23 April 2020




Noosa Council
PO Box 141
Tewantin QLD 4565

Attn: Kerri Coyle
Via email: [email protected]


                Cc    John & Kathleen Hofmann
                      c/- JFP Urban Consultants Pty Ltd
                      T1. 209 Kon-Tiki Business Centre, 55 Plaza Parade
                      Maroochydore QLD 4558

                      Attention: Allison Drabsch
                      Via email: [email protected]

Dear Kerri,

Amended Affected Entity Response Notice – Change Application for a
Minor Change to reduce the number of residential lots under
Development Approval 152006.1999 – Development Permit for
Reconfiguring a Lot (1 into 52 residential lots, new road and park) at
191 Hollett Road, Noosaville (Lot 53 on SP163571)

Applicant Ref: M1775
Council Ref: 152006.1999.4
Our Ref: HBD 6923390

We refer to the abovementioned Change Application, notice of which has
previously been given to Energex Limited, pursuant to section 80 of the
Planning Act 2016. Energex issued an affected entity response on 20
December 2019 (Energex Ref. HBD 6829410) objecting to the change
application, but advising that this position may be revised, subject to the
Applicant providing further detailed assessment of several outstanding          Enquiries
issues. The Applicant provided amended application material to Energex on       Benjamin Freese
1 April 2020 in response to this notice.                                        Telephone
                                                                                (07) 3664 5097
Energex has assessed the amended application material and subsequent            Facsimile
changes to the development received on 1 April 2020 and reviewed its            (07) 3664 9829
                                                                                Email
position in relation to the Change Application. As an affected entity for the
                                                                                benjamin.freese@
Change Application, Energex advises that it has no objection to the changes     energyq.com.au
proposed, subject to the requirements of this response notice.
                                                                                Corporate Office
The application material identified on the following page has been assessed     26 Reddacliff Street,
by Energex and forms the basis of our advice. The development is to be          Newstead QLD 4006
carried out in accordance with these plans and reports. Any changes to these    GPO Box 1461
                                                                                Brisbane Qld 4001
plans and reports may require an amended response notice.                       Telephone (07) 3664 4000
                                                                                Facsimile (07) 3025 8301
                                                                                www.energex.com.au

                                                                                Energex Limited
                                                                                ABN 40 078 849 055


Reference: HBD 6923390
Log in to download the original file

EGX_PROD_n6923390_191_Hollett_Road,_Noosaville_L53_SP163571.pdf · 6.4 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 31 pages

Page 2

                                                   2




                              Application Material Assessed
Title                                          Plan Number                Rev      Date
Reconfiguration Plan                           M1775-13F                  F        26 March 2020
Sheet 1 of 6
Plan of Development                            M1175-13                   F        26 March 2020
Sheet 2 of 6
Powerline Ground Clearance                     M1775-20                   A        29 January 2020
Electromagnetic Field Assessment,              -                          V1.0     27 March 2020
prepared by J&P Richardson Industries
and certified by Steven Flower RPEQ

The Applicant is also advised the following in relation to the development:

1. The conditions of any easements in favour of Energex must be maintained at all
   times.

2. Any future development proposed on the easement, including works associated
   with the new road, pedestrian/cyclist connections and/or other services connections
   must have prior approval from Energex.
   Prior to works commencing, the Applicant/Developer is to submit RPEQ certified
   drawings to Energex, having regard to any existing electrical assets in the vicinity of
   the proposed works.
    Note: where relevant, this may be satisfied by referring to Energex any future
    development application/s for Operational Work, in accordance with the
    requirements of the Planning Regulation 2017.

3. Lighting structures are not permitted in the easement without prior written consent
   of Energex. Lighting designs for proposed developments (e.g. road, carparks etc)
   on the easement are likely to require reduced height structures. Please submit
   detailed design to Energex for approval. These drawings must clearly show the
   following:
       Proposed height of the lighting structures and the ground level at the structure
        base;
       Relative (to lighting structures) ground levels at Energex structures (towers,
        pole etc) either side of the lighting structures; and
       The location of the Energex structures in relation to the proposed lighting.

4. No planting is permitted in the Easement without prior approval from Energex. If
   planting is proposed, the applicant is required to provide a Detailed Landscape
   Plan to Energex for approval which:
       Keeps the planting of trees to the outer most edge of the easement and not
        directly under any overhead conductors;
       Plots the location of the overhead conductors (accounting for a cross-arm if
        applicable and plotting the powerline on the outmost edge of each side of the
        cross-arm);


Reference: HBD 6923390

                                  Have you seen our fact sheets?
    See the ‘considerations when developing around electricity infrastructure’ section of our website
                                www.energex.com.au/referralagency

Page 3

                                                       3




          Uses       species      included      on       Energex’s     Safetrees     list
           (https://www.energex.com.au/about-us/our-commitment/to-the-
           environment/vegetation/safetree-program); and
          Ensures a horizontal clearance is achieved between the tree and the outer most
           conductor equal to the mature height of the tree.

5. Access to the easement and access along the easement must be available to
   Energex personnel, including vegetation crews and regular routine line inspection
   crews, and heavy equipment, such as Heavy Trucks, Machinery and Cranes for
   construction, maintenance and emergency services, at all times.

6. The following clearance must be maintained from the top of any machinery moving
   in the vicinity of energised conductors at all times:
          132kV and 110kV conductors – 4.5m minimum clearance.
    All operators of machinery are to be made aware of the presence of high voltage
    conductors. Should it be necessary to transport equipment or extend any
    equipment, such that these clearances cannot be confidently maintained, a Safety
    Advice request must be submitted to Energex via the following link:

    https://www.energex.com.au/about-us/contact-us/forms/general-forms/safety-
    advice-form

7. Any future works on the easement or in the vicinity of Energex assets are to be
   carried out in accordance with Energex Standard Guidelines OH-03/12. A copy of
   these guidelines is attached for reference.

Should you require further information regarding this matter, please contact the
undersigned on (07) 3664 5097 or [email protected] faithfully,



Benjamin Freese
Town Planner

Encl.      Attachment 1 – Copy of Energex Standard Guidelines OH-03/12
           Attachment 2 – Copies of plans and reports assessed by Energex




Reference: HBD 6923390

                                      Have you seen our fact sheets?
        See the ‘considerations when developing around electricity infrastructure’ section of our website
                                    www.energex.com.au/referralagency

Page 4

                               Standard Guidelines OH-03/12
When considering Works, either on Energex easements or in the vicinity of Energex assets,
please be aware of the following general conditions:

   Satisfactory clearance from your proposed structure to the existing (and/or future) electricity
    wires must be maintained in accordance with the Electrical Safety Regulations 2013.

   No civil works are to occur within 5 metres of any part of an Energex Structure (e.g.- tower
    base, pole or stay) without Energex approval.

   If the minimum 5m horizontal separation to the Energex structure cannot be achieved, the
    Developer must consult Energex with regards to allowable construction methods. This may
    include full depth shoring of the excavation sides for a minimum of 5 metres either side of
    the structure.

   Any excavations deeper than 5m must have a minimum horizontal separation from the
    excavation to any tower, base or pole at least equal to the excavation depth. The
    excavation is not to be left open overnight and backfill is to be compacted in 150mm layers
    in the immediate vicinity of the structure.

   10 metres clear access must be provided around all towers and pole structures after the
    completion of any works on the easement.

   Natural ground level on the easement should not be disturbed without Energex approval.

