CSI14096#2LakewayDriveCooroibah-Rev1 AES Final
AES - ALL WASTE WATER MANAGEMENT FIELD DATA AND LAND
APPLICATION DESIGN – MOUNDED ABOVE GROUND
Client: Dean White
Job No: 14096
Site Address: # 2 Lakeway Drive, Cooroibah
Council: Noosa Shire
Field Work By: BAC
Date of Field Work: 09/03/21
Reported By: BAC
Report Date: 11/03/21, 22/02/22
Test method: AS1547-2012
This Report has been compiled by:
Brian Croke, Assoc Dip Civil Engineering, QBCC Site Classifiers Lic. 1064963, AES Cert.QLD00202
On behalf of Creabian Pty Ltd atf The Croke Family Trust abn 17108178312 trading as CSI:Soil Testing , QBCC Site Classifiers Lic.1064964
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
Large file: the download may take up to a minute.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 19 pages
Page 2
DOMESTIC WASTE WATER LAND APPLICATION DESIGN
Designer Name: CSI Soil Testing
QBCC Licence Number: QBCC Site Classifiers Lic No. 1064963
AES Certificate Number: 202
1. Site conditions:
The area is grassed with scattered trees. The general area slopes at approximately 3-10%.
2. Soil Assessment:
The bore logs of the site indicate that the soil profile consists of a dark grey CLAY over grey CLAY over yellow brown
mottled light grey CLAY over red brown CLAY. From on-site visual examination a textural classification of Category 5
has been adopted.
3. Calculation of Disposal Area using the AES Design Calculator.
Direct Natural Ground: AES pipes bedded in coarse washed sand
Excavated Bed Dimensions: 9.6 long x 12.5m wide, (from AES Infiltration Foot Print Area minimum footprint) 900mm
deep (depth is AES system sand depth from AES dimensions table + 150mm backfill). Total footprint area = 120 m2
If standard fixtures used:
CAT 5 SOIL
TOWN WATER
8 PEOPLE
150 litres/day/person (Reticulated/Bore)
Q (day) = 8x150 = 1200 litres/day
DLR = 10 mm/day
REQUIRED BED = 9.6 long x 12.5m wide, 900mm deep AES beds.
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 3
4. Minimum setback distances (from Queensland Plumbing and Waster Code March 2019)
VERTICAL SEPARATION Advanced
Unsaturated soil depth to a permanent water table or 0.3m
impermeable rock layer
HORIZONTAL SEPARATION - Distance from the edge
of the bed/trench to the nearest point of the feature
Top of bank of permanent or intermittent water course or lake, 10m
bay or estuary; or
Top water level of a surface water source used for agriculture,
aquaculture or stock purposes or;
Bore or a dam
Property boundaries, pedestrian paths, footings of buildings, 2m
recreation areas, retaining wall footings - up slope or level with
the land application area
Property boundaries, pedestrian paths, footings of buildings, 4m
recreation areas, retaining wall footings - down slope of the land
application area
In ground swimming pools 6m
In ground water tanks 6m
Embankment cut/fill - down slope of the land application area 6m
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 4
5. Land Application Method and Area:
• The bed shall be mounded and cut into natural ground only enough to create a toe in natural ground
• It is proposed that disposal be by 300mm AES pipes layed in a bed of washed coarse sand.
• Installation to be to AES Design and Installation standards by a suitably experienced, qualified and licenced
plumber/drainer.
• The bed will be a minimum of 9.6 long x 2.7m wide with an additional 9.8m system extension due to high category
soils. The AES bed will be 900mm deep which will include 300mm system sand below the pipes, 150mm system
sand above the pipes and 150mm topsoil above that sand. The system sand extension shall be downhill of the main
bed and be a minimum 150mm deep by the length of the bed by 9.8m wide and located at the bottom of the bed
depth.
• An inspection port is required to be installed at the furthest point from the influent to AES pipe.
• Plan to excavate in dry times if possible.
• Strip topsoils for use later as topsoil over AES system.
• Ensure that the natural soil is not compacted or smoothed over while excavating and installing and that clay soils
are scarified 200mm deep. Gypsum may be added to clay.
• Diversion drains/mounds will be required to intercept any surface waters draining onto and from the disposal area.
• A Primary Septic system complying to AS1546.1 2008, with a pump well, is to be used.
• The Land Application area shall be grassed. Native shrubs (with non-intrusive roots suitable for the local area and
for being adjacent to effluent disposal areas – see horticulturist for advice) should be planted at the downhill edge of
the land application area. Access for future maintenance should be considered.
• The land application area shall be in the vicinity of Test holes (TH).
• The area shall maintain a distance of 10m away from the watercourses.
• This report has been compiled using information supplied by the owner i.e. 5 (five) equivalent bedrooms. If
information has changed this report will become void and may not be used and will need to be amended (further
charges will apply).
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 5
6. Waste water system Installation:
• Installation shall be carried out by suitably qualified persons (licensed Drainer) following the AES
suppliers/manufacturers guidelines/specifications and any relevant standards/ Local Authority conditions and must
at all times adhere to industry best practice. Installation must comply with AS/NZS 3500, Plumbing and Drainage
Act, AS/NZS 1547 and the On-site sewerage code. Other Federal, State and local laws or referenced standards
may be relevant.
• The use of water saving devices is recommended.
