Structural Plans 20220173 - 10 Natasha Structural Issue 190123 · OPW22/0299

of 56

Plans and drawings: the text below has words only, no drawings.

Very large file (10.3 MB): may take a few minutes to open.

Log in to see the plans as drawn

Original PDF page 2, section 1. The text section number identifies this passage in the reader.

                                                                                                 CONCRETE NOTES                                                                       CONCRETE NOTES CONT.                                                                     STRUCTURAL STEEL NOTES                                                              STRUCTURAL STEEL NOTES CONT.
      GENERAL NOTES                                                                              C1   ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 3600 CURRENT       C29 ALL UNREINFORCED MASONRY WALLS ARE TO BE SEPARATED FROM ABUTTING                     S1 DESIGN CONFORMS TO AS 4100. FABRICATION & ERECTION SHALL BE CARRIED OUT IN        S20 FOR EACH GROUP OF ANCHOR BOLTS PROVIDE A TEMPLATE WITH SETTINGS OUT
       G1.     THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL ARCHITECTURAL AND                 EDITION WITH AMENDMENTS. ALL CONCRETE SHALL BE PLACED AND CURED IN                  CONCRETE WITH TWO LAYERS OF SUPER ALCOR.                                                ACCORDANCE WITH THE PROVISIONS OF AS 4100.                                            LINES CLEARLY MARKED FOR POSITIONING THE BOLTS WHEN CASTING IN
               OTHER CONSULTANTS DRAWINGS AND SPECIFICATIONS AND WITH SUCH OTHER                      ACCORDANCE WITH SECTION 19 AS 3600 WHERE CURING COMPOUND IS USED IT MUST BE
               WRITTEN INSTRUCTIONS AS MAY BE ISSUED DURING THE COURSE OF THE CONTRACT.               APPLIED: (A) ONTO SLABS WITHIN 2 HOURS OF FINISHING OPERATION. (B) ONTO WALLS   C30 MASONRY WALLS NOT COINCIDING WITH LOAD BEARING WALLS UNDER MUST NOT BE               S2 UNLESS NOTED OTHERWISE, ALL STEEL SHALL CONFORM WITH THE FOLLOWING                S21 GALVANISING SHALL BE TO AS 4680 (MEMBERS) OR AS 1214
               ALL DISCREPANCIES SHALL BE REFERRED TO THE ARCHITECT OR SUPERINTENDENT FOR             AND COLUMNS IMMEDIATELY AFTER REMOVAL OF FORMWORK (NB PVA CURING                    BUILT ON CONCRETE SLABS OR BEAMS UNTIL FORMWORK SUPPORTING SAME HAS                     AUSTRALIAN STANDARDS IN RESPECT OF GRADE & CONDITIONS OF SUPPLY
               DECISION BEFORE PROCEEDING WITH THE WORK.                                              COMPOUND IS NOT ACCEPTABLE, USE WAX OR RESIN EMULSION, POLYTHENE SHEETING           BEEN REMOVED. DISTRIBUTE MASONRY ON SLAB PRIOR TO CONSTRUCTING WALLS.                                                                                                            THREADED FASTENERS
                                                                                                      OR CONTINUOUS SPRAYS.) HORIZONTAL FORMWORK SHALL BE STRIPPED WHEN                                                                                                               ROLLED SECTIONS:            AS3679.1GRADE 300                                        COATING MASS: AVERAGE - 600 GRAMS PER SQ. METRE
       G2.     ALL DIMENSIONS RELEVANT TO SETTING OUT AND OFF SITE WORK SHALL BE VERIFIED             APPROVED BY THE ENGINEER.                                                       C31 FIRST SLAB BAR IS TO BE POSITIONED MAX 100mm FROM FACE OF BEAMS, R.C.C WALLS                WELDED SECTIONS:            AS3679.2GRADE 300
               BY THE CONTRACTOR BEFORE CONSTRUCTION AND FABRICATION IS COMMENCED. THE                                                                                                    AND SLAB THICKENINGS PARALLEL TO BAR. FIRST BEAM TIE TO BE PLACED MAXIMUM                   FLAT BARS:                  AS3679.1GRADE 300                                        MEMBERS
               ENGINEER'S DRAWINGS SHALL NOT BE SCALED. SEE ARCHITECTURAL DRAWINGS FOR           C2   LAPS TO REINFORCEMENT:                                                              50mm FROM FACE OF COLUMN OR SUPPORTING WALL UNDER.                                          PLATE/FLOOR PLATE:          AS3678GRADE 250                                          COATING MASS: MINIMUM - 550 GRAMS PER SQ. METRE
               ALL RELEVANT DIMENSIONS.                                                                  BAR           SLABS & WALL           BEAMS                                                                                                                                   HOLLOW SECTIONS             AS1163GRADE C300
                                                                                                         N12               550             700                                        C32 THE SUB CONTRACTOR SHALL GIVE AT LEAST 24 HOURS NOTICE SO THAT INSPECTION                   PURLINS & GIRTS             AS1397G450 Z350                                   S22 PROVIDE SURVEY CERTIFICATES RELATING TO ERECTED STEELWORK THAT CONFIRM
       G3.     DURING CONSTRUCTION THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING                   N16               750             950                                            MAY BE MADE OF THE FOLLOWING:                                                                                                                                                 THAT TOLERANCES COMPLY WITH SECTION 15 OF AS 4100.
               THE STRUCTURE IN A STABLE CONDITION AND ENSURING NO PART SHALL BE OVER                    N20               950             1300                                            - MEMBRANE INSTALLATION THE SUB BASE (WHERE APPLICABLE)                                 COPIES OF TEST CERTIFICATES CONFIRMING CONFORMANCE TO THE ABOVE
               STRESSED UNDER CONSTRUCTION ACTIVITIES.                                                   N24              1200              1550                                           - REINFORCEMENT & TENDONS FIXED IN PLACE                                                STANDARDS AND GRADES ISSUED BY SUPPLIER OF THE STEEL SHALL BE SUPPLIED TO        S23 REMOVE ALL TEMPORARY CLEATS ON COMPLETION AND RESTORE THE SURFACE IN
                                                                                                         N28              1450              1900                                           - CORES & EMBEDMENTS FIXED IN PLACE                                                     RECOR CONSULTING.                                                                    AN APPROVED MANNER.
