEMENT
                                                                                      MARK            WIDTH          DEPTH        A            B               LIGS        COMMENTS                                                                                                                       TYPICAL STRIP FOOTING DETAIL
                                                                                      GB1               800            450      6N16          6N16     N12-300 CLOSED TIES                                                                                                                                SCALE 1:20
                                                                                      GB2               500            450      5N16          5N16     N12-300 CLOSED TIES
                                                                                      GB3              1100            400      6N12          6N12     R10-300 CLOSED TIES
                                                                                      GB4               700            400   2/L11TM300
                                                                                      GB5               500            400    L11TM400
                                                                                      GB6               300            400    L11TM200

                                                                                                                                                                                                                                                                                                                                                DOWEL WALL TO COLUMN.                                                                  WALL AND COLUMN REINFORCEMENT
                                                                                                             TYPICAL GROUND BEAM DETAIL                                                                                                                                                                                                         REFER TYPICAL DETAIL. NOT
                                                                                                                                                                                                                                                                                                                                                SHOWN FOR CLARITY
                                                                                                                                                                                                                                                                                                                                                                                                                                       OMITTED FOR CLARITY

                                                                                                             SCALE 1:20




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           ENSURE STARTER BARS FOR
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           WALL REINFORCEMENT ARE
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           CAST IN PAD FOOTING AS
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           REQUIRED TYP




                                                                                                                                                                                                                                                                                                                                                    LAP LENGTH
                                                                                                                                                                                                                                                                                                                                                        TYP




                                                                                                                                                                                                                                                                                                                                                                                                                                                      STRIP FOOTING/GROUND BEAM TOP
                                                                                                                                                                                                                                                                                                                                 LAP BTM REINFORCEMENT
                                                                                                                                                                                                                                                                                                                                                                                                                                                      REINFORCEMENT TO BE CONTINUOUS
                                                                                                                                                                                                                                                                                                                                 THROUGH PAD FOOTING
                                                                                                                                                                                                                                                                                                                                                                                                                                                      THROUGH PAD FOOTING. LAP MIDSPAN
                                                                                                                                                                                                                                                                                                                                               STRIP FOOTING/                                          PAD FOOTING/PILE CAP                                 STRIP FOOTING/
                                                                                                                                                                                                                                                                                                                                               GROUND BEAM                                                                                                  GROUND BEAM


                                                                                                                                                                                                                                                                                                                              TYPICAL STRIP FOOTING/GROUND BEAM TO PAD FOOTING/PILE CAP DETAIL
                                                                                                                                                                                                                                                                                                                               SCALE 1:20
                                                                                                                                                                                                                                                                                                                              RETAINING WALL FOOTING TO PAD FOOTING DETAIL SIMILAR

      200mm       0          200       400   600   800
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  INFORMATION
 1 :20
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      NOT FOR CONSTRUCTION
                                                                                                                                                                                                                                                                                                                                                                                                                              Client                                               Status                                   Title
                                                                                                                                                                                                                                                                                                                                                                                                                               MARK BAIN                                            INFORMATION
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            TYPICAL SLAB AND FOOTING DETAILS - SHEET 1
                                                                                                                                                                                                                                                                                                                                                                                                                              Drawn By                  Designed By                Approved By
                                                                                                                                                                                                                                                                                                                                                                                                                                JAL                         JM                      JO
                                                                                                                                                                                                                                                                                                                                                                                                                              Project No.               Discipline                 Scale

                                                                                                                                                                                                                                                                                                                                              [email protected]                                                          20220173                    STRUCTURAL                1 : 20                  (at A1)

                                                                                                                                                                                                                                                                                                                                                                                                                              Project Name
                                                                                                                                                                                                                                                                                                                                              37 MARY ST NOOSAVILLE, QLD                                                                                                                                                    Drawing No.                                       Revision
1        04.11.22 ISSUE FOR INFORMATION                                                                                        JAL   JO                                                                                                                                                                                                                                                                                        NOOSA VILLAS
                                                                                                                                                                                                                                                                                                                                              07 5211 1003                                                                                                                                                                   S020                                              1
Rev        Date       Description                                                                                               By   Chk                                                                                                                                                                                                                                                                                       10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               FULL SIZE ON ORIGINAL    0             10   20   30   40   50   60   70   80        90    100 mm

Section 8

                                                                                                                                                                                                                                                                                                                                  PIER                                              PIER                        PIER
                                                                                                                                                                                                                                                                                                NOTE:                               ℄                                                 ℄                           ℄
                                                                                                                                                                                                                                                                                                PROVIDE STARTER BARS
                                                                             PIER                                                              PIER                                                                                 PIER                                                        FOR BLOCK WALLS
                                                                               ℄                                                                 ℄                                                                                    ℄
                                            NOTE:




                                                                                                                                                                                                                                                                                                                                                                                                                                                   300
                                            PROVIDE STARTER BARS
                                            FOR BLOCK WALLS




