5.0 METHODS FOR REDUCING MAGNETIC FIELD LEVELS
5.1 Background
Magnetic field strength of a powerline is a function of a number of variables, including the
current through the transmission circuits, the distance from the line, and the physical and
electrical geometry of the conductors. As the current through the transmission lines
changes with time, the associated magnetic field is a continuously changing parameter.
The Electric Field strength is a function of the physical attributes of a line and the voltage to
which the line has been energised. As such, the Electric field strength at a particular point
will remain at the same order of magnitude over time.
5.2 Increasing distance from source
As the magnetic field strength decreases as distance from the source increases, the
separation from the distribution line to the habited areas should be maximised as far as
practicable.
It is noted that the net separation is a function of both the lateral and vertical ( ie due to
conductor height ) offsets.
5.3 Conductor geometry and phase configuration
Different arrangements of phase conductors can produce different magnetic field strengths
for the same line current. Equilateral triangular arrangements tend to be the most
favourable, producing more field cancellation than the common flat arrangements.
With multi-circuit lines the careful placement of conductors with respect to phase can
significantly reduce the net magnetic field. The example often used is the double circuit
vertical construction diagonally phased (A-B-C on one side, C-B-A on the other).
5.4 Conductor compactness
The compactness of a line can reduce the resultant magnetic fields by enhancing the field
cancellation effect between the phases.
5.5 Load current reduction and balancing
Load current can be reduced by supplying the load fed through the subject circuit by using
an alternate route or increasing the supply voltage. These options are rarely available.
5.6 Undergrounding
Undergrounding can be effective at reducing magnetic fields due to the very compact
positioning of the respective phase conductors. However, because undergrounding is far
more expensive than overhead construction, it does not often fall into the category of
prudent avoidance.
Hollett Road EMF Study V1.0