       G4.     WHERE EXCAVATION WORK IS TO BE CARRIED OUT ADJACENT TO EXISTING FOOTINGS.                 N32              1700              2300                                           - NO CONCRETE SHALL BE PLACED UNTIL INSPECTION IS COMPLETED
               THE EXACT LEVEL OF THE UNDERSIDE OF THE FOOTING SHALL BE OBTAINED BY TEST                                                                                                                                                                                       S3 MEMBER SIZES SHALL BE AS SHOWN ON THE STRUCTURAL DRAWINGS.                        S24 GROUT UNDER ALL BASE PLATES. BEFORE GROUTING, SUPPORT BASE PLATES ON
               PITS PRIOR TO EXCAVATION UNDERPINNING AND SHORING OF THE STRUCTURE SHALL                8TM                 450                                                        C33 CONSTRUCTION SUPPORT PROPPING SHALL BE LEFT IN PLACE AS REQUIRED IN ORDER               NO SUBSTITUTION IS PERMITTED WITHOUT AGREEMENT OF RECOR CONSULTING.                   STEEL PACKERS OR WEDGES. GROUT UNDER BASE PLATES AND INTO CORED HOLES
               BE CARRIED OUT AS DETAILED AND THE EXISTING STRUCTURE SHALL BE MAINTAINED IN            11TM                 650                                                           TO AVOID OVERSTRESSING A COMPLETED FLOOR DUE TO CONSTRUCTION LOADING. ALL                                                                                                     WITH CONBEXTRA GP NON-SHRINK GROUT OR EQUIVALENT, MINIMUM COMPRESSIVE
               A STABLE AND UNDAMAGED              CONDITION.                                                                                                                             BACK PROPPING SHALL BE APPROVED BY RECOR CONSULTING.                                 S4 THE CONTRACTOR SHALL PREPARE WORKSHOP (SHOP DETAIL) DRAWINGS AND SHALL                STRENGTH 20MPa,MIN. THICKNESS 15mm, MAX. THICKNESS 40mm
                                                                                                 C3   CONCRETE STRENGTH GRADE & COVER FOR PARTICULAR ELEMENTS SHALL BE AS                                                                                                         SUBMIT EITHER AN ELECTRONIC PDF FILE OR TWO HARD COPIES OF EACH DRAWING FOR
       G5.     ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH THE RELEVANT                 FOLLOWS UNLESS NOTED OTHERWISE:                                                 C34 IF PLASTIC SHRINKAGE OF THE CONCRETE IS OBSERVED DUE TO RAPID DRYING OR                 EXAMINATION OF CONNECTION DETAILS. FABRICATION SHALL NOT COMMENCE UNTIL           S25 STRUCTURAL STEEL TO BE CONCRETE ENCASED SHALL BE UNPAINTED AND
               CURRENT S.A.A. CODES (INCLUDING ALL AMENDMENTS) AND THE LOCAL STATUTORY                                                                                                    OTHER CONDITIONS, APPLY A SINGLE SPRAY COAT OF ALIPHATIC ALCOHOL                        THE WORKSHOP DRAWINGS HAVE BEEN REVIEWED, A REVIEW WILL BE PROVIDED FOR               WRAPPED WITH SL41 FABRIC. THE GAP BETWEEN THE STRUCTURAL STEEL AND THE
               AUTHORITIES REQUIREMENTS. EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.                 ELEMENT                       COVER         CONCRETE STRENGTH GRADE               EVAPORATION RETARDANT ("MASTERKURE 111CF-CONFILM" BY MASTER BUILDERS OR                 MEMBER SIZES AND CONNECTION DETAILS, BUT WILL NOT EXTEND TO DIMENSIONS. ALL           FABRIC SHALL BE 25mm. THE MINIMUM COVER TO THE FABRIC SHALL BE 50mm.
                                                                                                        FOOTINGS                      50mm                   25 MPa                       EQUAL APPROVED) IMMEDIATELY AFTER SCREEDING. NOTE: "CONFILM" IS NOT A CURING            DIMENSIONS AND SETOUTS SHALL BE OBTAINED FROM ARCHITECTURAL DRAWINGS.
       G6.     ALL DIMENSIONS ARE IN MILLIMETERS UNLESS STATED OTHERWISE. ALL LEVELS ARE                SLAB ON GROUND                30mm                   32 MPa                       COMPOUND.                                                                               SHOULD VARIATIONS BE NECESSARY TO THE STRUCTURAL DETAILS PROVIDED, THESE          S26 ROOF AND/OR WALL SHEETING SHALL BE FIXED TO PURLINS OR GIRTS IN
               EXPRESSED IN METRES.                                                                     SUSPENDED SLAB - INTERNAL     30mm                   40 MPa                                                                                                               SHALL BE REFERRED TO RECOR CONSULTING FOR APPROVAL BEFORE BEING INCLUDED              ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
                                                                                                        SUSPENDED SLAB - EXTERNAL     40mm                   40 MPa                   C35 LOW HEAT CONCRETE SHALL BE USED FOR ALL BEAMS THAT ARE DEEPER THAN 700mm                ON SHOP DETAIL DRAWINGS. SHOP DETAILS SHALL PROVIDE FOR FIXING OR SUPPORT
       G7.     CONSTRUCTION OF ANY MASONRY WALLS OR OTHER PERMANENT LOADING MUST NOT                                                                                                      AND HAVE A WIDTH GREATER THAN 1200mm. LOW HEAT CONCRETE SHALL BE TESTED IN              OF ANY BUILDING ELEMENTS SHOWN ON ARCHITECTURAL DRAWINGS. SHOULD                  S27 ALL SUNDRY ITEMS SUCH AS GUTTER SUPPORTS, CEILING AND ARCHITECTURAL
               BE BUILT ON CONCRETE SLABS OR BEAMS UNTIL FORMWORK SUPPORTING SAME HAS                   MAX. AGGREGATE SIZE = 20mm SLUMP = 100mm +/- 15mm                                 ACCORDANCE WITH AS 1012 METHOD 22 PART B SEMI-ADIABATIC TEMPERATURE RISE                VARIATIONS BE NECESSARY TO THE STRUCTURAL DETAILS PROVIDED, THESE SHALL BE            ELEMENTS, FIXTURES ARE TO BE ALLOWED FOR IN THE PRICING BY THE TENDERER
               BEEN REMOVED. HOWEVER PROPS AND FORMWORK SHALL NOT BE REMOVED BEFORE                     (AT POINT OF DISCHARGE)                                                           OF CONCRETE. THE TEMPERATURE RISE IS TO BE LESS THAN 30°C. TRIAL MIXES WITH             REFERRED TO RECOR CONSULTING FOR APPROVAL BEFORE BEING INCLUDED ON SHOP               AS PER ARCHITECT'S DETAILS.