                                                                                                                                                                                                                                                                                                           PIER
                                                                                                                                                                                                                                                     255




                                                                                                                                                                                                                                                                                                             ℄




                                                                                                                                                                                                                                                                                                                                                                                                                                  900
                                                         PIER
                                                           ℄
                                                                                                                                                                                                                                                                                                  PILE UNDER TYP

                                            PILE UNDER TYP




                                                                                                                                                                                                                                                                                                           PIER




                                                                                                                                                                                                                                                                                                                                                                                                                                                   1300
                                                                                                                                                                                                                                                                                                             ℄
                                                                                                                                                                                                                                                                                                                                                                                           REINF "C" TOP

                                                                                                      REINF "C" TOP
                                                                                                                                                                                                                                                                                                                                                                                           REINF "B" BTM

                                                                                                                                                      REINF "B" BTM




                                                                                                                                                                                                                                                     2090

                                                                                                                                                                                                                                                              2600




                                                                                                                                                                                                                                                                                                                                                                                                                                  1400




                                                                                                                                                                                                                                                                                                                                                                                                                                                                    3200
                                                                                                                                                                                                                                                                                                           PIER
                                                                                                                                                                                                                                                                                                             ℄




                                                                                                                                                                                                                                                                                                                                         REINF "A" BTM




                                                                                                                                                                                                                                                                                                                                                                 REINF "D" TOP
                                                                                                                                                                                                            REINF "A" BTM
                                                                                                                                                                                REINF "D" TOP




                                                                                                                                                                                                                                                                                                                                                                                                                                                   1300
                                                                                                                                                                                                                                                                                                           PIER
                                                                                                                                                                                                                                                                                                             ℄
                                                         PIER
                                                           ℄




                                                                                                                                                                                                                                                     255




                                                                                                                                                                                                                                                                                                                                                                                                                                  900
                                                                                                                                                                                                                                                                                                           PIER
                                                                                                                                                                                                                                                                                                             ℄
                                                                       260                                            2090                                            2090                                                                 260




                                                                                                                                                                                                                                                                                                                                                                                                                                                   300
                                                                                                                                               4700

                                                                                                                                                                                                                                                                                                                            255                          845                                       845                 255

                                                                SCHEMATIC PILE CAP PLAN - PC1                                                                                                                                                                                                                                                                                       2200
                                                                SCALE 1 : 20

                                                                                                                                                                                                                                                                                                                                SCHEMATIC PILE CAP PLAN - PC5
                                                                                                                                                                                                                                                                                                                                SCALE 1 : 20




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               NOTE:                                                          PILE CAP
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               STARTER BARS AND HOLD     PIER                                     ℄                   PIER
                                                                                                                                                                                                                                                                          INSTALL STARTER BARS FOR WALL OVER OR                                                                                                                                                                                DOWN BOLTS OMITTED
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           ℄                                                            ℄
                                                                                                                                                                                                                                                                          H.D. BOLTS FOR STEEL COLUMN OVER AS                                                                                                                                                                                  FOR CLARITY           250                                                                     250
                                                                                                                                                                                                                                                                          REQUIRED. NOT SHOWN FOR CLARITY
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               PILE UNDER TYP
                                                                                                                                                                       REFER
                                                                                                                                                                       SCHEMATIC PILE                                                                                     HEAD PIN AND EMBEDMENT DESIGNED                                                      NOTE:                                                   PILE CAP




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               250
                                                                                                                                                                       CAP PLAN                                                                                           AND CERTIFIED BY PILING CONTRACTOR                                                   STARTER BARS AND HOLD
                                                                                                                                                                                                                                                                                                                                                               DOWN BOLTS OMITTED




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        PIER
                                                                                                                                                                                                                                                                          REINFORCEMENT 'D'




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          ℄
                                                                                                                                                                                                                                                                                                                                                               FOR CLARITY
                                                                                                      GRATING AND RECESS TO LIFT                                       TOP OF FTG                                                                                                                                                                                                                                                                                                              DOWEL




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    REINF "A" BTM

                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     REINF "D" TOP
                                                                                                      MANUFACTURER'S DETAIL                                            RL VARIES




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             PILE CAP




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          LENGTH
                       PILE CAP DETAILS FOR REINFORCEMENT




                                                                                                                                                                                                                                                                                                                                                                                                                                   REINF "A" BTM

                                                                                                                                                                                                                                                                                                                                                                                                                                                    REINF "D" TOP
                                                                                     300




                                                                                                                                                                                                                                                                                                                                                                                                                                                                      LENGTH




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 ℄
                                                                                                      LOCALLY DISPLACE REINFORCEMENT                                                                                                                                                                                                                           PILE UNDER
                                                                                                                                                                                                                                                                          REINFORCEMENT 'C'
                                                                                                                                                                                                    DEPTH
                                                                                300 TYP.




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        PIER
                                                                                                                                       REFER




                                                                                                                                                                                                                                                                                                                                                               DOWEL
                                                                                                                                        PLAN




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          ℄
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               250
                                                                                                                                                                                                                                                                          REINFORCEMENT 'B'
                                                                                           150 MIN.