   Final ground levels should slope gently to the edge of the easement, surrounding area or
    kerb such that pooling of water on the easement is avoided and conductor ground
    clearances are not decreased.

   Stockpiling of spoil on the easement is prohibited.

   Proposed underground services such as stormwater, sewerage, water and the like are to be
    kept to the outer edge of the easement. Services crossing the easement should be as near
    as practicable to right angles to the overhead conductor direction and not within 10 metres
    of any tower, pole or stay. Pipelines and crossings are to be clearly marked. Please
    submit the relevant design drawings to the Principal Mains Design Engineer for review.

    The identification, assessment and mitigation of any possible hazards in the service due to
    electromagnetically induced voltages, is the responsibility of the Developer.

   Any cut in the vicinity of a structure or between a structure and the road kerb will need to be
    stabilised by a retaining wall. The retaining wall design and location is to be submitted to
    Energex for approval.

   Any costs incurred by Energex as a result of the works on the easement are to be met by
    the property Developer / owner.

   Access to the easement and access along the easement must be available to Energex
    personnel, including vegetation crews and regular routine line inspection crews, and heavy
    equipment, such as Heavy Trucks, Machinery and Cranes for construction, maintenance
    and emergency services, at all times.

   Existing access tracks must be re-instated, repaired or maintained if they are damaged
    during construction or other activities.

Reference: HBD 6923390

                                   Have you seen our fact sheets?
     See the ‘considerations when developing around electricity infrastructure’ section of our website
                                 www.energex.com.au/referralagency

Page 5

                                                    2




   Energex will require the Developer / owner to supply and install gates where fencing
    prohibits access to and along the easement area. To enable travel along the easement at
    anytime the gates must be series locked with an Energex padlock. Both the padlock and a
    design drawing of an acceptable gate will be provided by Energex.

   Lighting structures are not permitted in the easement without prior written consent of
    Energex. Lighting designs for proposed developments (e.g. road, carparks etc) on the
    easement are likely to require reduced height structures. Please submit detailed design to
    Energex for approval. These drawings must clearly show the following:

    o   Proposed height of the lighting structures and the ground level at the structure base;
    o   Relative (to lighting structures) ground levels at Energex structures (towers, pole etc)
        either side of the lighting structures; and
    o   The location of the Energex structures in relation to the proposed lighting.

   Pools and structures (including lighting structures) or metal fences are not permitted to be
    installed on or near Energex easement without prior approval or notification.

   Rubbish, materials and / or tall equipment such as cranes and excavators are not permitted
    to be stored or used on the easement.

   Excavations or mounding of material under or close to conductors or Energex structures is
    not permitted.

   Energex must be notified of construction on or near the easement, conductors or structures
    prior to commencement of construction.

   All construction work must be clear of the easement unless construction risk hazard is
    identified. High voltage clearances must be maintained prior to construction commencing.

   Warning signs may be required during and after construction.

   No planting is permitted in the Easement without prior approval from Energex. If planting is
    proposed, the applicant is required to provide a Detailed Landscape Plan to Energex for
    approval which:

    o   Keeps the planting of trees to the outer most edge of the easement and not directly
        under any overhead conductors;
    o   Plots the location of the overhead conductors (accounting for a cross-arm if applicable
        and plotting the powerline on the outmost edge of each side of the cross-arm);
    o   Uses species included on Energex’s Safetrees list (https://www.energex.com.au/about-
        us/our-commitment/to-the-environment/vegetation/safetree-program); and
    o   Ensures a horizontal clearance is achieved between the tree and the outer most
        conductor equal to the mature height of the tree.

   At all times the following clearance must be maintained from the top of any machinery
    moving in the vicinity of energised conductors:

    o   132kV and 110kV conductors – 4.5m minimum clearance;
    o   33kV and 11kV conductors – 3m minimum clearance

    Should it be necessary to transport equipment or extend any equipment, such that these
    clearances cannot be confidently maintained, you are required to contact our office to
    ascertain whether a Safety Officer is required on–site. All operators of machinery are to be
    made aware of the presence of high voltage conductors.

Reference: HBD 6923390

                                   Have you seen our fact sheets?
     See the ‘considerations when developing around electricity infrastructure’ section of our website
                                 www.energex.com.au/referralagency

Page 6

                                                   3




   All easement conditions must be maintained

   All previous conditions must be adhered to and Energex may, at its discretion, audit the
    finished development to check that it conforms to the conditions of the development.

   Detailed civil design drawings showing any proposed cut and fill levels on the easement and
    the location of the Energex assets in relation to the proposed development must be
    approved by Energex before any works can commence on site.




Reference: HBD 6923390

                                  Have you seen our fact sheets?
    See the ‘considerations when developing around electricity infrastructure’ section of our website
                                www.energex.com.au/referralagency

Page 7

PROPERTY DESCRIPTION                                                                                                                                                                                                                                                                                                                                           STATISTICS            STAGE 1 STAGE 2 STAGE 3 TOTAL
LOT 53 ON SP163571                                                                                                                                                                                                                                                                                                                                             NO. OF LOTS
PARISH OF TEWANTIN/WEYBA                                                                                                                                                                                                                                                                                                                                         LOW DENSITY            17         22       --     39
COUNTY OF MARCH                                                                                                                                                                                                                                                                                                                                                  RURAL PURSUIT           --         --      1       1
TOTAL AREA 110.0 ha                                                                                                                                                                                                                                                                                                                                              TOTAL                  17         22       1      40
NOTES                                                                                                                                                                                                                                                                                                                                                          LENGTH OF NEW
                                                                                                                                                                                                                                                                                                                                                                 20m ROAD              470m      840m       --   1310m
(1) This plan was prepared for the purpose and exclusive use of                                                                                                                                                                                                                                                                                                AREA OF PARK          38.12ha 11.74ha 10.204ha 60.064ha
K HOFMANN to accompany an application to NOOSA SHIRE COUNCIL for
a Development Permit to Reconfigure the land described in the plan and                                                                                                                                                                                                                                                                                         TOTAL AREA            46.93ha 30.14ha 32.93ha 110.0ha
is not to be used for any other purpose or by any other person or                                                                                                                                                                                                                                                                                              TOTAL NETT AREA OF LOTS (excluding lots 22 & 40)  16.7ha
corporation.                                                                                                                                                                                                                                                                                                                                                   AVERAGE LOT SIZE (excluding lots 22 & 40)        0.439ha
JFP URBAN CONSULTANTS PTY LTD accepts no responsibility for any loss
or damage suffered howsoever arising to any person or corporation
who may use or rely on this plan in contravention to the terms of this
clause or clauses 2, 3 or 4 hereof.

(2) The contours on this plan were derived from 2014 LIDAR data and
are suitable only for the purpose of this application. The accuracy of the
contours has not been verified and no reliance should be placed upon
such contours for any purpose other than for the purpose of this
application.

(3) The dimensions, areas, size and location of improvements, flood
information (if shown) and number of lots shown on this plan are
approximate only and may vary.

(4) This plan may not be reproduced unless these notes are included.