               THE MINIMUM TIME SPECIFIED. DISTRIBUTE    MASONRY EVENLY ON SLAB ADJACENT                                                                                                  TEST RESULTS ARE TO BE SUBMITTED FOR APPROVAL. LOW HEAT CONCRETE IS TO                  DETAIL DRAWINGS. SHOP DETAILS SHALL PROVIDE FOR FIXING OR SUPPORT OF ANY
               TO ITS FINAL POSITION PRIOR TO CONSTRUCTING WALLS.                                C4   MIX DESIGNS SHALL BE SUBMITTED FOR APPROVAL. THE USE OF BLENDED CEMENTS,            HAVE A DELIVERY TEMPERATURE OF LESS THAN 27°C. SECTIONS CAST WITH LOW HEAT              BUILDING ELEMENTS SHOWN ON ARCHITECTURAL DRAWINGS.                                S28 THE BUILDER SHALL PROVIDE ALL CLEATS AND HOLES FOR FIXING STEEL TO STEEL,
                                                                                                      FLYASH AND/OR CHEMICAL ADMIXTURES WILL NOT BE PERMITTED EXCEPT WITH PRIOR           CONCRETE ARE TO BE INSULATED BY USING PLYWOOD FORMWORK WHICH IS TO                                                                                                            TIMBER TO STEEL AND TIMBER TO TIMBER. AS REQUIRED BY ENGINEERING AND
       G8.     ALL NON LOAD BEARING WALLS SHALL BE KEPT CLEAR OF THE UNDERSIDE OF SLABS               APPROVAL OF RECOR CONSULTING IN WRITING. IF FLYASH IS USED WITH APPROVAL            REMAIN IN PLACE FOR A MINIMUM OF 5 DAYS AFTER PLACING. ALSO THE TOP SURFACE                                                                                                   ARCHITECTURAL INTENT WHETHER SHOWN OR NOT.
                                                                                                                                                                                                                                                                                      SHOP DETAIL DRAWINGS SHALL CLEARLY INDICATE:
               AND BEAMS BY 20mm UNLESS OTHERWISE SHOWN.                                              THEN THIS SHOULD NOT EXCEED 80KG/PER cu. m. CONCRETE AGGREGATE SHALL                OF THE BEAM IS TO BE INSULATED WITH TWO SHEETS OF FORMPLY OR SIMILAR                         : DIMENSIONS OF ITEMS, IDENTIFICATION, STEEL GRADE
                                                                                                      CONSIST OF CRUSHED RIVER GRAVEL OR BASALT IN ACCORDANCE WITH AS 2758.1. SLAG        APPROVED MATERIAL FOR A PERIOD OF 5 DAYS.                                                    : PROCEDURES NECESSARY FOR SHOP AND SITE ASSEMBLY                            S29 ALL STRUCTURAL STEELWORK BELOW GROUND TO BE ENCASED BY N25 75mm ALL
       G9.     REFER ARCHITECT'S DRAWINGS FOR ANY DEMOLITION REQUIREMENTS.                            AGGREGATES WILL NOT BE PERMITTED. CALCIUM CHLORIDE WILL NOT BE PERMITTED                                                                                                                                                                                          ROUND U.N.O.
                                                                                                                                                                                                                                                                                       : LOCATION, TYPE AND SIZE OF WELDS AND BOLTS
                                                                                                      AND SHALL NOT BE USED UNDER ANY CIRCUMSTANCE.                                                                                                                                    : ORIENTATION OF MEMBERS
                  DESIGN CRITERIA                                                                                                                                                                                                                                                                                                                                   S30 FOR GALVANISED COATINGS, REPAIR FIELD DAMAGE AND SITE WELDS WITH TWO
                                                                                                                                                                                                                                                                                       : CAMBER OR PRESET (IF ANY)
                  LIVE LOADS                                                                     C5   PROJECT ASSESSMENT SHALL BE IN ACCORDANCE WITH AS 1379 & AS 3600. ALL           TIMBER NOTES                                                                                     : LOCATION OF TEMPORARY CONNECTIONS AND BRACING                                  COATS OF A TWO PACK EPOXY POLYAMIDE ZINC-RICH PAINT CONTAINING A MINIMUM
                  ROOF                                0.25kPa                                         ORGANISATIONS RESPONSIBLE FOR TESTING AND ASSESSMENT OF CONCRETE AND            T1    ALL TIMBER FRAMING TO BE MIN. H3 TREATED. ALL HARDWOODS TO BE DURABILITY                                                                                                    OF 92% ZINC DUST IN THE DRY FILM WHICH SHALL BE BUILT UP TO 0.075mm MINIMUM.
                                                                                                                                                                                                                                                                                       : SURFACE PREPARATION METHOD AND COATING SYSTEM
                  INTERNAL FLOORS                     1.5kPa                                          CONCRETE MATERIALS SHALL BE NATA REGISTERED. SAMPLING AND TESTING SHALL BE            CLASS 1.                                                                                   : WELDING AND BOLTING CATEGORIES
                  BATHROOMS                           2.0kPa                                          TO AS 1012. ACCEPTANCE CRITERIA - AVERAGE MUST EXCEED REQUIRED VALUE, NO        T2    EXPOSED FRAMING                                                                                                                                                         S31 FOR PAINT COATINGS, REPAIR FIELD DAMAGE AND SITE WELDS USING THE SAME
                  BALCONIES                           2.0kPa                                          SAMPLE TO BE LESS THAN 85% OF REQUIRED VALUE. SUBMIT TEST RESULTS OF PROJECT          (EXPOSED FRAMING REFERS TO ALL TIMBER FRAMING THAT MAY BE SUBJECT TO               S5 ALL WELDING SHALL BE CARRIED OUT IN ACCORDANCE WITH AS 1554.1. ELECTRODES             PARENT COATING SYSTEM. SUCCESSIVE PAINT LAYERS SHALL BE ABRADED TO A
                                                                                                      ASSESSMENT TO RECOR CONSULTING.                                                       PERIODIC WETTING)                                                                     SHALL BE TO AS 1553, AS1858 AS 2203 OR AS 2717 AS APPROPRIATE. WELDS FOR              FEATHERED EDGE OF APPROXIMATELY 25mm WIDTH PER LAYER. MECHANICALLY
                  WIND LOADS                                                                                                                                                                         - ALL EXPOSED FRAMING TO BE EITHER H3 PRESSURE TREATED OR DURABILITY                                                                                               GRIND SURFACES TO ACHIEVE SMOOTH AND BRIGHT METAL COMPARABLE TO CLASS
                                                                                                                                                                                                                                                                                  STRUCTURAL CONNECTIONS SHALL BE WELD CATEGORY SP UNLESS NOTED OTHERWISE
                  REGION                              B1                                         C6   SUPPLY OF READY MIXED CONCRETE SHALL COMPLY WITH AS 1379.                                        CLASS 1 (MINIMUM) SAWN TIMBER (U.N.O.)                                                                                                                           2.5. PAINT REINSTATEMENT SHALL FULLY COVER THE FEATHERED PART OF THE SAME
                  TERRAIN CATEGORY                    2.5 (N); 3 (S, E, W)                                                                                                                           - FRAMING MEMBERS EXPOSED TO MOISTURE (JOISTS, BEARERS, ETC.) ARE TO      S6 UNLESS OTHERWISE SHOWN, ALL CONNECTIONS SHALL BE AS SHOWN IN                          LAYER.