                                                      N16-150                                                                                                                                                                                                                                                                                                                                              REINF "B" BTM                                                                                                                                  REINF "B" BTM
                                                                                                                                                                                                                                                                          REINFORCEMENT 'A'
                                                                                                                                                                                                                                                                                                                                                                                                           REINF "C" TOP                                                                                                                                  REINF "C" TOP
                                                                                                                                                                                                                                            WIDTH (xLENGTH)
                                                                                                                                                                                                                                                                                                                                                                                                              WIDTH                                                                                                                                              WIDTH

                                                                  TYPICAL LIFT SUMP DETAIL                                                                                   STEEL SCREW
                                                                                                                                                                                                                                                                          PILES TO BE DESIGNED BY
                                                                                                                                                                                                                                                                          CONTRACTOR WITH REFERENCE
                                                                  SCALE 1:20                                                                                                 PILE. REFER PLAN FOR                                                                         TO THE GEOTECHNICAL REPORT
                                                                                                                                                                             DETAILS                                                                                      TO ACHIVE THE GIVEN PILE LOAD                                                                          SCHEMATIC PILE CAP PLAN - PC4                                                                                          SCHEMATIC PILE CAP PLAN - PC2 & PC3
                                                                                                                                                                                                                                                                                                                                                                                 SCALE: NTS                                                                                                             SCALE: NTS



                                                                                                                                                             PILE CAP SCHEDULE
                                                                                                                                                                                                                            DIMENSIONS                                                 REINFORCEMENT
                                                                                                                                                             MARK                               LENGTH                         WIDTH             DEPTH              'A'              'B'            'C'              'D'
                                                                                                                                                             PC1                                  4700                          2600              450         N16-250 U-BARS   N16-250 U-BARS N16-250 U-BARS   N16-250 U-BARS
                                                                                                                                                             PC2                                  1800                          1100              450         N16-250 U-BARS   N16-250 U-BARS N16-250 U-BARS   N16-250 U-BARS
                                                                                                                                                             PC3                                  1100                          1100              450         N16-250 U-BARS   N16-250 U-BARS N16-250 U-BARS   N16-250 U-BARS
                                                                                                                                                             PC4                                  1100                           600              450         N16-250 U-BARS   N16-250 U-BARS N16-250 U-BARS   N16-250 U-BARS
                                                                                                                                                             PC5                                  3200                          2200              450         N16-250 U-BARS   N16-250 U-BARS N16-250 U-BARS   N16-250 U-BARS




                                                                                                                                                                                                                            TYPICAL PILE CAP DETAIL
                                                                                                                                                                                                                            SCALE 1:20




      200mm       0          200    400   600   800
 1 :20


                                                                                                                                                                                                                                                                                                                                                                                                                                                                               Client                                                Status                                   Title
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                MARK BAIN                                                                                     TYPICAL SLAB AND FOOTING DETAILS - SHEET 2
                                                                                                                                                                                                                                                                                                                                                                                                                                                                               Drawn By         Designed By                          Approved By
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 Author           Designer                            Approver
                                                                                                                                                                                                                                                                                                                                                                                                                                                                               Project No.      Discipline                           Scale

                                                                                                                                                                                                                                                                                                                                                                                                   [email protected]                                                      20220173                                               1 : 20                  (at A1)

                                                                                                                                                                                                                                                                                                                                                                                                                                                                               Project Name
                                                                                                                                                                                                                                                                                                                                                                                                   37 MARY ST NOOSAVILLE, QLD                                                                                                                                                 Drawing No.                                                                         Revision
1        04.11.22 ISSUE FOR INFORMATION                                                                                                JAL      JO                                                                                                                                                                                                                                                                                                                              NOOSA VILLAS
                                                                                                                                                                                                                                                                                                                                                                                                   07 5211 1003                                                                                                                                                                S021                                                                                1
Rev        Date       Description                                                                                                       By     Chk                                                                                                                                                                                                                                                                                                                              10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 FULL SIZE ON ORIGINAL    0           10      20   30               40               50            60   70   80        90    100 mm

Section 9

                                                                     NOTE:
                                                                     STARTER BARS AND HOLD
                                                                     DOWN BOLTS OMITTED
                                                                                                     PAD FOOTING                                                                                                                                                                                           REFER PLAN FOR
                                                                                                                                                                                                                                                                                                           SLAB REINFORCEMENT
                                                                                                                                                                                                                                                                                                                                                                                                                                                                 PLUMBING NOTES
                                                                     FOR CLARITY                                                                                                        STACKS PIPE                                                                                                                                                                             PIPE PLACEMENT
                                                                                                                                                                                                                           BLOCK WALL
                                                                                                                                                                                        REFER HYDRAULICS
                                                                                                                                                                                                                           REFER DRG S050 FOR
                                                                                                                                                                                                                                                                                                                                                                                                                                                                 PLUMBING & DRAINAGE NOTES
                                                                                                                                                                                                                           DETAILS                                                                                                                                              ZONE            COMMENT
                                                                                                                                                                                                                                                                                                                                                                                A          ALLOWED - REFER TO                                                    1.    PLUMBING & DRAINAGE UNDER A SLAB SHALL BE AVOIDED WHERE PRACTICAL. PIPES MAY
                                                                                                                                                                                                                                                                                                                                                                                           THICKENING DETAIL 1.                                                        BE ENCASED IN CONCRETE OR IN RECESSES IN THE SLAB WHEN PROVIDED WITH
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       FLEXIBLE JOINTS AT THE EXTERIOR OF THE SLAB




