Plans 2155 01 S A FOR APPROVAL 06 11 2019

of 8

Page text shows just the words. Original shows the document exactly as it was published.

Plans and drawings

This document appears to be plans or drawings. Its page text below holds only the words printed on the drawings, without the drawings themselves, so it may be jumbled or hard to follow. To see the plans as drawn, choose Original above or download the file (both need you to log in).

Log in to see the plans as drawn
                                          DRAINAGE PATH                               DISCHARGE RUNOFF                                                 GEOTECHNICAL                                                                                                                          CONCRETE NOTES:
                                                                                      CLEAR OF BUILDING
                                                                                                                                                       A sub-soil investigations was undertaken at this site by Global Testing report No. 18/0717 this site has been                        1.      All workmanship and materials shall be in accordance with the requirements of the relevant current Australian




                     DRAINAGE PATH
                                                                                                                                                       classified as class 'P/M' in accordance with AS2870 - 2011.                                                                                  Standard Codes (AS3600-2001 & AS2870-1996), Building By-Laws and the ordinances of the relevant Local
 GROUND                                          PROPOSED                                                                                              The Building Works contractor must review this report and obtain confirmation from a geotechnical engineer                                   Authority.
 SLOPE                                           RESIDENCE                                                                                             that the report is representative after site earthworks have been completed.                                                          2.     Concrete Specification
                                                                                                                                                       Refer to this report for details regarding:                                                                                                  Application      Conc Str (MPa)          Max Slump (mm)         Max Agg. Size (mm) Min. Cover (mm)
                                                                                                                                                        ·      Temporary batter slopes and positive support options for proposed excavations.                                                       Footings                N25                     80 (+20, -10)                   20              50
                                                                                                                                                        ·      Water table levels and if De-watering of proposed excavations is required                                                            External Slab on ground N25                     80 (+20, -10)                   20              40
                                                                                                                                                        ·      Site drainage recommendations
                                                                                                                                                       A general description of various soil classification materials is listed in the following table.                                             All concrete testing is to be carried out by a NATA registered laboratory, in strict accordance with the
                                                                                                                                                                                                                                                                                                           requirements of AS1012. The following minimum testing schedule is to be adopted in addition to the
            DISCHARGE RUNOFF                                                                                                                                SITE CLASS         FOUNDATIONS                                                                                                                 requirements of the manufacturer's quality assurance program.
            CLEAR OF BUILDING                                                                                                                                                                                                                                                                       - A minimum of one test (3 cylinders) to be taken from each element cast on any given day (eg. Columns,
                                                                                                                                                        CLASS A           Mostly sand and rock sites with little or no ground movement from moisture changes.
                                                                                                                                                                                                                                                                                                           footings, etc)
                                                                                                                                                        CLASS S           Slightly reactive clay sites with only slight ground movement potential from moisture changes.                            - A minimum of one test (3 cylinders) to be taken from each concrete strength grade cast on any given day.
                                                                                                                                                                                                                                                                                                    - A minimum of one test (3 cylinders) to be taken from each 50m³ or part thereof cast on any given day for
                                                                                                                                                                          Moderately reactive clay or silt sites which can experience moderate ground movement                                             each strength grade.
                                                                                                                                                        CLASS M
                                                                                                                                                                          potential from moisture changes.                                                                                          - All samples are to be taken from the agitator, on site, tested by a NATA registered laboratory and results
                DRAINAGE PATH