                  IMPORTANCE LEVEL                    2                                          C7   ALL CONCRETE SHALL BE MOISTURE CURED FOR (7) DAYS AFTER POURING, BY AN                           BE MALTHOID CAPPED AND PENETRATING NAILS SHOULD BE CONSTRUCTED TO          "STANDARDISED STRUCTURAL CONNECTIONS" PUBLISHED BY AUSTRALIAN STEEL
                  REGIONAL WIND SPEED                 V500(57m/s)                                     APPROVED METHOD.                                                                                 LIMIT MOISTURE PENETRATION ALONG NAIL SHANK.                                                                                                                 S32 ALL CANTILEVER MEMBERS TO BE PROPPED UNTIL FULLY FIXED AT SUPPORTS
                                                                                                                                                                                                                                                                                  INSTITUTE. FOR CONNECTIONS, WHERE NO STRUCTURAL DETAIL IS PROVIDED, 2/M20
                  Mz-CAT                              0.83                                                                                                                                           - MANUFACTURED TIMBER PRODUCTS, IF SPECIFIED, ARE TO BE MINIMUM H3           BOLTS IN 8.8/S CATEGORY SHALL BE USED AND ALL WELDS SHALL BE 6mm CONTINUOUS
                  Ms-SHIELDING                        1.0                                        C8   ALL FORMWORK SHALL CONFORM TO AS3610 (RESHORING NOT PERMITTED).                                  TREATED AND PROTECTED IN ACCORDANCE WITH MANUFACTURER'S                    FILLET WELDS USING E48XX ELECTRODES OR EQUIVALENT AND ALL CLEAT PLATES AND
                  Mt-TOPOGRAPHIC                      1.0                                                                                                                                              SPECIFICATION ( EG HYNE TECH DATA SHEETS 6 AND 8). USE A HIGH QUALITY
                  Vz (ULT)                            46m/s (N); 50m/s (S, E, W)                 C9   REINFORCEMENT SYMBOLS
                                                                                                                                                                                                                                                                                  STIFFENERS SHALL BE 10mm THICK.                                                  SCREW PILES
                                                                                                                                                                                                       EXTERIOR PAINT FINISH TO EXPOSED SURFACES.
                                                                                                                                                                                      T3    ALL FASTENERS TO BE HOT DIPPED GALVANISED. EXTERNAL ANCHORS WHERE SUBJECT          S7 BOLTING CATEGORIES ARE IDENTIFIED ON THE STRUCTURAL DRAWINGS IN THE
                  EARTHQUAKE LOADS                                                                      REINFORCEMENT TYPES ARE DESIGNATED AS FOLLOWS:-                                     TO SALT AIR TO BE STAINLESS STEEL.                                                    FOLLOWING MANNER:                                                                SP1.   ALL PILES TO BE DESIGNED, MANUFACTURED AND INSTALLED BY
                  EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH                             BAR REINFORCEMENT                                                                            - NAILS TO BE 2.8 mm DIA. x 30 mm LONG.
                  AS 1170 PART 4 BASED ON THE FOLLOWING:                                                                                                                                                                                                                                                                                                                  THE PILING CONTRACTOR. ALL PILES TO BE CERTIFIED (SUPPLY
                                                                                                        'R' DENOTES ROUND STEEL BAR.                                                                 - SCREWS TO BE No.14 TYPE 17 WITH 50mm EMBEDMENT (U.N.O.)                     BOLTING CATEGORY BOLT GRADE BOLT TO         METHOD OF STD.                             FORMS 15 & 16) FOR DESIGN AND INSTALLATION BY A PRACTICING
                                                                                                        'N' DENOTES DEFORMED STEEL BAR.                                                              - ALL JOIST HANGERS, FRAMING ANCHORS AND TRIPLE GRIPS TO BE                                    AUST. STD INSTALLATION TO AS 4100                                     PROFESSIONAL ENGINEER.
                  ANNUAL PROBABILITY OF EXCEEDANCE              1:500                                   'W' DENOTES HARD DRAWN DEFORMED WIRE.                                                          MANUFACTURED BY PRYDA OR EQUIVALENT. FULLY NAILED - 4 NAILS MINIMUM.           4.6/S    4.6     AS 1111     SNUG TIGHTENED                                                 NOTE THAT INSTALLATION INCLUDES TRIMMING AND
                  PROBABILITY FACTOR, KP                        1.0                                     MESH REINFORCEMENT                                                                             INSTALL PER MANUFACTURERS SPECIFICATION.                                       8.8/S    8.8     AS 1252     SNUG TIGHTENED                                                 REMOVING OF EXCESS
                  HAZARD FACTOR, Z                              0.08                                    'SL' DENOTES SQUARE WELDED MESH.                                              T4    WASHERS TO TIMBER TO BE:                                                                  8.8/TF    8.8    AS 1252     FULLY TENSIONED                                                LENGTHS AND INSTALLING DOWEL HEAD PINS).