                                                                                                                                                                                                                                                                                     EQ. EQ. EQ.
                                                                                                                                                                                                                                                                                                   ZONE A                                                                       B          ALLOWED




                                                                                                                                                                                                                                                                       FOOTING
                                                                                                                                                                                                                                                                                                                                                                                                                                                                 2.    PENETRATION OF THE EXTERNAL FOOTINGS BY PLUMBING SHALL BE AVOIDED IF




                                                                                                                                                                                                                                                                        DEPTH
                                                                                                                                                                                        2 LAYERS OF                      ISOLATION JOINT                                                           ZONE B                                                                                                                                                              POSSIBLE, BUT WHERE NECESSARY THE PIPES SHALL BE SLEEVED.
                                                                                                                                                                                                                                                                                                                                                                                C          ALLOWED - REFER TO




                                                                                                                                   REINF "D" TOP
                                                                                                                   REINF "A" BTM
                                                                                                                                                                                        ABLEFLEX                                                                                                                                                                                                                                                                 3.    JOINTS IN PLUMBING & DRAINAGE PIPES WITHIN 3m OF THE BUILDING SHALL
                                                                                                                                                                                                                                                                                                                                                                                           THICKENING DETAIL 2.




                                                                                                                                                   LENGTH
                                                                                                                                                                                                                                                                                                   ZONE C                                                                                                                                                              BE ARTICULATED & FLEXIBLE CONNECTIONS USED.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                 4.    CLOSED-CELL POLYURETHANE LAGGING, WITH A MINIMUM THICKNESS OF 40mm, SHALL
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       BE USED AROUND ALL PLUMBING & DRAINAGE PENETRATIONS THROUGH THE EXTERNAL




                                                                                                                                                                        450 AT STACKS
                                                                                                                                                                                                                                                                       BLOCKOUT IN                                                                                                                                  PENETRATION OF THE                                 FOOTINGS.
                                                                                                                                                                                                                                                                                                                                       PENETRATION OF THE                                                           EDGE BEAM BY PLUMBING
                                                                                                                                                                                                                                                                       FOOTING TO BE                                                   EDGE BEAM BY PLUMBING                                                                                                     5.    PLUMBING TRENCHES SHALL BE SLOPED AWAY FROM THE BUILDING & SHALL BE
                                                                                                                                                                                                                                                                       APPROX 2 x PIPE DIA.                                                                                                                         SHALL BE SLEEVED                                   BACKFILLED WITH CLAY IN THE TOP 300mm WITHIN 1.5m OF THE BUILDING. THE CLAY
                                                                                                                                                                                                                                                                                                                                       SHALL BE SLEEVED                                                             REFER NOTES                                        USED SHALL BE COMPACTED. WHERE PIPES PASS UNDER THE FOOTING, THE TRENCH
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       SHALL BE BACKFILLED WITH CLAY OR CONCRETE TO RESTRICT THE INGRESS OF WATER




                                                                                                                                                                                                                                                                      200 'D' EDGE




                                                                                                                                                                                                                                                                                                                                                                  'D' EDGE
                                                                                                                                                                                                                                                                      MAX BEAM




                                                                                                                                                                                                                                                                                                                                                                    BEAM
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       UNDER THE FOOTING.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                 6.    WHERE PIERS ARE USED TO SUPPORT A SLAB ON FILL, PLUMBING & DRAINAGE PIPES
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       FOUNDED WITHIN SUCH FILL, SHALL BE HUNG FROM THE SLAB MESH WITH
                                                                                   REINF "B" BTM                                                                                                                                                                                                   1
                                                                                                                                                                                                                                                                                                                                              'Z' BARS TO MATCH                                                                                                        NON-CORROSIVE STRAPS.
                                                                                                                                                                                                                                                                                                       1                                                                                                                                                         7.    WATER RUNOFF SHALL BE DRAINED AWAY FROM BUILDING DURING CONSTRUCTION.
                                                                                                                                                                                                                                                                                                                                              BEAM REINF.
                                                                                   REINF "C" TOP                                                                                                                                      CONCRETE PAD FOOTING                                                                                                                                                                   BTM. REINFORCEMENT                  8.    ALL PLUMBING & DRAINAGE MUST COMPLY WITH THE LOCAL AUTHORITY & THE NATIONAL