                LEGEND
                STAGING

                POWER POLES

                30m MANDATORY BUILDING SETBACK

                BUILDING ENVELOPE (1600m² max.)                                                                                                                                                             53
                                                                                                                                                                                                         SP163571



               FIRE TRAIL (12m WIDE)

               RL 3.0

                ENVIRONMENTAL ENHANCEMENT (NP2016)

                ENVIRONMENTAL PROTECTION (NP2016)                                                                                                                                                                                                                                                                                                                     53
                                                                                                                                                                                                                                                                                                                                                                   SP163571




                FLOOD HAZARD OVERLAY (NP2016)

                RIPARIAN BUFFER AREA (NP2016)
                                                                                                                                                                                                                                                                                                                                              3
                STREAMS AND RIVERS (NP2016)

               WATERCOURSE AND DRAINAGE (NP2016)
                                                                                                                                               1                                                                                                                     2
               CATEGORY A OR B AREA CONTAINING
               ENDANGERED REGIONAL ECOSYSTEMS
               CATEGORY A OR B AREA CONTAINING
               OF CONCERN REGIONAL ECOSYSTEMS
               CATEGORY A OR B AREA THAT IS
               LEAST CONCERN REGIONAL ECOSYSTEM

               NON GQAL

               FRAGMENTED GQAL

               NON GQAL DUE TO
               WETNESS LIMITATIONS
               POSSIBLE GQAL SUBJECT
               TO LOW WATER STORE
               EMERGENCY ACCESS FOR FIREFIGHTING
               PURPOSES FROM WALTER HAY DRIVE
               EXISTING EMERGENCY MANAGEMENT TRAIL
                                                                                                                    NORTH:       SCALE:                                                                                       ISSUES:                                                              TITLE:                                                                                                                                 DETAILS:
                                                                                                                                                                                                                                                                                                                                                                                                                             PROJECT:                 STAGE:       PLAN:          ISSUE:
                                                                                                                             N   SCALE: @ A1 1:2500 @ A3 1:5000
                                                                                                                                                                                                                                                                                                                                                                                                                              M1775 00 13                                           F
                                         BRISBANE - SUNSHINE COAST - CENTRAL QLD
                                         SUNSHINE COAST
                                                                                             PLANNERS
                                                                                             URBAN DESIGNERS
                                                                                                                                 0            50          100           150          200          250           300
                                                                                                                                                                                                            metres
                                                                                                                                                                                                                              F
                                                                                                                                                                                                                              E
                                                                                                                                                                                                                                        STAGE 2 LAYOUT AMENDED
                                                                                                                                                                                                                                        LAYOUT AMENDED
                                                                                                                                                                                                                                                                 26-03-20
                                                                                                                                                                                                                                                                 16-09-19
                                                                                                                                                                                                                                                                            TJM
                                                                                                                                                                                                                                                                            TJM       RECONFIGURATION PLAN                                                                                                                    SHEET:

                                         Tower 1, Level 2, 55 Plaza Parade,                                                      THIS SCALE SHOWN IS ORIGINAL DRAWING SCALE - (A1 SIZE)                                       D         LAYOUT AMENDED           11-09-19   TJM                                                                                                                                              1 OF 6
                                         Maroochydore, Qld 4558
                                         P 07 5450 3900 W www.jfp.com.au
                                                                                             SURVEYORS
                                                                                             ENGINEERS
                                                                                                                                 DO NOT SCALE FROM THIS DRAWING - USE ONLY DIMENSIONS PROVIDED - IF IN DOUBT PLEASE ENQUIRE   C         BLE'S AMENDED            09-08-19   DWW       K HOFMANN                                                                                                                              FILE:
                                                                                                                                                                                                                              B         BLE'S AMENDED & ADDED    07-08-19   DWW                                                                                                                                               M1775-13F-RP.dwg
          CONSULTANTS                     JFP URBAN CONSULTANTS PTY LTD A.C.N. 050 414 045   LANDSCAPE ARCHITECTS                DESIGNED          TJM   CHECKED         AD      DATUM                                        A         ORIGINAL                 25-07-19   TJM       HOLLETT ROAD, NOOSAVILLE                                                                                                               DATE:
                                                                                                                                 DRAWN             TJM   APPROVED        GB      L.A. NOOSA SHIRE COUNCIL                     ISSUE:      DETAILS:               DATE:      INIT:                                                                                                                                            26th March 2020
                                                                                                                                                                                                                                                                                COPYRIGHT © 2020 JFP URBAN CONSULTANTS PTY LTD. THIS DOCUMENT MAY NOT BE COPIED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS IN PART OR IN WHOLE WITHOUT THE WRITTEN CONSENT OF JFP URBAN CONSULTANTS PTY LTD.

Page 8

PROPERTY DESCRIPTION                                                                                                                                                                                                                                                                                                                                           STATISTICS            STAGE 1 STAGE 2 STAGE 3 TOTAL
LOT 53 ON SP163571                                                                                                                                                                                                                                                                                                                                             NO. OF LOTS
PARISH OF TEWANTIN/WEYBA                                                                                                                                                                                                                                                                                                                                         LOW DENSITY            17         22       --      39
COUNTY OF MARCH                                                                                                                                                                                                                                                                                                                                                  RURAL PURSUIT           --         --      1        1
TOTAL AREA 110.0 ha
                                                                                                                                                                                                                                                                                                                                                                 TOTAL                  17         22       1       40
NOTES                                                                                                                                                                                                                                                                                                                                                          LENGTH OF NEW
                                                                                                                                                                                                                                                                                                                                                                 20m ROAD              470m      840m       --   1310m
(1) This plan was prepared for the purpose and exclusive use of
K HOFMANN to accompany an application to NOOSA SHIRE COUNCIL for
                                                                                                                                                                                                                                                                                                                                                               AREA OF PARK          38.12ha 11.74ha 10.204ha 60.064ha
a Development Permit to Reconfigure the land described in the plan and                                                                                                                                                                                                                                                                                         TOTAL AREA            46.93ha 30.14ha 32.93ha 110.0ha
is not to be used for any other purpose or by any other person or                                                                                                                                                                                                                                                                                              TOTAL NETT AREA OF LOTS (excluding lots 22 & 40)   16.7ha
corporation.
JFP URBAN CONSULTANTS PTY LTD accepts no responsibility for any loss
                                                                                                                                                                                                                                                                                                                                                               AVERAGE LOT SIZE (excluding lots 22 & 40)        0.439ha
or damage suffered howsoever arising to any person or corporation
who may use or rely on this plan in contravention to the terms of this
clause or clauses 2, 3 or 4 hereof.

(2) The contours on this plan were derived from 2014 LIDAR data and
are suitable only for the purpose of this application. The accuracy of the
contours has not been verified and no reliance should be placed upon
such contours for any purpose other than for the purpose of this
application.

(3) The dimensions, areas, size and location of improvements, flood
information (if shown) and number of lots shown on this plan are
approximate only and may vary.

(4) This plan may not be reproduced unless these notes are included.




               LEGEND
                STAGING

               POWER POLES                                                                                                                                                                                    53
                                                                                                                                                                                                           SP163571



                30m MANDATORY BUILDING SETBACK

                BUILDING ENVELOPE (1600m² max.)

