Response to Information Request 5-7 Rufous Street Peregian Beach - Attachment D MCU13/0092
Very large file (23.1 MB): the whole original can take several minutes to open, especially on a phone. Text is quick to read.
methodology) are explained in Section 7.1. In summary, component LAeq noise from refrigeration
plant on trucks loading / unloading at the commercial site during stipulated loading times, when
predicted at the nearest residences, should not exceed the existing LAeq noise levels at the
residential areas during that time. The existing noise levels applicable at the residential areas
near the commercial site are indicated in the logging results (please refer to Figure 5 to Figure 12
attached at the end of the report).
The quasi-continuous noise limits are presented in Table 5. Similar to the transient noise
emissions, an adjustment of 2dBA has been made for quasi-continuous noise emissions.
Table 5: Noise limits for quasi-continuous emissions
Noise Limits LAeq, adj (dBA)
7am to 6pm 6pm to 10pm 10pm to 7am
55 53 52
7.3 Limits of mechanical plant noise
In determining the appropriate noise emission limits for continuous mechanical plant noise,
reference has been made to the Environmental Protection (Noise) Policy 2008 and the
Environmental Protection Act 1994.
For continuous noise, the acoustic quality objectives for outdoors as presented in Table 3 would
apply at all noise sensitive receptors. In addition to these long-term goals, controlling background
creep must be achieved as described in Section 10 of the EPP (Noise). To the extent that it is
reasonable to do so, noise from an activity must not be:
a) For noise that is continuous and measured using the LA90, Tll parameter, more than nil
dBA greater than the existing acoustic environment measured by the LA90, T; or
b) For noise that varies over time measured by LAeq, adj, T more than 5dBA greater than
the existing acoustic environment measured by LA90, T.
For air-conditioning equipment, Section 440U of the Act states that an occupier of a premises (at
or for which there is air-conditioning equipment) must not use, or permit the use of, equipment
on any day:
a) Before 7am, if it makes a noise of more than 3dBA above the background level; or
b) From 7am to 10pm, if it makes a noise of more than 5dBA above the background
level; or
c) After 10pm, if it makes a noise of more than 3dBA above the background level.
11
This criterion is impossible to achieve, as any additional noise, no matter how small, will result in an increase of the
LA90, T noise level. Since it is impossible to fulfil the specified requirement, the statement has been re-interpreted to
mean that the component noise levels due to the continuous noise must be equal to or less than the existing
ambient LA90 noise level.
@ Renzo Tonin Ron Rumble Proposed Shopping Centre, Rufous Street, Peregian
Noise Impact Assessment
Q9554-01F02 (Rev 3) Peregian Shopping Centre.doc Multi Span Australia Group pty Ltd
5 August 2013 Page 14
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Response to Information Request 5-7 Rufous Street Peregian Beach - Attachment D MCU13/0092Related documentApplication case desk ↗
About this file
- File size
- 23.1 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.