• The location of the septic tank shall meet council requirements and shall be downhill from the building and above
the flood and storm water flows.
• All Council approvals must be obtained prior to commencement of work.
• Design detail, logistics and proper functioning of the plumbing works is the responsibility of the installation
plumber/drainers.
• The designated land application area shall be clearly delineated with vegetation or other type of border.
• At least two (2) warning signs shall be erected on the boundaries of the land application area eg. ‘WARNING-KEEP
OUT- EFFLUENT’
• Prior to engagement, the installation will be required to be inspected. As registered Site and Soil
Evaluators/Designers we can issue you with a site inspection certificate to acknowledge installation is according to
our design (further charges apply). The installer must be a licensed Drainer and must certify the installation.
Please ensure that the building design engineer sees this report so they can be aware of the introduction of water to the
soils in the land application area, in case it affects the footing design.
7. Maintenance requirements:
• The owner/tenant shall comply with the manufacturer and suppliers, maintenance and best practice requirements
(supplied at installation) to ensure the proper functioning of the system. These procedures should be passed onto
subsequent owners/tenants.
• The owner should ensure that the system is inspected for performance by a suitably qualified service technician
according to system and/or Council requirements.
• The designated land application area shall be kept clear of all humans, animals and traffic.
• The use of strong caustic, alkalis, oils, acids, bleaches, disinfectants or chemical detergents may kill the essential
bacteria, and harm the natural break down process both in the tank and in the pipes.
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 6
8. AES System Pipe Layout Details (Refer to AES Design Installation Manual):
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 7
SCALE
10
30
ADVANCED ENVIRO - SEPTIC
OWNER / ENGAGED BY
LOT AND PLAN
AMENDMENTS
ISSUE DATE SUBJECT AUTHORISED
A 24/01/2018 REVISION A R.CRISP
CHANKAR ENVIRONMENTAL PTY LTD
T/A
QBCC LICENCE NUMBER
150 238 31
Phone: +61 7 5474 4055
Fax: +61 7 5335 1691
Email : [email protected]
www.enviro-septic.com.au
T.SHERPA
DESIGNER DATE
ADVANCED ENVIRO-SEPTIC
PIPE LAYOUT DETAILS FOR
FIVE ROWS
THREE PIPES SYSTEM
SCALE:
1:60 (A4)
PROJECT JOB NUMBER REVISION SHEET NO
AES - CHK A SL1
Page 8
9. AES Section View
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
[OCR of page images]
CSI ‘sou TESTING
What are you Building on ?
9. AES Section View
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/I atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 9
CSI sou resrne What are you Building on ? Low vent Inspection point Top soil min cover of 150mm System sand crowned to shed water Excavated backfill Import if there is insufficient to create backfill mound Provide diversion mound Inspection point Inlet_from septic tank tt —_— Natural ground line (Minimal Fall) Ripped basal crea" | parallel to AES pipes add gypsum. Length as specified in report AES CROSS-SECTION DETAILS FOR SITE BEDS WITH MOUNDED SOIL COVER on area deta Land applicat CSI: 14096 #2 Lakeway Drive, Cooroibah A4 Section Issue C Creabian p/l atf...abn 17108178312 ...PO Box 1128, BUDDINA Q 4575 1300 762 240, 0418 708 636 / 07 5493 5966. [email protected] www.csisoiltesting.com.au
Page 10
10. AES - Sand Coverage Minimums
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
[OCR of page images]
What are you Building on ?
C CSI sou esr
10. AES - Sand Coverage Minimums
150mm
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/I atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 11
11. Land application area diagram
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 12
CSI sou resrne —
What are you Building on? and manufacturer's specification for specific
details.
NOTE!!
THE INSTALLER OF THE AES SYSTEM MUST
BE CERTIFIED, TRAINED & COMPETENT AT
AES INSTALLATIONS.
AES SYSTEM MUST RUN PARALEL WITH THE
CONTOUR OF THE LAND. INSTALLER TO MAKE
ADJUSTMENTS IN LOCATION TO ENSURE
COMPLIANCE WITH THIS REQUIREMENT & THE
AES INSTALLATION MANUAL & AES SITE
INSTRUCTIONS AVAILABLE FROM THEIR
WEBSITE. BASE OF SYSTEM IS TO BE
FLAT/LEVEL.
IF DOUBT EXISTS CONTACT AES DIRECTLY
BEFORE DOING WORK.
Q100 flood level 29
Proposed NEW
with pump well
TANK — RL 3.5
<=). RESIDENCE
FFL 5.00 |;
on area diagram
cat
Land app
30 20 10 0
PO LSU
. . Scale 1:1000
CSI: 14096 #2 Lakeway Drive, Cooroibah A4 Plan Issue B
Creabian p/l atf...abn 17108178312 ...PO Box 1128, BUDDINA Q 4575
1300 762 240, 0418 708 636 / 07 5493 5966. [email protected] www.csisoiltesting.com.au
Page 13
12. AES Calculator
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/l atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
[OCR of page images]
CSI ‘sou TESTING
What are you Building on ?
12. AES Calculator
CSI: 14096#2LakewayDriveCooroibah-Rev1
Creabian p/I atf....abn 17108178312 ....PO Box 1128, BUDDINA Q 4575
1300 762 240, 0439 568 937 [email protected] www.csisoiltesting.com.au
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20