                                                                                                                                                                                                                                                                                                                                                                                             75
                                                                                                                                                                                                                                      REFER ADJACENT SCHEDULE                                                        3 x D MIN                                                                    1000 MIN                   50 COVER                                  PLUMBING & DRAINAGE CODE AS3500-2003.
                                                                                       WIDTH                                                                                                                                          FOR DETAILS
                                                                                                                                                                                                                                                                                                                                                                                                                                                                 PLUMBING & DRAINAGE TRENCHES
                                                                                                                                                                                                                                                                                     PIPE PENETRATION - ZONE A                                                               PIPE PENETRATION - ZONE C                                                           1.    PLUMBING & DRAINAGE TRENCHES SHALL BE LOCATED OUTSIDE THE INFLUENCE OF THE
                                                                     SCHEMATIC PAD FOOTING PLAN                                                                           TYPICAL PAD FOOTING AT PIPE LOCATIONS DETAIL                                                               BEAM THICKENING 1                                                                       BEAM THICKENING 2                                                                         FOOTINGS. THAT IS, TRENCH EXCAVATIONS SHALL NOT EXTEND BELOW A LINE DRAWN 30
                                                                     SCALE 1:20                                                                                                  SCALE 1:20                                                                                                                                                                                                                                                                            DEGREES TO THE HORIZONTAL FOR SAND, OR 45 DEGREES TO THE HORIZONTAL FOR SILT
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       OR CLAY, FROM THE BOTTOM EDGE OF THE EDGE BEAMS OR FOOTINGS IN ACCORDANCE
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       WITH CLAUSE 6.3 OF AS2870-2011.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                 2.    TRENCH BACKFILL SHALL BE COMPACTED IN ACCORDANCE WITH CLAUSE 5.5 OF
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       AS/NZS3500.3.2003 OR CLAUSE 7.2.13 OF AS/NZS3500.3.2003. SAND BEDDING & SURROUND
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       SHALL BE BLOCKED WITH A CLAY PLUG WHEREVER TRENCHES PASS UNDER THE EDGE
                                                                                                                                                                                                                                                                                                                                                                                                                                                                       OF ANY SLAB.




                                                                                                          BLOCK WALL
                                                                                                          REFER DRG S050 FOR
                                                                                                          DETAILS                                                                                                                                                                                                                         FILL TO UNDERSIDE OF FOOTING
                                                                                                                                                                                                                                                                                                                                          WITH MASS CONCRETE. PIPE TO
                                                                                                          ISOLATION JOINT
                                                        200 MIN




                                                                                                                                                                                                                                                                                                                                          BE SLEEVED. REFER NOTES.




                                                                                                                                                                                                                                                                                                             MIN
                                                                                                                                                                                                                                                                                                             200
                                                                                                                               REINFORCEMENT 'D'

                                                                                                                                                                                                                                                                                                                                          DIMENSIONS OF ADDITIONAL CONCRETE ARE
                                                                                                                                                                                                                                                                                                                           630 MIN        MINIMUM. CONCRETE THICKENINGS AND
                                                                                                                                                                                                                                                                                                                                          FOOTINGS ARE TO BEAR ON TARGET NATURAL
                                                                                                                                                                                                                                                                                                                                          GROUND OR ENGINEERED FILL. FOOTINGS ARE
                                                                                                                               REINFORCEMENT 'C'                                                                                                                                                                                          NOT BE CAST ON BEDDING SAND FROM
                                                        DEPTH




                                                                                                                                                                                                                                                                                                                                          SERVICES TRENCHES.
                                                                                                                               REINFORCEMENT 'B'

                                                                                                                               REINFORCEMENT 'A'                                                                                                                EDGE/INTERNAL BEAM OVER SERVICE CONNECTION
                                                                                                                                                                                                                                                                SCALE 1:20



                                 15 MPa BLINDING AS REQUIRED TO                   WIDTH (x LENGTH)
                                 ACHIEVE 150 SOCKET INTO NATURAL
                                 MATERIAL WITH MINIMUM ALLOWABLE
                                 BEARING CAPACITY AS SHOWN IN
                                 FOUNDATION NOTES ON DRG. S001

                  PAD FOOTING SCHEDULE
                                                       DIMENSIONS                                          REINFORCEMENT
                  MARK                     LENGTH         WIDTH          DEPTH            'A'            'B'            'C'            'D'                                                                                                                                                                                                                                                                                         GRATED DRAIN AS PER HYD.
                                                                                                                                                                                                                                                                                                                                                                                                                                   ENGINEERS DETAILS
                  PF1                        1600          1600           450       N16-300 U-BARS N16-300 U-BARS N16-300 U-BARS N16-300 U-BARS
                  PF2                        1400          1400           450       N16-300 U-BARS N16-300 U-BARS N16-300 U-BARS N16-300 U-BARS                                                                                                                                                                                                                                                                                    1 N12 TRIMMER
                  PF3                        1800           700           450       N16-300 U-BARS N16-300 U-BARS N16-300 U-BARS N16-300 U-BARS                                                                                                                                                                                                                                            1 N12 TRIMMER                           SLAB MESH
                                                                                                                                                                                                                   400          1N12 CONTINUOUS TRIMMER
                                                                                                                                                                                                                                                                                                                                     1 N12                                                                                         REFER PLAN.
                                                                                                                                                                                                                                LAP AS REQUIRED
                                                                                                                                                                                                                                                                                                                                     CONTINUOUS
                                                       TYPICAL PAD FOOTING DETAIL                                                                                                                                                  50 MAX. STEP                                                                                      TRIMMER                                        FALL                                                   FALL
                                                        SCALE 1:20




