Unitywater does not guarantee that fire fighting flow will be available at all times on the grounds
that components of Unitywater’s water supply infrastructure may be shut down temporarily for
planned maintenance or to repair bursts or damage caused by others.
The current type of use for this property is attached housing. Hence, in accordance with Table
1 above, the Minimum Standard of Service that applies is 15 litres/second at 12 m residual
head.
Current Dynamic Model Data
Unitywater’s current dynamic water supply model indicates the following under a demand
condition of 2/3 of the estimated maximum hour demand on the peak day in Year 2031.
Table 2 – Estimated Available Flow and Pressure to 2031
Water Main Estimated RL at
Assessment Node Node Location
Diameter (mm) Assessment Node
Noo1923 Corner of Gympie 300 1.61
Terrace and Robert
Street
Background Static Head Fire Flow Residual Head
Demand (m) Demand (m)
(litres/second) (litres/second)
0.35 56.8 15 55.2
Unitywater reserves the right, at any time, to change the operating pressures within the water
supply network, but not below the Minimum Standard of Service stated in Table 1.
Unitywater accepts no liability whatsoever for changes in the operating pressure of this water
supply network and the consequent impacts on any fire suppression system within the subject
property. It shall be the property owner’s responsibility to ensure that any fire suppression
system operating on the property complies with the relevant requirement of the Building Code
of Australia and that this system is regularly tested for compliance with the relevant standards.
Any upgrade of the fire suppression system required due to changes in the operating pressure
of the water supply network will be the property owner’s responsibility.
Suggested Approach to Design of Fire Suppression System
It is suggested that the owner of the property consult with a qualified and suitably experienced
hydraulic designer to consider the risks associated with designing a fire suppression system
for the subject property based upon the output from Unitywater’s current dynamic water supply
model. Unitywater may alter the operating pressure of the network at any time.
It is suggested that this risk should be balanced against the cost of designing and installing a
fire suppression system that would provide the desired level of performance when supplied
with water from Unitywater’s mains at the Minimum Standard of Service stated in Table 1.
Page 2 of 3
Unitywater is a statutory authority that provides water and sewerage Unitywater has certification to
OH&S ISO 4801:2001 Reg No 4260
services for the Moreton Bay, Sunshine Coast and Noosa Council areas. Environmental ISO 14001:2004 Reg No 4259
Quality Systems ISO 9001:2008 Reg No 4258
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
SR811902069 -Pressure & Flow Response - Lot 2 RP87781 - 165 Gympie Rd Noosaville - Kingston Developments.pdfRelated documentApplication case desk ↗
About this file
- File size
- 133 KB (small file)
- File type
No other editions are linked here.