                  SUB-SOIL CLASS                                Ce                                      'RL' DENOTES RECTANGULAR WELDED MESH.                                                        M12 BOLTS 55 SQ. X 3 THK                                                                               FRICTION - TYPE JOINT
                  EARTHQUAKE DESIGN CATEGORY                     I                                      TRENCH MESH REINFORCEMENT                                                                    M16 BOLTS 65 SQ. X 5 THK                                                         8.8/TB    8.8     AS 1252    FULLY TENSIONED                                 SP2.   EFFECTIVE LENGTH TO BE DETERMINED BY THE DESIGNER
                                                                                                        'TM' DENOTES TRENCH MESH WITH W8 LIGS AT 600.                                 T5    ALL BOLTS ARE TO BE HEX HEAD BOLTS WITH CORRECT SIZED WASHERS. DO NOT USE                                       BEARING - TYPE JOINT                                          (MINIMUM 3m).
       G10. CONSTRUCTION USING THE STRUCTURAL DRAWINGS SHALL NOT COMMENCE UNTIL A                       REINFORCEMENT GRADES ARE DESIGNATED AS FOLLOWS:-                                    CUPHEAD BOLTS.
            CONSTRUCTION CERTIFICATE IS ISSUED BY THE PRINCIPAL CERTIFYING AUTHORITY &                  BAR REINFORCEMENT GRADE 500 - NORMAL DUCTILITY                                T6    BOLTS TO BE INSTALLED INTO PRE-DRILLED HOLES OF DIAMETER NOT EXCEEDING 10% OF          COPIES OF TEST CERTIFICATES CONFIRMING CONFORMANCE TO THE RELEVANT              SP3.   PILES TO COMPLY WITH THE FOLLOWING:
            ONLY IF THE STRUCTURAL DRAWING IS DESIGNATED "ISSUE FOR CONSTRUCTION"                       MESH REINFORCEMENT GRADE 500 - LOW DUCTILITY                                        BOLT DIAMETER.                                                                         STANDARD AND BOLT GRADE ISSUED BY THE SUPPLIER OF THE BOLTS SHALL BE                           50mm MAXIMUM DESIGN ECCENTRICITY
                                                                                                        TRENCH MESH REIN. GRADE 500 - LOW DUCTILITY                                   T7    COACH SCREWS SHALL BE SCREWED INTO PRE-DRILLED HOLES AND NOT HAMMERED.                 SUPPLIED TO RECOR CONSULTING.                                                                  50mm MAXIMUM INSTALLATION TOLERANCES
       G11. THE CONTRACTOR SHALL GIVE AT LEAST 24 HOURS NOTICE OF ANY INSPECTIONS OF                                                                                                  T8    PRE-DRILLED HOLES FOR THE SHANK SHALL NOT BE LESS THAN THE SHANK DIAMETER
            STRUCTURAL WORK THAT ARE REQUIRED TO BE MADE BY ECOR CONSULTING.                                                                                                                AND SHALL NOT EXCEED IT BY MORE THAN 1mm.                                          S8 BOLTING CATEGORIES 8.8/TF & 8.8/TB REQUIRE TENSIONING IN ACCORDANCE WITH AS
                                                                                                 C10 SIZES OF CONCRETE ELEMENTS DO NOT INCLUDE THICKNESS OF APPLIED FINISHES.                                                                                                     4100. TENSIONING SHALL BE CARRIED OUT IN ACCORDANCE WITH CLAUSE 15.2.5 OF        SP4.   ALLOW FOR A MINIMUM CORROSION RATE OF 0.02mm / YEAR.
                                                                                                                                                                                      T9    PRE-DRILLED HOLES FOR THE THREADED PORTION SHALL NOT EXCEED THE ROOT
                                                                                                                                                                                            DIAMETER OF THE SCREW.                                                                AS 4100 BY EITHER THE PART-TURN METHOD OR THE DIRECT-TENSION INDICATOR
                                                                                                 C11 BEAMS SIZES ARE SHOWN DEPTH FIRST AND INCLUDE SLAB THICKNESS                                                                                                                 METHOD. THE TORQUE-CONTROL METHOD SHALL NOT BE USED. FOR BOLTING                 SP5.   PILES TO HAVE A DESIGN LIFE OF 50 YEARS.
                                                                                                                                                                                      T10   FIXINGS SHALL BE INSTALLED TO THE DIMENSIONS SHOWN IN DETAILS. IN ANY CASE, ALL
       G.12. WATERPROOFING                                                                                                                                                                  FIXINGS SHALL BE INSTALLED WITHIN MINIMUM EDGE DISTANCES, END DISTANCES AND           CATEGORY 8.8/TF, THE CONTACT SURFACES SHALL BE FREE FROM PAINT, LACQUER,
             ALL EXTERNAL SLABS, ROOF SLABS & RETAINING WALLS SHALL HAVE A WATERPROOF            C12 UNLESS NOTED OTHERWISE ALL FORMED EDGES AND CORNERS OF CONCRETE                                                                                                              GALVANISING OR OTHER APPLIED FINISH, UNLESS NOTED OTHERWISE ON THE               SP6.   ALL PILES TO BE CONCRETE CORE FILLED WITH A MINIMUM 32MPa
                                                                                                                                                                                            SPACINGS AS PER AS1720.1 (TYPICALLY 4d, 5d AND 5d RESPECTIVELY) U.N.O.                                                                                                        CONCRETE WITH 6mm AGGREGATE. PILES TO BE CUT OFF 150mm
             MEMBRANE APPLIED TO ARCHITECT'S & CONTRACTOR'S DETAILS. THE MEMBRANE WILL               MEMBERS SHALL HAVE 20mm CHAMFERS.                                                                                                                                            STRUCTURAL DRAWINGS. CONTRACTOR TO PROVIDE CERTIFICATION FOR BOLTING
                                                                                                                                                                                      T11   TIMBER BEARERS AND JOISTS WITH D / B >= 4                                                                                                                                     ABOVE UNDERSIDE OF PILE CAP AND PILES TO BE CLOSED ENDED
             BE THE PRIMARY METHOD OF WATERPROOFING. THE MEMBRANE SHALL BE DETAILED TO                                                                                                               - PROVIDE BLOCKING OVER SUPPORTS AT 1800 MAX. CRS IN                         CATEGORY ACHIEVED AS DETAILED ON STRUCTURAL DRAWINGS.
             ACCOMMODATE MOVEMENT AT EXPANSION JOINTS.                                           C13 PLACE CONCRETE IN LAYERS SUCH THAT EACH SUCCEEDING LAYER IS BLENDED INTO                                                                                                                                                                                             TYP.
                                                                                                                                                                                                       ACCORDANCE WITH AS1684.