                                                                                                                                                                                                                                                                                                                                        200




                                                                                                                                                                                                                                                                                                                                                                                                                                                                MIN.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                150
                                                                                                                                                                                                                                                                                                                     250
                                                                                                                                                                                                                         LAP MESH 300 MIN.
                                                                                                                                                                                                                                                                                                                                                                                                             200                   N12 AT 400 'U' BARS
                                                                                                                                                                                                                         DASHED LINE DENOTES                                                                                                                                                                 TYP.                  LAP 450 WITH MESH
                                                                                                                                                                                                                         VISQUEEN MEMBRANE                                                                                                                                                                                         75 BOTTOM COVER
                                                                                                                                                                                                                                                                                                                                                                                                                                   3 N12


                                                                                                                                                                                                  TYPICAL SLAB SETDOWN 50mm HIGH MAX.                                                TYPICAL EDGE THICKENING                                                                           TYPICAL GRATED DRAIN DETAIL
                                                                                                                                                                                                                                                                                                                                                                                       SCALE 1:20
                                                                                                                                                                                                      SCALE 1:20
                                                                                                                                                                                                                                                                                     DETAIL - ET1
                                                                                                                                                                                                                                                                                     SCALE 1:20




      200mm        0          200    400   600   800
 1 :20


                                                                                                                                                                                                                                                                                                                                                                                                                    Client                                                  Status                                   Title
                                                                                                                                                                                                                                                                                                                                                                                                                     MARK BAIN                                                                                       TYPICAL SLAB AND FOOTING DETAILS - SHEET 3
                                                                                                                                                                                                                                                                                                                                                                                                                    Drawn By                      Designed By               Approved By
                                                                                                                                                                                                                                                                                                                                                                                                                      Author                        Designer                  Approver
                                                                                                                                                                                                                                                                                                                                                                                                                    Project No.                   Discipline                Scale

                                                                                                                                                                                                                                                                                                                                                    [email protected]                                          20220173                                                 1 : 20                  (at A1)

                                                                                                                                                                                                                                                                                                                                                                                                                    Project Name
                                                                                                                                                                                                                                                                                                                                                    37 MARY ST NOOSAVILLE, QLD                                                                                                                                       Drawing No.                                      Revision
1        04.11.22 ISSUE FOR INFORMATION                                                                                                                     JAL   JO                                                                                                                                                                                                                                                 NOOSA VILLAS
                                                                                                                                                                                                                                                                                                                                                    07 5211 1003                                                                                                                                                      S022                                             1
Rev        Date        Description                                                                                                                          By    Chk                                                                                                                                                                                                                                                10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm

Section 10

                                            PARCHEM FOSROC
                                            "ROADSEAL" OR
                                            APPROVED EQUIV




                                                                                            40mm.
                                            BOND BREAKING TAPE

                                            PARCHEM FOSROC
                                            "EXPANDAFOAM ROD"                              6mm.
                                            OR SIMILAR                                                                                  FACE OF WALL / FOOTING                                                                 R16 HDG DOWELS SAWCUT 400 LG                       10mm COMPRESSIBLE FILLER BOARD                    R16 HDG DOWELS SAWCUT 400 LG
                                                                                                                                        10mm COMPRESSIBLE                                                                      AT 400 CRS GREASE ONE END                          WITH APPROVED SEALANT                             AT 400 CRS GREASE ONE END
                                                                                                                                        FILLER BOARD WITH                                                                      STOP BARS 600mm FROM                                                                                 STOP BARS 600mm FROM
                                            40 DEEP x 6 WIDE                               CUT EVERY 2ND CROSS                                                                                                                 JOINT INTERSECTIONS                                STOP REINFORCEMENT                                JOINT INTERSECTIONS                        STOP REINFORCEMENT
                                                                                                                                        APPROVED SEALANT
                                            SAWCUT REFER DETAIL                            BAR 25 CLEAR OF JOINT                                                                                                                                                                  25 CLEAR OF JOINT                                                                            25 CLEAR OF JOINT
                                            18HRS AFTER POUR




                                                                                                                                          150 MIN.




                                                                                                                                                                                                                                75




                                                                                                                                                                                                                                                                                                                                    75
                                                                                                                                                                                                                        150