                                                                                      DRAINAGE PATH
 GROUND                                          PROPOSED                                                                                                                                                                                                                                           provided to the Engineer for review
 SLOPE                                                                                                                                                 CLASS H1-H2 Highly reactive clay sites, which can experience high ground movement from moisture changes.
                                                 RESIDENCE                                                                                                                                                                                                                                   3.     No penetrations, recesses or chases other than those shown on the structural drawings shall be made in
                                                                                                                                                                          Extremely reactive sites, which can experience extreme ground movement from moisture                                      concrete members without the approval of the Engineer.
                                                                                                                                                        CLASS E
                                                                                                                                                                          changes.                                                                                                           4.     Unless noted otherwise all formed edges and corners of concrete members shall have 20mm chamfers.
                                                                                                                                                                          Sites which include soft soils, such as soft clay or silt or loose sands; uncontrolled fill; landslip                     Provide drip grooves to the perimeter of the soffits of all concrete members.
                                                                                                                                                        CLASS - P         risk; mine subsidence; collapsing soils; soil subject to to erosion; reactive sites subject to
                                                                                                                                                                          abnormal moisture conditions or sites which cannot be classified otherwise.
            DISCHARGE RUNOFF                                          DISCHARGE RUNOFF
            CLEAR OF BUILDING                                         CLEAR OF BUILDING
                                                                                                                                                       EARTHWORKS NOTES:                                                                                                                     CONCRETE SLABS:
                                                                                                                                                       Where any filling is carried out on the site after the completion of the site investigation and civil earth works, the               Preparation:
   TYPICAL SITE DRAINAGE LAYOUT                                                                                                                        following recommendation shall be followed:-                                                                                         1. Subgrade to be proof rolled with any unsuitable material removed and replaced in accordance with
                                                                                                                                                                                                                                                                                                   earthworks notes.
                                                                                                                                                       1. The site shall be stripped of all vegetation prior to the placement of any filling material.
                                                                                                                                                       2. Compaction Standards for filling material                                                                                         2. Any filling under slab to be placed in accordance with earthworks notes.
                                                                                                                                                               A. Controlled Filling                                                                                                        3. Place and compact a 50mm layer of bedding sand under slab areas with 0.2mm vapour barrier over, tap and
                                                                                                                                                               (a) Sand filling up to 800 deep, placed in maximum 300 thick layers and compacted with a vibrating roller                           seal all joints.
                                                                                                                                                               to achieve a minimum Dynamic Cone Penetrometer reading of 13 blows per 300 penetration                   (refer AS           3. At penetrations in slabs, unless otherwise detailed reinforcement must not be cut but shall be gathered
                                                                                                                                                               1329.F3.3). Sand fill may be flooded if necessary to achieve this compaction standard, provided the water                           equally to each side of the penetrations and extra reinforcement provided between the penetrations as
                                                   DR                                                                                                          can subsequently be drained from the site.                                                                                          directed by the Engineer.
                                                        AIN
                                                            AG                                                                                                 (b) Non-sand filling up to 400 deep, placed in maximum 150 thick layers and compacted with a                                 4. During dry weather moisten timber formwork to assist curing of surfaces.
                                                               E   PAT
                                                                       H                                                                                       mechanical roller. Clay fill shall be moist during compaction.                                                               Placing:
                                                                                                                                                               (c) Controlled filling shall continue for at least 1 meter past the edge of the structure and shall be battered              1. Ensure no water is added to the concrete after initial batching.
                                                                                                                                                               back to the original surface with a slope of no more than 1:2 (Vert : Hor).                                                  2. No concrete to be poured when site temperature exceeds 35° C or falls below 5° C.
                                                                                                                                                               (d) Where the depth of filling material exceeds that specified above, the filling material shall be                          3. Constructions Joints or pour breaks where not shown on the approved plans or details shall be located and
                                                                                                                                                                                                                                                                                                   formed to the approval of the Engineer
                                                                                  ATH




GROUND                                    PROPOSED                                                                                                             compacted as follows:-
SLOPE                                                                                                                                                                                                                                                                                       4. Vibrate concrete during placement
                                                                                    P




                                          RESIDENCE                                                                                                            Sand fill to 70% Density Index in accordance with AS1329.E6.1
                                                                                AGE




                                                                                                                                                               Non-sand fill to 98% Maximum Dry Density (Standard Compaction) in accordance with AS1329 cl 5.4.1                            Curing:
                                                                                                                                                                                                                                                                                            1. Curing by continuous wetting and/or covering for a period of not less than 7 days
                                                                              DRAIN




                                                                                                                                                               Compaction tests shall be carried out on each layer as the filling is placed and results provided to the
                                                                                                                                                                                                                                                                                                   or by application of an appropriate sprayed membrane curing compound.
                                                                                                                                                               Engineer for approval.
                                                                                                                                                                                                                                                                                            2. Retain form work as long as possible on vertical surfaces
                                                                                                                                                                                                                                                                                            Increased crack control methods:

                                                            DISCHARGE RUNOFF                                                                           REINFORCEMENT NOTES:                                                                                                                 1. Use of low shrink concrete with a design shrinkage strain less than 650x10-6
                                                                                                                                                                                                                                                                                            2. Concrete should not be placed when maximum daily temperatures are expected to rise
                                                            CLEAR OF BUILDING                                                                          1.     All workmanship and materials shall be in accordance with the requirements of the relevant current Australian                        over 30°C or when site wind speeds are expected to exceed 15 knots.
                                                                                                                                                              Standard Codes (AS3600-2001 & AS2870-1996), Building By-Laws and the ordinances of the relevant Local                         Tiling:
     DRAINAGE LAYOUT FOR WET SITES                                                                                                                            Authority.                                                                                                                    1.     Where floor slabs are to be tiled, the following recommendations are made, in order to minimize the effects of
                                                                                                                                                       2.     Reinforcement is presented diagrammatically. It is not necessarily shown in true projection.                                         shrinkage:-
                                                                                                                                                       3.     Provide the Engineer with 48 hours notice of reinforcement being ready for inspection.                                               - Provision of SL92 slab mesh (or equivalent).
                                                                                                                                                       4.     No concrete is to be poured without the prior approval of the Engineer.                                                              - Placement of tiles should be delayed for as long as possible (preferably for at least 3 months)
                                                                                  ADDITIONAL SPOON
                                                                                                                                                       5.     Splices in reinforcement shall be made only in the positions shown. Where not specified, laps shall be in                            - Use of elastic tile adhesives and provision of flexible joints between tiles at regular centres and over slab
                                                                                  DRAIN REQUIRED IF
                                                                                                                                                              accordance with AS3600 and not less than: N12 - 400, N16 - 500, N20 - 650, N24 -800, N28 - 1100, N32 -                                 joints.
                                                                                  FACE LIKELY TO SCOUR
                                                                                                                                                              1400, N36 - 1700.
                                                                                                                                                       6.     Welding of reinforcement will not be permitted.
                                                                                                                                                       7.     Reinforcement must not be continuous through construction joints.
                                     PROPOSED
                                                                                                                                                       8.     Spacement of sufficient "stools" under main bottom and top reinforcement to allow adequate support in
                                     RESIDENCE
                                                                                                                                                              correct position during concreting (but not generally greater than 900mm spacings).
                                                                                                                                                       9.     Supply and lay steel fabric in flat sheets at splices. Provide 225 minimum overlap of transverse wires to all
                                                                                                                                                              edges of slab fabric laps. (ie two wires of each sheet overlapping plus 25mm)
                                                                           SPOON DRAIN                                                                 10.    Provide 'L' bars to all beam corners and intersections. 500 minimum laps.
          FFL OF SLAB TO BE SET AT                                                                                                                     11.    Reinforcement Symbols:
                                                                           (DRAINAGE PATH)
          SUITABLE HEIGHT TO SUIT                                                                                                                               N Grade 500 MPa Deformed Bar
          DRAINAGE CONDITIONS                                                                                                                                   SL Grade 500 MPa Deformed Slab Mesh
                                                                                                                                                                Y Grade 410 MPa Deformed Bar
                                                                                                                                                                S Grade 250 MPa Deformed Bar - Pool Construction
SURFACE DRAINS ALONG LINE OF SLOPES                                                                                                                             R Grade 250 MPa Plain Bar

                                                                                                                                                       FORMWORK
            GROUND                                                                                                                                     All form work design and support to be undertaken by the contractor.
            SLOPE                                                                                                                                      Refer Architectural specifications for finishes.
                                                                                                                                                       Unless noted otherwise all formed edges and corners of concrete members shall have 20mm chamfers.
                                                  DRAINAGE PATH                                                                                        Provide drip grooves to the perimeter of the soffits of all concrete members.
                                                    PROPOSED
                                                    RESIDENCE




DRAINAGE LAYOUT FOR CUT AND FILL SITES
          NOTE:
          ENSURE SITE DRAINAGE IS MAINTAINED DURING AND POST CONSTRUCTION




              CONTOUR
                                                                                                                                           PLAN DETAILS:                             PLAN AMENDMENTS:                                                                                                                                                                                                                                                         PLAN TITLE:

                                                                                                                                           Designed:                  JT
                                                                                                                                                                                    Rev      Date      Comment                                                      Altered       Checked   DRIVEWAY AND CARPORT RECTIFICATION
                                                                                                                                                                                                                                                                                                                     STRUCTURAL NOTES
                                                                                                                                           Drawn:
                                                                                                                                           Checked:
                                                                                                                                                                      JT
                                                                                                                                                                      BR
                                                                                                                                                                                     A      05/11/19   ISSUE FOR APPROVAL                                              JT           BR
                                                                                                                                                                                                                                                                                            83 NOOSA PARADE, NOOSA HEADS
                        A.B.N. 62 117 061 659
                       PO Box 474, Buddina 4575, Qld
                       6 Innovation Parkway, Kawana Waters 4575, Qld
                                                                                                                                           Datum:
                                                                                                                                           Date:
                                                                                                                                                                    AHD
                                                                                                                                                                NOV 2019                                                                                                                    ADVISORY SERVICES QLD                     FOR APPROVAL
                       Ph. (07) 5493 9777    Fax (07) 5493 6888                                                                                                                                                                                                                                This plan is Copyright. Other than for the purposes of and subject to the conditions prescribed under the Copyright Act, no part of it may in any form or by
                       Website: www.ContourCE.com.au                                                   Quality Assured
                                                                                                      International 3rd Party Accredited
                                                                                                                                                                                                                                                                                            any means be reproduced, stored in a retrieval system or transmitted without the prior written permission of Contour Consulting Engineers. The plan shall not
                                                                                                                                                                                                                                                                                            be used for construction without prior written approval.
                                                                                                                                                                                                                                                                                                                                                                                                                                                              PLAN No:   2155 01 S 110   REVISION:   A
Log in to download the original file

Plans 2155 01 S A FOR APPROVAL 06 11 2019.pdf · 2.4 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.