               FIRE TRAIL (12m WIDE)

               FAUNA CROSSING POINT                                                                                                                                                                                                                                                                                                                                       53
                                                                                                                                                                                                                                                                                                                                                                       SP163571


               STREAMS AND RIVERS (NP2016)

               WATERCOURSE AND DRAINAGE (NP2016)                                                                                                                                                                                                                                                                                                  3
               CATEGORY A OR B AREA CONTAINING
               ENDANGERED REGIONAL ECOSYSTEMS
               CATEGORY A OR B AREA CONTAINING
               OF CONCERN REGIONAL ECOSYSTEMS
                                                                                                                                                   1                                                                                                                     2
               CATEGORY A OR B AREA THAT IS
               LEAST CONCERN REGIONAL ECOSYSTEM
               EMERGENCY ACCESS FOR FIREFIGHTING
               PURPOSES FROM WALTER HAY DRIVE
               EXISTING EMERGENCY MANAGEMENT TRAIL




                                                                                                                    NORTH:       SCALE:                                                                                       ISSUES:                                                               TITLE:                                                                                                                                 DETAILS:
                                                                                                                                                                                                                                                                                                                                                                                                                               PROJECT:                STAGE:       PLAN:           ISSUE:
                                                                                                                             N   SCALE: @ A1 1:2500 @ A3 1:5000                                                                                                                                                                                                                                                                M1775 00 13                                           F
                                         BRISBANE - SUNSHINE COAST - CENTRAL QLD
                                         SUNSHINE COAST
                                                                                             PLANNERS
                                                                                             URBAN DESIGNERS
                                                                                                                                 0            50          100           150          200          250           300
                                                                                                                                                                                                            metres
                                                                                                                                                                                                                              F
                                                                                                                                                                                                                              E
                                                                                                                                                                                                                                        STAGE 2 LAYOUT AMENDED
                                                                                                                                                                                                                                        LAYOUT AMENDED
                                                                                                                                                                                                                                                                 26-03-20
                                                                                                                                                                                                                                                                 16-09-19
                                                                                                                                                                                                                                                                             TJM
                                                                                                                                                                                                                                                                             TJM       PLAN OF DEVELOPMENT                                                                                                                     SHEET:

                                         Tower 1, Level 2, 55 Plaza Parade,                                                      THIS SCALE SHOWN IS ORIGINAL DRAWING SCALE - (A1 SIZE)                                       D         LAYOUT AMENDED           11-09-19    TJM                                                                                                                                              2 OF 6
                                         Maroochydore, Qld 4558
                                         P 07 5450 3900 W www.jfp.com.au
                                                                                             SURVEYORS
                                                                                             ENGINEERS
                                                                                                                                 DO NOT SCALE FROM THIS DRAWING - USE ONLY DIMENSIONS PROVIDED - IF IN DOUBT PLEASE ENQUIRE   C         BLE'S AMENDED            09-08-19    DWW       K HOFMANN                                                                                                                               FILE:
                                                                                                                                                                                                                              B         BLE'S AMENDED & ADDED    07-08-19    DWW                                                                                                                                               M1775-13F-RP.dwg
          CONSULTANTS                     JFP URBAN CONSULTANTS PTY LTD A.C.N. 050 414 045   LANDSCAPE ARCHITECTS                DESIGNED       TJM     CHECKED          AD     DATUM                                         A         ORIGINAL                 25-07-19    TJM       HOLLETT ROAD, NOOSAVILLE                                                                                                                DATE:
                                                                                                                                 DRAWN          TJM     APPROVED         GB     L.A. NOOSA SHIRE COUNCIL                      ISSUE:      DETAILS:               DATE:       INIT:                                                                                                                                             26th March 2020
                                                                                                                                                                                                                                                                                 COPYRIGHT © 2020 JFP URBAN CONSULTANTS PTY LTD. THIS DOCUMENT MAY NOT BE COPIED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS IN PART OR IN WHOLE WITHOUT THE WRITTEN CONSENT OF JFP URBAN CONSULTANTS PTY LTD.

Page 9

                 Powerlin
               to Easem e Clearance
                        ent = 11
                                 .2m
              Powerlin
             to Easem e Clearance
                      ent = 10
                               .1m


                                                                                                                                                11.3m
                                      Ground =19.3
                                         und =13 .4
                                                  .9m
                                               RL =5




                                                                                                                                              10.4m
                                          ine RL




                                                                                                              3.84
                                                                                          bove Gro und RL =2.3
                                                                                                            .54m
                                                                                                    ine RL =1
                                  Power L




                                                                                                                                                                                                                                                                                       11.6m
                                                                                                  und =11
                                bove Gro




                                                                                                                                                             0.4
                                                                                                                                         bove Gro und RL =6.3
                                                                                                                                                           .1m
                                                                                                                                                   ine RL =2

                                                                                                                                                 und =14
                                                                                                                                                                                                                                                                                   10.4m
                                                                                                 Gro




                                                                                                                                                                                                                            Ground =15.9
                                                                                                                                                                                                                              und =10 .3
                                                                                                                                                                                                                                       .6m
                                                                                            Power L




                                                                                                                                                                                                                                    RL =5
                       Height A




                                                                                                                                                                                                                                 e RL
                                                                                                                                               Gro
                                                                                                                                           Power L




                                                                                                                                                                                                                                                                                                 .9
                                                                                                                                                                                                                                                                              bove Gro und RL =6.0
                                                                                                                                                                                                                                                                                               .9m
                                                                                                                                                                                                                                                                                         e RL =23
                                                                                                                                                                                                                        Power Lin




                                                                                                                                                                                                                                                                                                                                                                    3
                                                                                  Height A




                                                                                                                                                                                                                                                                                                                                                               =6.53
                                                                                                                                                                                                                                                                                                                                                                 .7m
                                                                                                                                                                                                                                                                                                                                        Ground (at fence) =20.2
                                                                                                                                                                                                                                                                                      und =17
                                                                                                                                                                                                                      bove Gro




                                                                                                                                                                                                                                                                                                                                                         nce)=13
                                                                                                                                                 Height A




                                                                                                                                                                                                                                                                                                                                    bove Gro RL (at fence)
                                                                                                                                                                                                                                                                                Power Lin
                                                                                                                                                                                                                                                                                    Gro
                                                                                                                                                                                                             Height A




                                                                                                                                                                                                                                                                                                                                              und (at fe
                                                                                                                                                                                                                                                                                                                                             ine RL
                                                                                                                                                                                                                                                                                     Height A




                                                                                                                                                                                                                                                                                                                                     Power L
                                                                                                                                                                                                                                                                                                                            Height A
PROPERTY DESCRIPTION
LOT 53 ON SP163571

NOTES

(1) This plan was prepared for the purpose and exclusive use of
K HOFMANN and their other professional advisers and is not to be
used for any other purpose or by any other person or corporation.                             (5) The contours on this plan were derived from 2014 LIDAR data
JFP URBAN CONSULTANTS PTY LTD accepts no responsibility for                                   and are suitable only for the purpose of this application. The
any loss or damage arising to any person or corporation who may                               Accuracy of the contours has not been verified and no reliance
use or rely on this plan in contravention of these terms.                                     should be placed upon such contours for any purpose other than
                                                                                              for the purpose of this application
(3) Only a small number of spot heights are shown. Refer to the
AutoCAD drawing for all spot heights and codes in layers: X-RL,                               (6) These notes form an integral part of this plan. If others use this
X-CODE & X-MARK.                                                                              information, they should be advised of its purpose and limitations.
(4) Spot heights are representative of the topographical terrain at                           (7) This plan may not be reproduced unless these notes are
time of survey, 28/01/2020.                                                                   included.