                                                                                                                                                                                                                                                                                                                              150
                                            NOTE: DEPRESS MESH LOCALLY                              INDUCED CRACK
                                            TO MAINTAIN COVER                                                                                                                                                                                        200      200       200           2 N16 CONTINUOUS SUPPORT BARS                                   200          200   200     2 N16 CONTINUOUS SUPPORT BARS
                                                                                                                                       TYPICAL ISOLATION JOINT (IJ)                                                                                                                   ON CHAIRS AND DISCS
                                                                                                                                                                                                                                                                                      BARS NOT CONTINUOUS THROUGH
                                                                                                                                                                                                                                                                                                                                                                                 ON CHAIRS AND DISCS
                                                                                                                                                                                                                                                                                                                                                                                 BARS NOT CONTINUOUS THROUGH
                                                                                                                                       SCALE 1:10                                                                                                                                     JOINT INTERSECTIONS                                                                        JOINT INTERSECTIONS

                                              TYPICAL SAWN JOINT (SJ1)                                                                                                                                                        TYPICAL DOWELLED EXPANSION JOINT DETAIL (DEJ1)                                                         TYPICAL DOWELLED JOINT DETAIL (DJ1)
                                              SCALE 1:10                                                                                                                                                                      SCALE 1:10                                                                                             SCALE 1:10
                                              NOTE:      JOINT TO BE AIR BLASTED PRIOR TO APPLICATION OF SEALANT.
                                                         REFER TO MANUFACTURERS SPECIFICATION FOR EARLIEST
                                                         CUTTING TIME.




                                                                                                                                                                                   JOINT




                                                                                                                                                                                                                                             JOINT




                                                                                                                                                                                                                                                                                                                      JOINT
                                                                                                                                                              ISOLATION JOINT.                                ISOLATION JOINT.                             ISOLATION JOINT
                                                                                                                                                              ALL AROUND                                      ALL AROUND                                   ALL AROUND
                                                                                                                                                              COLUMN/WALL. REFER                              COLUMN/WALL. REFER                           COLUMN/WALL. REFER
                                                                                                                                                              TYPICAL DETAIL.                                 TYPICAL DETAIL.                              TYPICAL DETAIL.
                                                                                                                                                                                                                                                                            400                                                             400
                                                                                                                                                                                                                               JOINT                                       TYP.                                                             TYP.


                                                                                                                                                                                                                                                                                           JOINT                                                     JOINT




                                                                                                                                                                                                                                                                                                                                             ISOLATION JOINT
                                                                                                                                                                                                                                                                                                                                             ALL AROUND
                                                                                                                                                                                                                                                                                                                                             COLUMN/WALL. REFER
                                                                                                                                                                                                                                                                                                                                             TYPICAL DETAIL.
                                                            2 N12 x 1200 LONG




                                                                                                                                                                                                                                                                                                                      JOINT
                                                            TRIMMER BARS
                                                            AT 100 CRS. TOP &
                                                            BTM. TYP.


                  SQUARE / RECTANGULAR COLUMN PENETRATION                                            SQUARE / RECTANGULAR COLUMN/WALL PENETRATION                         SQUARE / RECTANGULAR COLUMN/WALL PENETRATION                 SQUARE / RECTANGULAR COLUMN/WALL PENETRATION SQUARE / RECTANGULAR COLUMN/WALL PENETRATION
                                                                                                     TYPE 1                                                               TYPE 2                                                       TYPE 3                                       TYPE 4
                                                                                                                    JOINT




                                                                                                                                                                           SLAB EDGE
                                                                                  60.
                                                                                     00°




                                                                                                                                                           JOINT



                                                                                JOINT/SLAB EDGE
                                               GE
                                             ED
                                              AB




                                                                    N12 'V' SHAPED TRIMMER
                                           /SL




                                                                    BARS PLACED IN CORNERS
                                       INT




                                                                    LESS THAN 60 DEGREES
                                    JO




                                                            ANGLED CORNER                                                   JOINT TERMINATION                                              RE-ENTRANT SLAB
                                                                                                                                                                                           CORNER / SETDOWN



                                           TYPICAL SLAB ON GROUND TRIMMER BAR PLACEMENT SCHEMATIC
                                           NTS.
                                           TO BE PLACED AT ALL COLUMNS, WALLS, PITS, FLOOR WASTES, ETC THAT CAUSE A PENETRATION
                                           THROUGH THE SLAB OR A RE-ENTRANT CORNER. REFER NOTES.