                                                                                                     THE PRECEDING ONE BY THE COMPACTION PROCESS. SLABS AND BEAMS SHALL BE                                                                                                     S9 UNLESS NOTED OTHERWISE, HOLES SHALL BE 2mm LARGER THAN THE NOMINAL BOLT
                                                                                                                                                                                                     - FOR JOISTS WITH SPAN > 3000 AND BOTTOM OF JOIST                                                                                                             SP7.   ALL PILES TO HAVE A MINIMUM SHEAR CAPACITY OF 10kN.
               NOTES ON ALL DRAWINGS SHALL OVER-RIDE ALL GENERAL CONSTRUCTION NOTES AS               POURED TOGETHER. THE FINISHED CONCRETE SHALL BE A DENSE HOMOGENEOUS MASS                                                                                                     DIAMETER. WHERE SLOTTED OR OVERSIZE HOLES ARE PERMITTED ON THE
                                                                                                                                                                                                       UNRESTRAINED BY CEILING DIAPHRAGM;
               OUTLINED ON THIS PAGE.                                                                COMPLETELY FILLING THE FORMWORK AND THOROUGHLY EMBEDDING THE                                                                                                                 STRUCTURAL DRAWINGS, THEY SHALL COMPLY WITH AS 4100. HAND FLAME CUTTING
                                                                                                                                                                                                              - PROVIDE 1 ROW OF BLOCKING BETWEEN EACH JOIST                                                                                                       SP8.   PROVIDE "AS BUILT" DRAWINGS WITH SURVEYED FINAL LOCATIONS.
                                                                                                     REINFORCEMENT. FINISH TYPE SHALL BE AS SPECIFIED IN THE ARCHITECTURAL                                                                                                        OF BOLT HOLES IS NOT PERMITTED. ALL BOLT HOLES SHALL BE DRILLED. BOLTS TO BE
                                                                                                                                                                                                                AT MIDSPAN FOR SPANS < 4200.
                                                                                                     DRAWINGS.                                                                                                                                                                    INSTALLED WITH A HARDENED WASHER UNDER THE TURNED PART OVER THE HOLE.
                                                                                                                                                                                                              - PROVIDE 2 ROWS OF BLOCKING BETWEEN EACH JOIST
      FOUNDATION NOTES                                                                           C14 COMPACTION:
                                                                                                                                                                                                                AT MIDSPAN FOR SPANS > 4200.
                                                                                                                                                                                                                                                                               S10 UNLESS NOTED OTHERWISE, ALL BOLTS AND WASHERS SHALL BE GALVANISED.
       F1      THESE DRAWINGS ARE TO BE READ IN CONJUNCTION WITH THE GEOTECHNICAL REPORT             USE IMMERSION AND SCREED VIBRATORS ACCOMPANIED BY HAND METHODS AS
               22380-001-Rev0 BY TECTONIC GEOTECHNICAL. REFER TO THIS REPORT FOR GROUND              APPROPRIATE TO REMOVE AIR BUBBLES AND COMPACT THE MIX. USE FORM VIBRATORS                                                                                                 S11 UNLESS NOTED OTHERWISE, A CUT SURFACE SHALL HAVE A MAXIMUM ROUGHNESS
               CONDITIONS AND FOUNDATION RECOMMENDATIONS.                                            WHERE USE OF IMMERSION VIBRATORS IS IMPRACTICABLE. ENSURE CONCRETE IS FULLY                                                                                                   NOT EXCEEDING 25 MICROMETERS. ALL CUTTING SHALL BE CARRIED OUT IN
                                                                                                     COMPACTED AND ENTRAPPED AIR REMOVED, BUT AVOID OVER VIBRATION THAT MAY                                                                                                        ACCORDANCE WITH THE RECOMMENDATIONS OF AWRA TECHNICAL NOTE 5.
                                                                                                     CAUSE SEGREGATION. DO NOT USE VIBRATORS TO MOVE CONCRETE ALONG THE FORMS
       F2      DESIGN BEARING PRESSURES                                                                                                                                                                                                                                        S12 FABRICATION TOLERANCES SHALL COMPLY WITH AS 4100, SECTION 14 UNLESS NOTED
               ALL FOOTINGS MUST BE FOUNDED A MINIMUM OF 500mm INTO MEDIUM DENSE SAND WITH       C15 EXACT SIZE AND LOCATION OF PENETRATIONS ARE TO BE OBTAINED FROM WORKSHOP                                                                                                      OTHERWISE ON THE STRUCTURAL DRAWINGS.
               AN ALLOWABLE BEARING PRESSURE OF 150kPa. REFER TO GEOTECHNICAL ENGINEER FOR           DRAWINGS PRIOR TO SCHEDULING OF REINFORCEMENT AND ARE NOT TO EXCEED
               ON SITE CERTIFICATION THE ABOVE PARAMETERS ARE ACHIEVED.                              DIMENSIONS WHERE SHOWN ON STRUCTURAL DRAWINGS.                                                                                                                            S13 ALL BEAMS AND RAFTERS SHALL BE FABRICATED AND ERECTED WITH NATURAL
                                                                                                                                                                                                                                                                                   CAMBER UP. ANY ADDITIONAL CAMBER SHALL BE AS NOTED ON THE STRUCTURAL
       F3      CERTIFICATION AND CLEANING                                                        C16 NO CHASES, HOLES GREATER THAN 150mm DIAMETER, OR EMBEDMENT OF PIPES                                                                                                           DRAWINGS. PROVIDE STRUCTURAL MEMBERS IN SINGLE LENGTHS UNLESS SPLICES
               ALL FOUNDATION MATERIAL AND BEARING CAPACITIES SHALL BE APPROVED AND                  GREATER THAN 40mm DIAMETER OTHER THAN THOSE SHOWN ON THE STRUCTURAL                                                                                                           ARE SHOWN ON THE STRUCTURAL DRAWINGS. ANY WELDED SPLICES TO MAKE UP
               CERTIFIED BY A PRACTISING QUALIFIED GEOTECHNICAL ENGINEER. THE BASES OF ALL           DRAWINGS SHALL BE MADE IN THE CONCRETE SLABS. FOR ALL OTHER CONCRETE                                                                                                          MEMBER LENGTHS SHALL BE FULL PENETRATION BUTT WELDS.