                                                                                                                         NORTH:           SCALE:                                                                                                   ISSUES:                                                   TITLE:                                                                                                                                DETAILS:
                                                                                                                                                                                                                                                                                                                                                                                                                                                   PROJECT:                        PLAN:           ISSUE:
                                                                                                                                  N      SCALE: @ A3 1:2000
                                             BRISBANE - SUNSHINE COAST - CENTRAL QLD PLANNERS                                            0                  20          40      60           80           100                120             140
                                                                                                                                                                                                                                                                                                               POWERLINE GROUND CLEARANCE M1775                                                                                                                                 20                  A
                                                                                                                                          SCALE 1:2000 at (A3) size                                                                                                                                                                                                                                                                                 SHEET:
                                             SUNSHINE COAST                                       URBAN DESIGNERS
                                             Tower 1, Level 2, 55 Plaza Parade,                   SURVEYORS
                                                                                                                                         THIS SCALE SHOWN IS ORIGINAL DRAWING SCALE - (A3 SIZE)
                                                                                                                                                                                                                                                                                                               K HOFMANN                  1 OF 1
                                                                                                                                         DO NOT SCALE FROM THIS DRAWING - USE ONLY DIMENSIONS PROVIDED - IF IN DOUBT PLEASE ENQUIRE                                                                                                                                                                                                                FILE:
                                             Maroochydore, Qld 4558
                                             P 07 5450 3900 W www.jfp.com.au                      ENGINEERS
                                                                                                  LANDSCAPE ARCHITECTS
                                                                                                                                         SURVEYED                LCM CHECKED    DNE      DATUM MGA Zone 56
                                                                                                                                                                                                                                                   A         ORIGINAL ISSUE   29-01-2020             TLP
                                                                                                                                                                                                                                                                                                           191 HOLLETT ROAD                                                                                                                        M1775-20 Powerlines.dwg
                                                                                                                                                                                                                                                                                                                                                                                                                                                   DATE:
    C O N S U L T A N T S JFP URBAN CONSULTANTS PTY LTD ACN 050 414 045                                                                  DRAWN                   TLP   APPROVED DNE      ORIGIN (BM) AHD vide SMARTNET                             ISSUE:    DETAILS:           DATE:                INIT: NOOSAVILLE                                                                                                                              29th January 2020
                                                                                                                                                                                                                                                                                                COPYRIGHT © 2012 JFP URBAN CONSULTANTS PTY LTD. THIS DOCUMENT MAY NOT BE COPIED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS IN PART OR IN WHOLE WITHOUT THE WRITTEN CONSENT OF JFP URBAN CONSULTANTS PTY LTD.

Page 10

PROPOSED SUBDIVISION AT HOLLETT ROAD, NOOSAVILLE


     Assessment of magnetic field levels associated with
      ENERGEX overhead 132kV circuits F790 / F7298




   A report completed by J&P Richardson Industries Pty Ltd
                  for KATHLEEN HOFMANN



                                         REVISION HISTORY
                      Number      Date         Status        Description
                       0.41     18/3/2020    Preliminary     For review
                        1.0     27/3/2020      Initial       For approval

Page 11

                                           (i)




                                     SUMMARY


A subdivision is proposed of Lot 53 SP163571 at Hollett Road, Noosaville.

Lot 53 is encumbered by a 26.5 metre wide easement that accommodates an
ENERGEX double circuit concrete and steel tower line supporting two 132kV high
voltage circuits.

ENERGEX has requested that an assessment be undertaken of the magnetic field
levels impacting on the proposed lots that will be located adjacent to the transmission
corridor to confirm that the levels are within industry standards and guidelines.

Average and maximum magnetic field calculations have been completed with respect
to the installed infrastructure and determined to be significantly less than the adopted
reference value of 4mG at the edge of the easement nearest the subject lots.

The subdivision layout has incorporated the principles of prudent avoidance in
building location and design on lots adjacent to the subdivision. This provision will
further reduce the magnetic field levels experienced by persons occupying the
residential subdivision.

Any miscellaneous development of the easement area for park or other recreational
purposes should aim to keep persons as clear of the powerline structures and
conductor alignment as practicable.

Page 12

                                   ( ii )


                          TABLE OF CONTENTS


1.0   INTRODUCTION …….....……………….…………………………….................... 1
      1.1  Property description
      1.2  Proposed Subdivision
      1.3  Purpose of study
      1.4  Methodology for assessing magnetic fields


2.0   THE TRANSMISSION LINES…………………………….………….................. 3
      2.1   Transmission line alignment and route
      2.2   Particulars in relation to Hollett Road property
      2.3   Feeder loading analysis
      2.4   Scenarios for future development


3.0   BACKGROUND ON MAGNETIC FIELDS ………………………..………..….… 6
      3.1 ARPANSA and ENA
      3.2 Australian Guidelines
      3.3 Prudent avoidance
      3.4 Electronic devices


4.0   MAGNETIC AND ELECTRIC FIELD CALCULATIONS……………..……….… 8
      4.1 General Parameters
      4.2 Average conductor height and geometry
      4.3 Magnetic and Electric field calculations


5.0   METHODS FOR REDUCING MAGNETIC FIELD LEVELS………..……….…..13
      5.1  Background
      5.2  Increasing distance from source
      5.3  Conductor geometry and phase configuration
      5.4  Conductor compactness
      5.5  Load current reduction and balancing
      5.6  Undergrounding


6.0   DISCUSSION….……...………………......……...…………………………………. 14
      6.1  Summary of magnetic field calculations
      6.2  Assessment of magnetic field levels
      6.3  Application of prudent avoidance principles
      6.4  General electrical safety considerations


7.0   CONCLUSIONS.……...………………......……...…………………………………. 16
      7.1  Review of key criteria
      7.2  Assumptions and limitations


APPENDIX 1    Subdivision plan of development…………………………………….. 17
APPENDIX 2    F790/F7298 structure site survey drawing……..………………….... 18
APPENDIX 3    F790/F7298 plan and profile drawing ……….…..………………….. 19
APPENDIX 4    ENERGEX IS(C)E intermediate tower geometry……….………….. 20

Page 13

      J&P Richardson Industries Pty Ltd        -1-


1     INTRODUCTION


1.1   Property description

      The subject property is lot 53 on SP163571 located at the intersection of Hollett Road and
      Walter Hay Drive, Noosaville. As shown in Figure 1 below, Lot 53 is split by existing
      transmission lines that are located on an established ENERGEX easement.

      Figure 1       Location of transmission infrastructure on subject property




1.2   Proposed subdivision

      The development proposal involves the subdivision of lot 53 into 39 low density and 1 rural
      pursuit lots in three stages (refer subdivision plan shown in Appendix 1).

      In its response to the development proposal, ENERGEX has suggested that the
      prospective magnetic field levels be investigated for properties immediately adjacent to the
      line – particularly lots 25-30, 39.




      Hollett Road EMF Study                                                        V1.0

Page 14

        J&P Richardson Industries Pty Ltd          -2-


1.3     Purpose of Study

        The purpose of this study is to provide a comprehensive response to ENERGEX’s request
        for an EMF investigation and report. In particular consider each of the following criteria:

           1. Current and future levels of EMF at the common boundary of easement B on
              RP177295 and the proposed lots.

           2. Compliance with applicable standards

           3. Incorporating the principles of prudent avoidance into the development

        The study will consider the proposed subdivision layout with regard to the existing and
        possible future scenarios for the transmission assets located within the easement corridor.


1.4     Methodology for assessing magnetic fields

        The initial step is to calculate the electric and magnetic field levels at the respective
        easement boundaries associated with an average value of load current through the
        transmission circuits. These values will be compared with a low-level target for magnetic
        field identified in the industry as broadly acceptable.

