Response to RFI Sewer & Water Network Plans · OPW25/0057
Plans and drawings: the text below has words only, no drawings.
Original PDF page 4, section 1. The text section number identifies this passage in the reader.
PROPOSED CONNECTION TO EXISTING Ø250 DI
Shane Rynne
I,............................................. of COVEY ASSOCIATES Pty. Ltd.
NOTE: CONNECTION TO UNITYWATER
3m FOR UNITYWATER CONNECTION TRUNK WATER MAIN BY UNITYWATER. EXACT
NETWORK INFRASTRUCTURE IS SUBJECT 18-03-2025
LOCATION OF WATER MAIN TO BE CONFIRMED ON............................, CERTIFY that:
TO FURTHER APPLICATION
ON SITE PRIOR TO CONSTRUCTION
1. This design drawing has been assessed in accordance with
3m NOTE: THRUST BLOCKS ARE REQUIRED requirements of the SEQ Code and Unitywater Standards;
AT ALL CHANGES OF DIRECTION 2. The construction of the works must only be undertaken in
accordance with this drawing; and
NOTE: ALL WORKS ON EXISTING WATER 3. No design Amendments are permitted either before or
EXISTING PATH AND MAINS TO BE CARRIED OUT BY
KERB RAMP TO BE during construction without the approval of Unitywater.
UNITYWATER AT DEVELOPER'S EXPENSE 4. During construction, where required, Variation Notifications
REMOVED BY
) must be submitted in accordance with the A&C Manual.
1.5m CONTRACTOR
E (2 NOTE: REFER TO SHEET C460 FOR
EL BOR SCHEDULE OF LIVE WORKS AND
UNN ACR/MAJ
900 0P E1 00 T SCHEDULE OF PIPEWORKS AND FITTINGS 2020-112
SIGNED: .........................................................
DN18
EXISTING
STORMWATER
DIA
TO BE REMOVED
NE
ex FH FLANGED OFF-TAKE CLAMP (REFER
LLA
SEQ-WAT-1105-2) UNDER PRESSURE
CONNECTION METHOD
CT
EXISTING Ø250 DI TRUNK WATER MAIN
EX
DI IST
WA ING
22.5° BEND TE D
R N2
MA 50 FL-FL SLUICE VALVE
IN
PE FULL FACE FLANGE
3m CONNECTION BY UNITYWATER
WITH BACKING RING
80
DN180 PE100 PN16
1
N1
AD
6D
RO
1
PN
22.5° BEND
100
PE
11.25° BEND BY UNITYWATER
WATER UNDER STW PIPE UNITYWATER TO REMOVE DUCKFOOT
MIN 300mm CLEARANCE HYDRANT AND COMPLETE CONNECTION
TO EXISTING WATER MAIN
22.5° BEND
CONTRACTOR TO
INSTALL TEMPORARY
DUCKFOOT HYDRANT
TUNNEL BORE BY CONTRACTOR
PE FULL FACE FLANGE
DN180 PE
WITH BACKING RING
WATER OVER SEW HC
100 PN16
MIN 500mm CLEARANCE
Ø150 PVC-O
PN16
WATER CONNECTION DETAIL NOTE
1. ALL DICL BENDS TO BE FLANGED JOINTS.
2. WHERE PE CROSSINGS ARE USED THRUST RESTRAINT TO
BE PROVIDED IN ACCORDANCE WITH SEQ-WAT-1211-1
ROAD CROSSING DETAIL 3. FLANGED CONNECTIONS IN ACCORDANCE WITH
SCALE 1:25 (A1) - 1:50 (A3) SEQ-WAT-1313-1
4. WHERE PE CROSSINGS ARE USED PIPES MAY BE CURVED
IN LIEU OF IMPLEMENTING BENDS IF CLEARANCE TO
MIN 600 COVER
BURIED SERVICES CAN BE MAINTAINED. MINIMUM RADIUS
(TYPICAL)
SCALE 1:100 (A1) - 1:200 (A3) BENDS IN ACCORDANCE WITH PIPA GUIDELINE POP202
(TABLE REPRODUCED BELOW)
108 MIN BEND RADIUS (x
Ø150 PVC-O PN16 DN180 PE100 PN16 WATER MAIN PROPOSED DN160 PE100 TUNNEL BORE (21.5m) 3m PIPE SDR (PN)
107 PIPE OD)
CONNECTION
DIANELLA CT 9 (20) 12
STW Ø600 RCP
BY
STW Ø375 RCP
106 UNITYWATER EXISTING
EXISTING STW
11 (16) 15
DESIGN SURFACE EXISTING STORMWATER SURFACE
105
Ø450 RCP
CL
TO BE REMOVED
104 PROPOSED CONNECTION TO EXISTING Ø250 DI
TRUNK WATER MAIN BY UNITYWATER. EXACT
103 LOCATION OF WATER MAIN TO BE CONFIRMED
~1m
ON SITE PRIOR TO CONSTRUCTION
102
22.5° BEND HORIZONTAL BEND
101 SEWER PROPERTY HORIZONTAL BEND
CONNECTION (LOT 1) 22.5° BEND MIN 300 APPROX. LOCATION OF
CLEARANCE
HORIZONTAL BEND PE FULL FACE FLANGE FL-FL SLUICE VALVE
300 MIN
100 CLEARANCE EXISTING ELECTRICITY WITH BACKING RING
& COMMUNICATIONS
Check all dimensions before commencement of work.
ROAD CROSSING SECTION IT IS THE RESPONSIBILITY OF THE Check Site boundary dimensions from the Title plans
CONTRACTOR TO CONTACT THE RELEVANT Check Building Boundary clearances by set out.
AUTHORITIES TO CONFIRM THE LOCATION OF Notwithstanding the information supplied on this drawing,
ALL EXISTING SERVICES PRIOR TO THE the location, depth and extent of underground or overhead
SCALE 1:100 (A1) - 1:200 (A3) COMMENCEMENT OF EXCAVATION services are to be confirmed and protected on site by the
contractor prior to commencement of works.
Approved
Checked - CT Drawing title - Project - PROPOSED 1 INTO 3 Site - Project No. 233467 Sheet No. C440
Design - SK Drawn - SK D 24/03/2025 UPDATED PROJECT NAME SK WATER CONNECTION DETAILS DEVELOPMENT 62 LAKE MACDONALD DRIVE, Digital Ref :
C440 WATER CONNECTION
DETAILS Issue : D
C 14/03/2025 UPDATED LOT LAYOUT SK
Scales - AS SHOWN B 20/09/2024 ISSUE FOR APPROVAL SK COVEY ASSOCIATES PTY LTD 124 DUPORTH AVENUE Client -
NOOSA COUNCIL COOROY This Document is copyright and shall not be copied
A 10/01/24 ISSUE FOR CLIENT REVIEW SK
ABN 59 137 305 992 PO BOX 16 without written approval, nor shall it be used except
Document Stage - APPROVAL (07) 5443 7777 MAROOCHYDORE QLD 4558 for the Development and the Site Specified.
Issue Date Description By [email protected]
c:\12dS\data\12DSERVER\233467_2957\DWG Covey\OPW\Uncontrolled\C440 WATER CONNECTION DETAILS.dwg Plot 1 July 2025 - 11:02 AM
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Response to RFI Sewer & Water Network Plans.pdfRelated documentApplication case desk ↗
About this file
- File size
- 2.4 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.