      100mm       0          100          200       300   400
 1 :10


                                                                                                                                                                                                                                                                                                                                                                                                    Client                             Status                                Title
                                                                                                                                                                                                                                                                                                                                                                                                     MARK BAIN                                                               TYPICAL SLAB AND FOOTING DETAILS - SHEET 4
                                                                                                                                                                                                                                                                                                                                                                                                    Drawn By         Designed By       Approved By
                                                                                                                                                                                                                                                                                                                                                                                                      Author           Designer         Approver
                                                                                                                                                                                                                                                                                                                                                                                                    Project No.      Discipline        Scale

                                                                                                                                                                                                                                                                                                                                                   [email protected]                           20220173                          As indicated           (at A1)

                                                                                                                                                                                                                                                                                                                                                                                                    Project Name
                                                                                                                                                                                                                                                                                                                                                   37 MARY ST NOOSAVILLE, QLD                                                                                                Drawing No.                                      Revision
1        04.11.22 ISSUE FOR INFORMATION                                                                                                              JAL     JO                                                                                                                                                                                                                                      NOOSA VILLAS
                                                                                                                                                                                                                                                                                                                                                   07 5211 1003                                                                                                               S023                                             1
Rev        Date       Description                                                                                                                    By      Chk                                                                                                                                                                                                                                     10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                                                                                                                                                                FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm

Section 11

                                                                                                                                                                      N12-200 'U' BARS
                                                                                                       COG BARS WHERE WALL                                            LAP 450
                                                                                                       TERMINATES AT SLAB




                                                                                                             75
                                    FLOOR                                                                                                                                                                                                                        NOTE: LAYING SEQUENCE OF WALL REINFORCEMENT
                                    RL VARIES                                                                                                                                                                                                                    FOR WALL WITH 2 LAYERS OR STEEL MAY BE DETERMINED
                                                                                                                                                                MAIN REINFORCEMENT                  N12-200 'U' BARS      N12-200 'L' BARS                       BY BUILDER TO SUIT FORMWORK ie. VERTICAL BARS MAY
                                                                                                                                                                AS PER TYPICAL WALL                 LAP 450               LAP 450                                BE CLOSEST TO THE FIRST SHUTTER. SO THAT
                                                                                                                                                                TYPE DETAILS                                                                                     INSTALLATION OF HORIZONTAL BARS IS EASIEST
                                                                                                                                                                                                   MAIN REINFORCEMENT     MAIN REINFORCEMENT
                                                                                                                                                                                                   AS PER TYPICAL WALL    AS PER TYPICAL WALL
                                                                                                                                                      PLAN - WALL END DETAIL                       TYPE DETAILS.          TYPE DETAILS.
                                                                                                       VERTICAL BARS
                                                                                                       EACH FACE
                                                                                                       REFER SCHEDULE
                                                                                                                                                                                                   PLAN - CORNER DETAIL             PLAN - INTERSECTION DETAIL
                                                                                                       HORIZONTAL BARS:
                                                                                                       REFER SCHEDULE


                                                                                                       WIDTH VARIES
                                                                                                      REFER SCHEDULE
                                                                                                                                                                                         TYPICAL CONCRETE WALL JUNCTION DETAILS
                                                              LAP VETICAL BARS
                                                               REFER DRG S001




                                                                                                                                                                                         SCALE 1:20 U.N.O.

                                                                                                       STARTER BARS TO
                                                                                                       MATCH VERTICAL
                                                                                                       REINFORCEMENT

                                    WALL BASE
                                    FLOOR RL VARIES




                                                                                                300
                                                                                                COG


                                                              TYPICAL WALL SECTION
                                                              SCALE 1:20


                                     WALL SCHEDULE
                                     MARK               VERT REINF.              HORIZ REINF.   DESCRIPTION                  REMARKS
                                     CW1                 S12-200 EF               S12-200 EF    200 THICK CONCRETE           POOL WALLS




      200mm       0          200    400     600   800
                                                                                                                                                                                                                                                                                                                                                                                                     INFORMATION
 1 :20
                                                                                                                                                                                                                                                                                                                                                                                                         NOT FOR CONSTRUCTION
                                                                                                                                                                                                                                                                                                                     Client                             Status                                   Title
                                                                                                                                                                                                                                                                                                                      MARK BAIN                          INFORMATION
                                                                                                                                                                                                                                                                                                                                                                                                 TYPICAL CONCRETE WALL DETAILS
                                                                                                                                                                                                                                                                                                                     Drawn By         Designed By       Approved By
                                                                                                                                                                                                                                                                                                                       JAL              JM               JO
                                                                                                                                                                                                                                                                                                                     Project No.      Discipline        Scale

                                                                                                                                                                                                                                                                            [email protected]                   20220173         STRUCTURAL         1 : 20                  (at A1)

                                                                                                                                                                                                                                                                                                                     Project Name
                                                                                                                                                                                                                                                                            37 MARY ST NOOSAVILLE, QLD                                                                                           Drawing No.                                      Revision
1        04.11.22 ISSUE FOR INFORMATION                                                                                                   JAL   JO                                                                                                                                                                    NOOSA VILLAS
                                                                                                                                                                                                                                                                            07 5211 1003                                                                                                          S030                                             1
Rev        Date       Description                                                                                                         By    Chk                                                                                                                                                                   10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                                                                                    FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm

The text continues on section 12.

Used in these records

About this file

File size
10.3 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Structural Plans 20220173 - 10 Natasha Structural Issue 190123.pdf · 10.3 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.