        Should calculated average values require mitigation, additional measures within the scope
        of prudent avoidance will be considered. As modification of the ENERGEX 132KV
        transmission line would be prohibitively expensive, the measures will focus on changes
        within the lot layout / building position within the subdivision development itself.

1.4.1   Relevance of magnetic versus electric fields
        The main focus of this report is in the calculation and minimising of magnetic fields
        associated with the ENERGEX high voltage lines. The majority of concerns regarding
        power frequency fields and possible negative impacts on human health have been directed
        toward magnetic fields.

        Electric fields are of a lesser concern, and are at very low levels for circuits energised at
        distribution voltages. Therefore electric field strengths will be listed in the report for
        completeness only.




        Hollett Road EMF Study                                                           V1.0

Page 15

        J&P Richardson Industries Pty Ltd       -3-


2.0     THE TRANSMISSION LINES

2.1     Transmission line alignment and route

2.1.1   Network connections
        The ENERGEX easement crossing the Noosaville property contains a double circuit
        concrete and lattice steel tower lines supporting conductors energised at 132kV.The
        associated circuits form part of the ENERGEX North Coast sub transmission network.

        As shown in Figure 2 below, the two circuits provide a 132kV connection from SSSRH
        Sunrise Hills substation to SSNVL Noosaville substation. When the lines were constructed
        (around 1983) they ran from Cooroy to Noosaville directly (as F796 and F797) – being later
        cut into SSSRH.

        There is no 132kV distribution bus at SSNVL – each feeder terminates directly onto the
        primary side of a 132kV/11kV transformer. The 11kV SSNVL bus is also normally open,
        meaning that the two 132kV feeders do not operate in strict parallel (the loads can be
        different).

        Figure 2       Part of North coast 132kV sub-transmission network




2.1.2   Line / structure description F7298/790
        Intermediate line structures are of concrete monopole construction incorporating composite
        offset post insulation. An additional standoff bracket has been added between the pole and
        insulator base to provide a climbing corridor on the structure.

        Lattice steel towers appear to have been used on strain structures.

        The line is a dual circuit six conductor configuration (single 37/3.00 AAC “SATURN”
        conductor per phase) with single overhead 18.2mm “Cossonay” (OHEW) earth wire. The
        lines have previously been phased for the minimum field arrangement (diagonal phasing).

        From ENERGEX records the design temperature of the 132kV lines was 80°C.


        Hollett Road EMF Study                                                      V1.0

Page 16

        J&P Richardson Industries Pty Ltd            -4-


2.2     Particulars in relation to Hollett Road property

        An easement in the order of 26.5 metres wide has been established over lot 53, with the
        transmission line located just offset from the centre of the easement (approximately 0.55m
        closer to the southern boundary - refer Appendix 2).

        As shown in Figure 1, there are a number of spans of 132kV mains on lot 53, but only two
        that impact on the subject area within the development :

                 Pole 303669 to Pole 303670 and
                 Pole 303670 to Pole 303671

        Relevant data for the three poles involved is summarised in Table 1 below.

        Table 1          Pole details

                                                                    BOTTOM CONDUCTOR POSITION
          TOWER                           OVERALL HEIGHT
                            TYPE2                                   Height above ground       Offset
          NUMBER                               (m)
                                                                            (m)                (m)
           303669           IS(C)E-0             19.5                     13.79                 2.3
           303670           IS(C)E-0             23.6                     17.903                2.3
           303671           IS(C)E-0             19.51                    13.791                2.3

        Note 1 : Pole and conductor heights sourced from ENERGEX plan and profile drawings.
                 Details for new P303671 were not provided, so it was assumed identical to
                 P303669.
        Note 2 : Detailed outline for the intermediate structure types IS(C)E shown in Appendix 2.
        Note 3 : As surveyed.


2.3     Feeder Loading analysis

2.3.1   F790 / F7298
        Loading for each of F790 and F7298 was determined by analysing load data supplied by
        ENERGEX for representative days as summarised in Table 2 below .

        Table 2          132kV feeder loading Sunrise Hills to Noosaville substation

                                        Average daily loading (A)
                Season reference
                                          F790             F7298
         Summer weekday (SWD)            75.38             62.62
         Summer weekend (SWE)            47.53             50.94
         Winter weekday (WWD)            36.76             37.46
         Winter weekend (WWE)            37.63             42.55
         OVERALL average (OAV)            52.5             50.9

        Note overall average load calculated as :

        OAV       =      [5*(SWD+WWD)/2 + 2*(SWE+WWE)/2]/7




        Hollett Road EMF Study                                                               V1.0

Page 17

        J&P Richardson Industries Pty Ltd        -5-


        A margin of 20% should be added to the above values to allow for system load growth.
        Final currents are 63A and 61A for F790 and F7298 respectively.
        The range of variation in load over a typical summer day for 132kV F790 is shown in Figure
        3 below.

        Figure 3       F790 Daily Load curve 21/1/2020




                                                                                   AVE = 75.4




2.4     Scenarios for future development

2.4.1   Network connections
        There is no indication that the circuit connections at 132kV (or 11kV feeders out of SSNVL)
        are planned to be altered in the foreseeable future.

2.4.2   Load criteria
        Magnetic field studies will be based on an average load calculation for each circuit (24hr
        365day). An escalation of 20% has been applied to the average present day load to
        account for future load growth.




        Hollett Road EMF Study                                                        V1.0

Page 18

      J&P Richardson Industries Pty Ltd         -6-


3.0   BACKGROUND ON MAGNETIC FIELDS


3.1   ARPANSA and ENA

      ARPANSA stands for the Australian Radiation Protection and Safety Agency. ARPANSA is
      a federal body that monitors and identifies solar radiation and nuclear radiation risks across
      a wide frequency spectrum to the population of Australia.

      The Energy Networks Association (ENA) is the peak national body representing gas and
      electricity distribution businesses throughout Australia. ENA has specific interest in electric
      and magnetic fields at power frequency (50Hz).

      In January, 2016 the ENA published the “EMF Management Handbook” which is
      considered to be the most up to date reference on the topic for Australian power networks.


3.2   Australian Guidelines

      The ENA handbook lists two sets of internationally recognised guidelines on EMF :

         a) International Commission on non-ionising radiation protection ( ICNIRP )
            “Guidelines for limiting exposure to time-varying electric and magnetic fields ( 1Hz-
            100kHz )” : 2010.

         b) IEEE International committee on Electromagnetic safety on non-ionising radiation
            “IEEE standard for safety levels with respect to human exposure to electromagnetic
            fields” :2002.

      As ARPANSA directly references ICNIRP 2010 as a guideline for exposure, the ICNIRP
      document will be used as the primary source for EMF levels in this report. It is noted that
      the IEEE guidelines provide an alternate set of limits which could be applied to specialist
      exposure environments.

      The reference levels for EMF exposure as listed in the ICNIRP guidelines ( Table 5-2 and
      Table 5-3 ENA Handbook ) are shown in Table 3 below.

