Log in to see the plans as drawn Performance outcomes Acceptable outcomes
the adverse impacts of bushfire. people living or congregating on premises, including
reconfiguring a lot, is not located within a medium or high
bushfire hazard area.
AO1.2
Development maximises setbacks from hazardous vegetation
to achieve an acceptable risk.
Editor’s Note — PSP8 Natural Hazards provides guidance for
assessing bushfire hazard risk and preparing a bushfire
hazard management plan.
Impacts on Ecologically Important Areas
PO2
Bushfire mitigation measures do not adversely impact on: No acceptable outcome provided
(a) biodiversity values, connectivity and ecosystem
functioning; and
(b) the long term physical integrity of waterways, wetland and
areas of native vegetation.
Water Supply for Fire Fighting Purposes
PO3 AO3.1
Development provides an adequate water supply for fire Premises are connected to the reticulated water supply.
fighting purpose which is reliable, safely located and freely
accessible. Editor's note—For reconfiguring a lot, water supply needs
to provide for a minimum flow and pressure of 10 litres a
second at 200kPa at all times for fire fighting purposes.
OR
AO3.2
Where there is no available reticulated water supply, the
premises has:
(a) an accessible dam, swimming pool or water tank
available for fire fighting purposes with an onsite water
volume of not less than 5,000 litres; and
(b) a water supply outlet pipe 50 milimetres in diameter
fitted with a standard fire brigade fitting connected to the
water supply (other than where the water supply is in a
swimming pool or dam).
Editor’s Note—Water supply capacity for fire fighting purposes
is in addition to water supply capacity for other uses and
activities on the premises.
Essential Community Infrastructure
PO4 AO4.1
Essential community infrastructure is able to function effectively Development involving essential community infrastructure is
during and immediately after bushfire events. not located within a medium or high bushfire hazard area.
OR
**FINAL DRAFT Post Consultation 2019** Page 2 of 4