Appendix G - development permit 132007.2398.02
Attached to the e-mail MCU15/0111 & REC15/0031 Development Application G - Original Development Permit & Approved Plans Email 8 of 8.
132007.2398.02
81.1 Single Body Corporate water meter to measure the total water consumption
(including fire hose reels, but excluding fire hydrants and fire sprinkler systems)
81.2 Individual water meters to each tenement capable of being separately rated. These
meters must be supplied and installed in accordance with Councils requirements
81.3 All water meters must be located in an easily assessable location to facilitate
unhindered reading by Council and/or Council’s contracted water meter readers,
and not behind fences or locked gates
81.4 A fire service (fully testable single detector check with metered bypass), where
applicable, for flows to fire hydrants and fire sprinkler systems (excluding fire hose
reels)
82. Fire hydrants are to be provided throughout the development in accordance with Council
Engineering Design Standards and in accordance with Queensland Fire Service
Standards.
Service Easements
83. A registered easement shall be created over the zone of influence of the proposed sewer
mains within the subject site and on the adjoining property Lot 4 RP 215622. The
easements shall provide access to the Water Agency for future operations and
maintenance activities and restrict any construction over the sewer (Refer Standard
Drawings SEQ-SEW-1100-1 and SEQ-SEW1100-2 for typical easement installations).
Easements shall be provided along the full alignment of any gravity sewers located on
private property. Easements shall be centred over the pipe. The easement for gravity
sewers up to 3m deep and up to and including 300mm diameter shall be 3m wide.
Gravity mains greater than 300mm up to and including 600mm diameter and/or mains to
a depth of 5m, require a 6m wide easement. For mains that are deeper than 5m or
larger than 600mm diameter, the easement is to be 10m wide. Where a maintenance
structure is located on lot, a 1m wide easement along the side boundary from the front
boundary to the rear boundary for sewage purposes, is to be provided to facilitate
access to the structure.
A licensed surveyor shall accurately locate all sewer mains and determine the necessary
width of the easement, which shall be shown on any plans submitted for Operational
Works/Building Works approval. To this extent the surveyor shall certify that the sewer
and the zone of influence is wholly contained within the easement to be created. The
applicant must be pay all costs associated with the acquisition and the registration of
easement/s.
84. Where sewer easements are necessary, the Applicant’s Solicitor shall give Council’s
Solicitor an appropriate undertaking in writing that the Title Deed and the easement
documents will be lodged at the Land Titles Office and any additional Titles Office forms
or requisitions requiring the consent of Council will be attended to promptly. A duly
executed copy of the easement shall be submitted to Council for perusal prior to the use
commencing.
Power Supply
85. An underground electricity service shall be provided to the site if not already provided.
In this regard, an approved ENERGEX Electrical Design Consultant shall work in
conjunction with Council’s Manager - Works Support to prepare detailed designs of the
electrical proposal.
The detailed deigns shall then be submitted to ENERGEX for approval and a copy of
their approval submitted to Council in conjunction with a “Certificate of Electricity Supply
for Proposed Subdivisions” (prepared by an approved ENERGEX Electrical Design
Consultant) prior to Council endorsing the Plan of Survey.
Page 10 of 20