      Table 3        ICNIRP reference levels for 50Hz EMF exposure

                                                       ELECTRIC FIELD         MAGNETIC FIELD
                    EXPOSURE TYPE                        STRENGTH               STRENGTH
                                                          (V/m)                   ( mG )
       Occupational ( General )                             10000                  10000
       Occupational ( head and torso)                    Not specified          Not specified
       Occupational ( arms and legs)                     Not specified          Not specified

       General public ( General )                            5000                   2000
       General public ( head and torso)                  Not specified          Not specified
       General public ( arms and legs)                   Not specified          Not specified




      Hollett Road EMF Study                                                           V1.0

Page 19

      J&P Richardson Industries Pty Ltd         -7-


3.3   Prudent Avoidance

      ENA recommends to members that they design, operate and maintain their networks
      prudently with regard to EMF exposure. Prudent avoidance has been defined in an
      Australian context by the former Chief Justice of the High Court of Australia, Sir Harry
      Gibbs as doing what can be done without undue inconvenience and at modest expense to
      avert the possible risk to health from exposure to new high voltage transmission facilities. In
      practical terms, this means designing new Transmission and Distribution facilities having
      regard to their capacity to produce EMF’s, and siting them having regard to the proximity of
      houses, schools, and the like.

      The ENA EMF handbook lists key guiding principles for applying prudent avoidance in
      relation to EMF, including the following :

            Measures to reduce exposure should be used if they can be implemented at ‘no
             cost’ or ‘very low cost’ and provided they do not unduly compromise other issues.

            There is no reliable scientific basis for the adoption of arbitrary low exposure limits
             or setbacks or for a specific exposure level at which precaution should apply.

            Prudent avoidance / precaution does not operate in isolation but rather is one of
             many issues that need to be given due consideration in the design and operation of
             the electricity supply system.


3.4   Electronic Devices

      Cathode ray tube (CRT) based computer monitors are susceptible to interference from low
      frequency magnetic fields. Immunity levels for CRT’s and other electronic devices are listed
      in AS/NZS 4251.1 “Electromagnetic compatibility – generic immunity standard”, and are
      summarized in Table 4 below.

      Table 4        LF magnetic field Immunity limits for electronic devices

          Device type          Residential / commercial environment
       CRT displays                            12.5mG
       Other equipment                         37.5mG




      Hollett Road EMF Study                                                           V1.0

Page 20

        J&P Richardson Industries Pty Ltd      -8-


4.0     MAGNETIC AND ELECTRIC FIELD CALCULATIONS


4.1     General Parameters

4.1.1   Load current
        The average load currents to be used in all studies are 63A and 61A per phase for F790
        and F7298 respectively (refer Table 2 S2.3.1) with both circuits energised.

        The 10PoE loads for F790 and F7298 through to 2023/2024 in the most recent ENERGEX
        132/132kV feeder forecast are 78A and 77A respectively.

4.1.2   Phasing
        The phasing configuration on the double circuit line is as shown in Figure 4 S4.2.3. The
        configuration is known as diagonal phasing and is the arrangement adopted to produce
        minimum magnetic field level.

4.1.3   Height of field calculation
        Height of field calculation above ground = 1m.


4.2     Average conductor height and geometry

        A temperature of 50°C will be used as the reference for average phase conductor height
        calculations.

4.2.1   F790/7298
        Phase conductor           :    SATURN (design temperature 80°C)
        OHEW                      :    1x18.2mm “Cossonay” OHEW
        Average span              :    207.5m
        Stringing tension         :    18.2% UTS (phase), 8.8% (OHEW)
        Minimum clearance         :    6.7m

        Calculate average conductor height = (RL1+RL2)/2 – 2/3 *sag

        Table 5A       Average height lower phase conductor F790 / 7298

            FROM                       TO                                           AVERAGE
                         RL(m)                  RL(m)    SPAN(m)     SAG@50°C
            POLE                      POLE                                           HAG (m)
           303669         13.79       303670    17.90       223           7.0         11.12
           303670         17.90       303671    13.79       192           5.2         12.38

        Table 5B       Average height OHEW F790 / 7298

            FROM                       TO                                           AVERAGE
                         RL(m)                  RL(m)    SPAN(m)     SAG@25°C
            POLE                      POLE                                           HAG (m)
           303669         19.59       303670    23.70       223          5.71         17.84
           303670         23.70       303671    19.59       192          4.23         18.82

        NB : HAG = Height above ground




        Hollett Road EMF Study                                                       V1.0

Page 21

        J&P Richardson Industries Pty Ltd           -9-


4.2.3   Geometry
        The magnetic field calculations will be based on the intermediate pole top construction
        shown in Appendix 2 for F790/F7298. A simplified ‘stick figure’ representation of the
        structure geometries is reproduced in Figure 4 below for convenience.

        Figure 4           F790 / 7298 Intermediate construction geometry ( IS(C)E

                   0.09m


                                                            2.00m

                   AФ                               CФ

                                                            1.90

                   BФ                               BФ
                             2.30m
                                                            1.90
                                                            m
                   CФ                               AФ




4.3     Magnetic and electric field calculations

4.3.1   Scenario1 average feeder load
        The results of electric and magnetic field calculations relevant to scenario1 are summarised
        in Table 7 below and Figure 6 and figure 7 overleaf.

        Table 7            EMF levels scenario1 average 132kV feeder load

                                        Calculated value at edge of
                                                                            4mG offset
               PARAMETER                        easement                                             Maximum
                                         Northern         Southern    Northern    Southern

         Magnetic Field strength         0.54mG            0.71mG       N/A          N/A              1.83mG

         Electric Field strength        0.139kV/m         0.113kV/m    ------        ------          0.329kV/m




        Hollett Road EMF Study                                                                V1.0

Page 22

J&P Richardson Industries Pty Ltd       -10-


Figure 6       Magnetic Field profile : scenario1




Figure 7       Electric Field profile : scenario1




Hollett Road EMF Study                              V1.0

Page 23

        J&P Richardson Industries Pty Ltd          -11-


4.3.2   Scenario2 Feeder 10PoE load forecasted
        The results of electric and magnetic field calculations relevant to scenario2 are summarised
        in Table 8 and Figure 8 below and figure 9 overleaf.

        Table 8          EMF levels scenario2 : maximum 132kV feeder load

                                       Calculated value at edge of
                                                                            4mG offset
               PARAMETER                       easement                                             Maximum
                                       Northern           Southern    Northern    Southern

         Magnetic Field strength        0.83 mG           0.71 mG       N/A          N/A             2.26mG

         Electric Field strength       0.136kV/m          0.113kV/m    ------       ------          0.329kV/m



        Figure 8         Magnetic Field profile : scenario2




        Hollett Road EMF Study                                                               V1.0

Page 24

J&P Richardson Industries Pty Ltd       -12-


Figure 9       Electric Field profile : scenario2




Hollett Road EMF Study                              V1.0

Page 25

      J&P Richardson Industries Pty Ltd         -13-


5.0   METHODS FOR REDUCING MAGNETIC FIELD LEVELS


5.1   Background

      Magnetic field strength of a powerline is a function of a number of variables, including the
      current through the transmission circuits, the distance from the line, and the physical and
      electrical geometry of the conductors. As the current through the transmission lines
      changes with time, the associated magnetic field is a continuously changing parameter.

      The Electric Field strength is a function of the physical attributes of a line and the voltage to
      which the line has been energised. As such, the Electric field strength at a particular point
      will remain at the same order of magnitude over time.


5.2   Increasing distance from source

      As the magnetic field strength decreases as distance from the source increases, the
      separation from the distribution line to the habited areas should be maximised as far as
      practicable.

      It is noted that the net separation is a function of both the lateral and vertical ( ie due to
      conductor height ) offsets.


5.3   Conductor geometry and phase configuration

      Different arrangements of phase conductors can produce different magnetic field strengths
      for the same line current. Equilateral triangular arrangements tend to be the most
      favourable, producing more field cancellation than the common flat arrangements.