               FOOTINGS SHALL BE CLEANED AND FREE OF WATER IMMEDIATELY BEFORE INSPECTION             MEMBERS NO PENETRATION, MADE IN THE CONCRETE SLABS. FOR ALL OTHER CONCRETE
               AND PLACEMENT OF CONCRETE.                                                            MADE WITHOUT PRIOR APPROVAL BY THE STRUCTURAL ENGINEER..                                                                                                                  S14 WELDING PERSONNEL SHALL BE QUALIFIED IN ACCORDANCE WITH CLAUSE 4.12 AS
                                                                                                                                                                                                                                                                                   1554.1.
       F4      FOOTINGS SHALL BE CONSTRUCTED & BACKFILLED AS SOON AS POSSIBLE FOLLOWING          C17 CONDUITS CAST INTO CONCRETE MEMBERS SHALL BE SPACED AT MAXIMUM DISTANCE
               EXCAVATION. FOUNDATION MATERIAL SHALL NOT BE PERMITTED TO SOFTEN OR DRY OUT.          POSSIBLE AND UNDER NO CIRCUMSTANCES CLOSER THAN A CLEAR SPACING OF TWICE                                                                                                      NON-DESTRUCTIVE WELD EXAMINATION SHALL BE AS FOLLOWS:
               IF CONCRETE IS NOT PLACED IMMEDIATELY AFTER EXCAVATION OF FOOTING, PROVIDE A          THE LARGER CONDUIT DIAMETER FROM PARALLEL REINFORCEMENT OR ANY OTHER
               50mm BLINDING LAYER OF WEAK (15MPa) CONCRETE TO THE BASE OF THE EXCAVATION            CONDUIT.                                                                                                                                                                      TYPE OF WELD    EXAMINATION METHOD EXTENT (% OF TOTAL
               FOUNDATION                                                                                                                                                                                                                                                          & CATEGORY                  LENGTH OF WELD TYPE)
                                                                                                 C18 REINFORCEMENT IS SHOWN DIAGRAMMATICALLY AND NOT NECESSARILY IN TRUE
       F5      SIDES OF FOOTINGS SHALL BE FORMED AS NECESSARY WHEN EXCAVATED FACE IS NOT             PROJECTION.                                                                                                                                                                   FILLET WELD, GP/SP VISUAL INSPECTION         100
               STABLE.                                                                                                                                                                                                                                                             BUTT WELD, GP     VISUAL INSPECTION        100
                                                                                                 C19 FOR OVERSIZE PENETRATIONS REFER TO ENGINEER FOR APPROVAL                                                                                                                      BUTT WELD, SP     VISUAL INSPECTION        100
       F6      ALL WALLS AND COLUMNS SHALL BE CONCENTRIC WITH SUPPORTING FOOTINGS UNLESS             I.E PENETRATIONS THAT DON'T FIT BETWEEN REINFORCEMENT SPACING.                                                                                                                BUTT WELD, SP     RADIOGRAPHIC OR        10 SHOP WELD
               OTHERWISE NOTED ON THE DRAWINGS.                                                                                                                                                                                                                                                 ULTRASONIC INSPECTION   25 FIELD WELD
                                                                                                 C20 DO NOT CUT REINFORCEMENT ON SITE TO CLEAR PENETRATIONS. DISPLACE
       F7      UNLESS APPROVED BY THE STRUCTURAL ENGINEER, EXCAVATIONS SHALL NOT EXTEND              REINFORCEMENT SLIGHTLY AS NECESSARY TO CLEAR BLOCK OUTS AND TRIM WITH 2-N12                                                                                               S15 RADIOGRAPHIC EXAMINATION: TO AS 1554, PART 1, CLAUSE 6.3.
               BELOW A LINE DIPPING AT 45 DEGREES AND AWAY FROM THE NEAREST UNDERSIDE                BARS EACH SIDE FOR ALL PENETRATIONS <300mm                                                                                                                                    ULTRASONIC EXAMINATION: TO AS 1554, PART 1, CLAUSE 6.4.
               CORNER OF ANY FOOTINGS, RETAINING WALLS OR EXISTING BUILDINGS                                                                                                                                                                                                       TESTING SHALL BE PERFORMED BY AN INDEPENDENT TESTING AUTHORITY AND THE
                                                                                                 C21 SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN THE POSITIONS SHOWN, UNLESS                                                                                                    RELEVANT TEST REPORT SHALL BE SUBMITTED TO RECOR CONSULTING.
       F8      WHERE FOUNDATION MATERIAL DIFFERS FROM THAT DESCRIBED IN THE SITE                     APPROVED BY THE STRUCTURAL ENGINEER.
               INVESTIGATION REPORT OR LOCALISED SOFT SPOTS ARE FOUND, THE ENGINEER SHALL                                                                                                                                                                                      S16 THE SUBCONTRACTOR SHALL GIVE NOTICE OF AT LEAST 48 HOURS SO THAT
               BE NOTIFIED AND IF NECESSARY THE MATERIAL SHALL BE EXCAVATED AND BACKFILLED       C22 WELDING OF REINFORCEMENT IS NOT PERMITTED.                                                                                                                                    INSPECTION MAY BE MADE BY EITHER RECOR CONSULTING (IF REQUIRED) OR THE
               WITH WEAK MIX CONCRETE.                                                                                                                                                                                                                                             SUBCONTRACTORS NOMINATED INSPECTION ORGANISATION AT THE FOLLOWING
                                                                                                 C23 REINFORCEMENT SHALL BE BENT COLD IN ACCORDANCE WITH AS3600 EXCEPT WHERE                                                                                                       STAGES:
       F9      THE SITE IS TO BE STRIPPED AND ALL VEGETATION REMOVED FROM THE BUILDING AREA.         APPROVED BY THE STRUCTURAL ENGINEER. NO RE-BENDING SHALL BE PERMITTED.                                                                                                          : COMMENCEMENT OF WELDING PROCEDURE AND WELDER QUALIFICATIONS TESTS
               GRUB HOLES TO BE BACKFILLED IN LAYERS AS INDICATED ON NOTE BELOW.                                                                                                                                                                                                     : COMMENCEMENT OF WELDING
                                                                                                 C24 ALL REINFORCEMENT SHALL BE SECURELY SUPPORTED IN ITS CORRECT POSITION                                                                                                           : PRIOR TO THE PLACEMENT OF THE ROOT RUNS OF COMPLETE PENETRATION BUTT
       F10     FILLED BUILDING PLATFORMS SHALL BE BUILT UP IN LAYERS OF 150mm MAXIMUM DEPTH          DURING CONCRETING BY APPROVED PLASTIC TIPPED BAR CHAIRS, SPACERS OR                                                                                                           WELDS
               AND UNIFORMLY COMPACTED TO A MINIMUM OF 98% OF THE STANDARD MAXIMUM DRY               SUPPORT BARS. MAXIMUM CENTRES OF SUPPORTING CHAIRS SHALL BE 800mm FOR                                                                                                           : COMPLETION OF FABRICATION PRIOR TO SURFACE PREPARATION
               DENSITY AS RECOMMENDED IN A.S.3798 5.1. RANGE OF -4.0% TO +0.5% OF THE STANDARD       FABRIC, 600mm FOR BARS UP TO 12mm DIAMETER, 900mm FOR BARS 16mm AND GREATER.                                                                                                    : COMMENCEMENT OF SURFACE PREPARATION PRIOR TO PROTECTIVE COATING
               OPTIMUM MOISTURE CONTENT.                                                                                                                                                                                                                                             : COMPLETION OF PROTECTIVE COATING PRIOR TO DELIVERY TO SITE
                                                                                                 C25 MINIMUM LAP FOR ALL FABRICS SHALL BE ONE MESH + 30mm. U.N.O.                                                                                                                    : STEELWORK ON SITE PRIOR TO ERECTION
