SR811902069 -Pressure & Flow Response - Lot 2 RP87781 - 165 Gympie Rd Noosaville - Kingston Developments · MCU18/0078

Attached to the e-mail Response_ SR811902069 -Pressure & Flow Response - Lot 2 RP87781 - 165 Gympie Rd Noosaville - Kingston Developments (A5124802).eml, inside MCU18/0078 and OPW18/0117 Response to information Request.msg.

of 3

Text shows just the words. Original shows the document exactly as it was published.

                                                                                                           Mailing Address:
                                                                                         PO Box 953, Caboolture QLD 4510
                                                                                                 Customer Service Centres:
                                                                                       33 King Street, Caboolture QLD 4510
                                                                                 6-10 Maud Street, Maroochydore QLD 4558
                                                                                              1300 0 UNITY (1300 086 489)
                                                                                                      www.unitywater.com
                                                                                                           ABN: 89 791 717 472




         Our ref: A5124802
         PF/SR811902069/2018




         Mr Brent Threadgold
         Kingston Developments
         PO Box 915
         Cooroy QLD 4563

         Email: [email protected]


         12 June 2018



         Dear Mr Threadgold

         Network Pressure and Flow Data – Request for information – Lot 2 RP87781, situated
         at 165 Gympie Road Noosaville

         I refer to your application received by Unitywater on 31 May 2018 in which you request
         pressure and flow data for the above property.

         Minimum Standard of Service
         In accordance with Queensland Government Guidelines Unitywater designs, constructs,
         operates and maintains its water supply network to provide the following minimum standard
         of service a 2/3 of the calculated maximum hour demand on the peak day:

         Table 1 – Minimum Standard of Service
           Type of Use                                  Flow Available from         Residual Head in Water
                                                     Unitywater’s Water Main        Main Servicing the Use
                                                    for Fire Fighting Purposes            (metres)
                                                           (litres/second)
           Residential including multi –
           storey residential dwellings 15                                        12
           of less than 3 storey
           Commercial that is ancillary
                                        15                                        12
           to residential use
           Multi-storey       residential
                                          30                                      12
           greater than 3 storey
           Commercial and or Industrial 30                                        12


                                                                                                                  Page 1 of 3
Unitywater is a statutory authority that provides water and sewerage                            Unitywater has certification to
                                                                                                OH&S ISO 4801:2001 Reg No 4260
services for the Moreton Bay, Sunshine Coast and Noosa Council areas.                           Environmental ISO 14001:2004 Reg No 4259
                                                                                                Quality Systems ISO 9001:2008 Reg No 4258
Full text of the other 2 pages

Page 2

         Unitywater does not guarantee that fire fighting flow will be available at all times on the grounds
         that components of Unitywater’s water supply infrastructure may be shut down temporarily for
         planned maintenance or to repair bursts or damage caused by others.

         The current type of use for this property is attached housing. Hence, in accordance with Table
         1 above, the Minimum Standard of Service that applies is 15 litres/second at 12 m residual
         head.

         Current Dynamic Model Data
         Unitywater’s current dynamic water supply model indicates the following under a demand
         condition of 2/3 of the estimated maximum hour demand on the peak day in Year 2031.

         Table 2 – Estimated Available Flow and Pressure to 2031
                                                                           Water Main      Estimated RL at
            Assessment Node                 Node Location
                                                                          Diameter (mm)   Assessment Node
                   Noo1923                 Corner of Gympie                     300                1.61
                                          Terrace and Robert
                                                Street
                 Background                    Static Head                  Fire Flow      Residual Head
                    Demand                         (m)                       Demand          (m)
               (litres/second)                                          (litres/second)
                      0.35                          56.8                        15                 55.2

         Unitywater reserves the right, at any time, to change the operating pressures within the water
         supply network, but not below the Minimum Standard of Service stated in Table 1.

         Unitywater accepts no liability whatsoever for changes in the operating pressure of this water
         supply network and the consequent impacts on any fire suppression system within the subject
         property. It shall be the property owner’s responsibility to ensure that any fire suppression
         system operating on the property complies with the relevant requirement of the Building Code
         of Australia and that this system is regularly tested for compliance with the relevant standards.
         Any upgrade of the fire suppression system required due to changes in the operating pressure
         of the water supply network will be the property owner’s responsibility.

         Suggested Approach to Design of Fire Suppression System
         It is suggested that the owner of the property consult with a qualified and suitably experienced
         hydraulic designer to consider the risks associated with designing a fire suppression system
         for the subject property based upon the output from Unitywater’s current dynamic water supply
         model. Unitywater may alter the operating pressure of the network at any time.

         It is suggested that this risk should be balanced against the cost of designing and installing a
         fire suppression system that would provide the desired level of performance when supplied
         with water from Unitywater’s mains at the Minimum Standard of Service stated in Table 1.
                                                                                                             Page 2 of 3
Unitywater is a statutory authority that provides water and sewerage                       Unitywater has certification to
                                                                                           OH&S ISO 4801:2001 Reg No 4260
services for the Moreton Bay, Sunshine Coast and Noosa Council areas.                      Environmental ISO 14001:2004 Reg No 4259
                                                                                           Quality Systems ISO 9001:2008 Reg No 4258

Page 3

         It may be beneficial to consider providing space and conduits on the subject property that
         could be utilised for installation of storage tanks and or pumping equipment and associated
         electrical equipment in the instance that an upgrade of the fire suppression system was
         necessary in the future.

         Further Information
         Should you require clarification of the foregoing please contact Unitywater on 1300 086 489
         during business hours or by email to [email protected] sincerely




         Michael Lukin
         Network Planning Manager




                                                                                                   Page 3 of 3
Unitywater is a statutory authority that provides water and sewerage             Unitywater has certification to
                                                                                 OH&S ISO 4801:2001 Reg No 4260
services for the Moreton Bay, Sunshine Coast and Noosa Council areas.            Environmental ISO 14001:2004 Reg No 4259
                                                                                 Quality Systems ISO 9001:2008 Reg No 4258

Used in these records

About this file

File size
133 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

SR811902069 -Pressure & Flow Response - Lot 2 RP87781 - 165 Gympie Rd Noosaville - Kingston Developments.pdf · 133 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.