      With multi-circuit lines the careful placement of conductors with respect to phase can
      significantly reduce the net magnetic field. The example often used is the double circuit
      vertical construction diagonally phased (A-B-C on one side, C-B-A on the other).


5.4   Conductor compactness

      The compactness of a line can reduce the resultant magnetic fields by enhancing the field
      cancellation effect between the phases.


5.5   Load current reduction and balancing

      Load current can be reduced by supplying the load fed through the subject circuit by using
      an alternate route or increasing the supply voltage. These options are rarely available.


5.6   Undergrounding

      Undergrounding can be effective at reducing magnetic fields due to the very compact
      positioning of the respective phase conductors. However, because undergrounding is far
      more expensive than overhead construction, it does not often fall into the category of
      prudent avoidance.



      Hollett Road EMF Study                                                             V1.0

Page 26

        J&P Richardson Industries Pty Ltd        -14-


6.0     DISCUSSION


6.1     Summary of magnetic field calculations

        The key results of sections 4.3 of this report with respect to magnetic field are summarised
        in Table 9 below.

        Table 9         Magnetic field levels for proposed 132kV constructions

                               CALCULATED MAGNETIC FIELD STRENGTHS (mG)
             Scenario
                                 Easement            Easement
                                                                         maximum
                                  (North)             (South)
                  1                0.54                 0.71               1.83
                  2                 0.71                0.83               2.26

        Scenario1 represents the system normal configuration with inbuilt escalation in the average
        132kV line currents to account to load growth. It therefore represents a ‘future’ average
        magnetic field level. Scenario 2 represents a ‘worst case’ field with both feeders in service.


6.2     Assessment of magnetic field levels

        It can be seen with reference to Table 9 and Table 3 that the calculated magnetic field
        levels are several orders of magnitude less-than the maximum permissible exposure levels.

        It is further noted that the calculated worst case magnetic field at the edge of the easement
        is less than 25% of the widely adopted industry reference value of 4mG adjacent the
        proposed lots. In addition the maximum magnetic field across the easement itself (under
        the powerline) is significantly less than this reference value.


6.3     Application of prudent avoidance principles

        Routine consideration must be given to measures that may reduce the magnetic field levels
        at the site within the scope of prudent avoidance. Even very minor cost impacts may be
        difficult to justify at this particular site given the very low prospective magnetic field levels.

6.3.1   ENERGEX transmission infrastructure.
        The conductor phase orientation on the two double circuit tower lines is already configured
        for minimum magnetic field level.

        The only other way that magnetic field levels associated with the transmission circuits could
        be reduced is by altering the physical construction of the support structures – by using
        more compact or taller structures, or undergrounding.

        Any of these changes would have either functional or significant cost impact and therefore
        not be within the scope of prudent avoidance.




        Hollett Road EMF Study                                                            V1.0

Page 27

        J&P Richardson Industries Pty Ltd       -15-


6.3.2   Subdivision lot layout
        The main way that prudent avoidance is applied in subdivisions is to increase the distance
        from the source.

        Practical ways in which prudent avoidance can be incorporated into the plan development
        include the following :

                   a. Not positioning buildings close to the property boundary abutting the
                      easement

                   b. Locating bedrooms and main living areas at the opposite end of the
                      residence where practicable.

                   c. Orienting lots so that the short end of the building is parallel with the axis of
                      the transmission lines.

        The subdivision design has considered and applied prudent avoidance principles in the
        latest subdivision layout plan (refer Appendix 1). It can be seen that a buffer zone between
        the building envelope and the edge of the power line easement has been included. The
        buffer zone will reduce the magnetic field levels within the dwelling and therefore lower the
        resident’s long term exposure.


6.4     General Electrical safety considerations

        The two main areas of hazard are as follows :

        1. Direct contact with the energised conductors

           Sub-transmission lines such as 132kV F790 and F7298 do not employ systems to
           restrict earth fault currents and can be associated with very high fault currents.
           Combined with the energised voltage level these circuits become very unforgiving of
           inadvertent contact - likely to lead to serious injury or death.

        2. Contact with a concrete structure during an earth fault.

           When an earth fault occurs on the transmission line, current takes all paths to earth
           back to the source, including through the structure foundation. This current flow causes
           a rise in potential (voltage) on the pole. This potential can be a touch hazard to persons.


        In order to minimise these hazards, it is recommended that any development within the
        easement area :

              Have prior approval of ENERGEX

              Minimise the opportunity for persons contacting the concrete line structures (for
               example keep walking paths a minimum of 5m from pole bases).

              Minimise the opportunity for persons frequenting the area directly under the
               conductors themselves.(for example play equipment kept as far as practicable from
               the line itself).




        Hollett Road EMF Study                                                           V1.0

Page 28

      J&P Richardson Industries Pty Ltd           -16-


7.0   CONCLUSIONS


7.1   Review of key criteria

      An assessment of the proposed subdivision with regard to the report aims listed in S1.3 is
      summarised in Table 10 below.

      Table 10        Subdivision compliance assessment summary

                      Criteria                                          Assessment

        No              Description               Achieved                      Comment

                                                             Refer S2.4.2.
              Calculations have considered                   No advice received from ENERGEX regarding any
         1    current and future levels of EMF.
                                                     Y       future (Planned) changes to the 132kV circuits or
                                                             their load (request submitted 30/1/2020).

              Compliance with applicable
         2    standards and industry practice.
                                                     Y       Refer S6.2.

                                                             Refer S6.3.
              Development incorporates the
         3    principles of prudent avoidance.
                                                     Y       ENERGEX line phasing already configured in
                                                             minimum field arrangement.



      It can be seen from Table 10 above that the proposed subdivision layout meets the
      required criteria with respect to magnetic fields associated with the ENERGEX 132kV
      power infrastructure.


7.2   Assumptions and limitations

            Safety issues concerning touch voltages in the vicinity of towers or preventing
             access to high voltage towers or conductor corridors are not included in this study.

            Load criteria for magnetic field studies based on the average and estimated
             maximum current through each 132kV feeder based on the supplied data.

            Magnetic and electric field calculations based on the geometry of the double circuit
             intermediate constructions used on the line.

            Magnetic and electric field studies based on an average phase conductor
             temperature of 50°C.

            Positioning on the easement assumed for F790 assumed to be 12.7m from the
             southern edge.




      STEVEN FLOWER B Eng B Sc RPEQ
      SENIOR ELECTRICAL ENGINEER



      Hollett Road EMF Study                                                                  V1.0

Page 29

J&P Richardson Industries Pty Ltd                                  -17-
                                    APPENDIX 1   PRELIMINARY DEVELOPMENT PLAN FOR HOLLETT ROAD, NOOSAVILLE




 Hollett Road EMF Study                                                                                      V1.0

Page 30

J&P Richardson Industries Pty Ltd                    -18-
                                    APPENDIX 2   F790/F7298 Structure site survey drawing




Hollett Road EMF Study                                                                      V1.0

Page 31

J&P Richardson Industries Pty Ltd                  -19-
                                    APPENDIX 3   F790/F7298 Plan and Profile drawings




Hollett Road EMF Study                                                                  V1.0

Page 32

  J&P Richardson Industries Pty Ltd                           -20-
                                      APPENDIX 4   Type IS©E double circuit 132KV Intermediate Pole Geometry




Hollett Road EMF Study                                                                                         V1.0

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.