Cambooya Pty Ltd

To minimise the potential for any adverse interaction effects, footings should found at least below a plane
extending 1 m horizontally from the base of trenches/batter slopes/excavations/retaining walls, then rising up
at 1V:1H. This requirement is illustrated in the following diagram.




6.3    Retaining Wall Design
It is anticipated that the proposed structure walls will retain the excavated soils, therefore, these
structure/retaining walls are considered to be ‘rigid’. Rigid walls are defined as being unable to rotate or tilt,
and should be designed using ‘at-rest’ earth pressure coefficients (K0), as given in Table 1.
Passive pressure (Kp) should be ignored where there is potential for in-ground services trenches (or similar)
in front of the wall.

Table 1: Lateral Earth Pressure Coefficients.
                                                   Lateral Earth Pressure
                                                        Coefficients

                           Bulk       Friction
 Retained Material       Density       Angle
                         (kN/m3)     (degrees)         Kp            Ko



      Loose sand           17            27           2.66          0.55
Medium dense Sand          18            32           3.26          0.47
      Dense sand           19            37           4.02          0.4
  Very dense sand          21            42           5.05          0.33

If appropriate, an allowance of 10 kPa should be made for lateral stress induced by compaction plant
operating behind the walls. The effects of surcharge should be included by multiplying the vertical pressure
developed by the surcharge by the appropriate lateral earth pressure coefficient from Table 1.
Drainage material behind the wall should be installed for the full height of the wall, for a width of at least
0.3 m. The material must be free draining and granular and have a perforated or slotted drainage pipe at the
heel of the wall to rapidly remove the water into the stormwater system. Alternatively, the wall will need to be
designed for the full hydrostatic pressure.

6.4    Drainage & Erosion Control
Site drainage should be designed to readily remove surface water and to prevent ponding of water.
Stormwater should be piped to an engineer-designed dissipation system. Concentrated surface water flows
(e.g., roof runoff) should be avoided.




J001873-001-R-Rev0                                                                                      Page 7

Used in these records

About this file

File size
9.3 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Appendix E - Geotechnical Report.pdf · 9.3 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.