       F11     SITE PREPARATION : ALL EARTHWORKS TO BE CARRIED OUT IN ACCORDANCE WITH AS                                                                                                                                                                                             : COMPLETION OF ERECTION PRIOR TO ENCASING OR FIXING CLADDING
               3798 GUIDELINES ON EARTHWORKS FOR COMMERCIAL AND RESIDENTIAL DEVELOPMENTS.        C26 WHERE NO STEEL IS SHOWN ON THE DRAWING AT RIGHT ANGLES TO MAIN
                                                                                                     REINFORCEMENT PLACE N12-300 ON THE SIDE OF THE MAIN REINFORCEMENT REMOTE                                                                                                  S17 SURFACE TREATMENT AND PAINTING OF STEELWORK TO BE AS PER ARCHITECTURAL
       F12     SLAB ON GROUND: THE SUBGRADE UNDER SLABS SHALL BE PREPARED BY STRIPPING ALL           FROM THE OUTSIDE OF THE CONCRETE. ALL OPENINGS AND RE-ENTRANT ANGLES IN THE                                                                                                   SPECIFICATION. SURFACE TREATMENT SHALL BE CARRIED OUT IN ACCORDANCE WITH
               VEGETATION AND PROOF ROLLING THE SURFACE. ANY SOFT AREAS SHALL BE REMOVED             CONCRETE SHALL HAVE 2/N12 TOP AND BOTTOM ALONG THE ENCLOSING EDGE AND                                                                                                         AS 1627. (SEE ALSO ITEM S8) PROVIDE SEAL PLATES TO ALL HOLLOW SECTIONS, WITH
               AND REPLACED WITH APPROVED COMPACTED MATERIAL. MATERIAL UNDER SLAB SHALL              PROJECTING 350 PAST CORNERS.                                                                                                                                                  BREATHER HOLES IF MEMBERS ARE TO BE HOT DIPPED GALVANISED
               HAVE A MINIMUM SAFE BEARING CAPACITY OF 100kPa WITH A MAXIMUM LINEAR
               SHRINKAGE OF 8% AND A PLASTIC INDEX NOT EXCEEDING 16. ALL FILLING AND             C27 CONSTRUCTION BREAK, JOINT LOCATIONS AND DETAILS SHALL BE APPROVED BY THE                                                                                                  S18 ERECTION TOLERANCES SHALL COMPLY WITH AS 4100 SECTION 15 UNLESS NOTED
               BACKFILLING SHALL BE COMPACTED IN MAXIMUM 150mm THICK LAYERS BY MECHANICAL            STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION.                                                                                                                                    OTHERWISE ON THE STRUCTURAL DRAWINGS.
               COMPACTION TO 98% OF THE MAXIMUM DRY DENSITY (STANDARD) AS
               DETERMINED BY AS 1289 TEST E 1.1                                                  C28 THE FACE OF ALL CONCRETE AGAINST WHICH NEW CONCRETE IS TO BE CAST IS TO BE                                                                                                S19 ALL STEELWORK SHALL BE TEMPORARILY BRACED IN A SECURE MANNER IN ORDER
                                                                                                     THOROUGHLY MECHANICALLY SCABBLED, FULLY EXPOSING THE AGGREGATE MATRIX.                                                                                                        TO STABILISE THE STRUCTURE DURING ERECTION. DETAILS TO BE PROVIDED BY SUB
       F13     PLACE A 50mm THICK LAYER OF BEDDING SAND OVER SUBGRADE MATERIAL.                                                                                                                                                                                                    CONTRACTOR.

       F14     PLACE 0.2mm THICK POLYETHYLENE FILM VAPOUR BARRIER TO NCC UNDER SLAB WITH
               ALL JOINTS SEALED.



                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       INFORMATION
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           NOT FOR CONSTRUCTION
                                                                                                                                                                                                                                                                                                                                                                                                                                          Client                             Status                                Title
                                                                                                                                                                                                                                                                                                                                                                                                                                           MARK BAIN                          INFORMATION
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   NOTES SHEET - SHEET 1
                                                                                                                                                                                                                                                                                                                                                                                                                                          Drawn By         Designed By       Approved By
                                                                                                                                                                                                                                                                                                                                                                                                                                            JAL              JM               JO
                                                                                                                                                                                                                                                                                                                                                                                                                                          Project No.      Discipline        Scale

                                                                                                                                                                                                                                                                                                                                                                  [email protected]                                                  20220173         STRUCTURAL         1:1                  (at A1)

                                                                                                                                                                                                                                                                                                                                                                                                                                          Project Name
                                                                                                                                                                                                                                                                                                                                                                  37 MARY ST NOOSAVILLE, QLD                                                                                                                       Drawing No.                                      Revision
1     04.11.22 ISSUE FOR INFORMATION                                                                                                JAL       JO                                                                                                                                                                                                                                                                                           NOOSA VILLAS
                                                                                                                                                                                                                                                                                                                                                                  07 5211 1003                                                                                                                                      S001                                             1
Rev     Date      Description                                                                                                         By      Chk                                                                                                                                                                                                                                                                                          10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      FULL SIZE ON ORIGINAL    0           10    20   30   40   50   60   70   80        90    100 mm

Used in these records

About this file

File size
10.3 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Structural Plans 20220173 - 10 Natasha Structural Issue 190123.pdf · 10.3 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.