Appendix H - Slope Stability Assessment
Brett Hage 22328-001-Rev0
14 September 2022
Table 3: Setback distances for on-site sewerage facilities (Protection of surface and groundwater)
Separation Distance
Site Feature
Advanced Secondary Secondary Effluent
Effluent
Surface Waters:
Top of bank of permanent or intermittent water course, lake,
bay or estuary;
Top water level of a surface water source used for agriculture, 10 m 30 m
aquaculture or stock purposes;
Open stormwater drainage channel or drain;
Bore or a dam.
Unsaturated soil depth to a permanent water table (vertically) 0.3 m 0.6 m
Note: Distances measured from the edge of the irrigated wetted area to any point of the feature.
Unsaturated soil depths of 0.6 m (i.e. depth to rock or wet soil) and 0.3 m are recommended for Secondary
and Advanced Secondary effluent, respectively. Boreholes indicate adequate unsaturated soil depths are
available.
Individual site layout shall be decided at building stage, in conjunction with a design provided by a NC
registered evaluator.
5.3.3 System Construction
Construction of wastewater land application areas must be carried out in accordance with Appendix M of
AS1547:2012 and NC requirements. In order to prevent any adverse impacts on the water quality from
effluent disposal, the elements given below shall be implemented:
Shallow subsurface drip systems must be installed at 100 mm to 150 mm depth into 150 mm to
250 mm of good quality sandy topsoil, in grassed of other suitably vegetated areas. Any sandy
topsoil material won from site works may be used to supplement the soil within the respective
disposal fields or alternatively shall be imported to the site.
Receiving native soils will be prepared by undertaking deep ripping / shallow cultivation combined
with the addition of organic matter (10 kg/m² raw mulch) and gypsum (1 kg/m²) to ‘break up’ any
relatively hard clay subsoils and improve overall drainage characteristics.
Shallow subsurface irrigation lines will run parallel to slope contours. To evenly distribute
wastewater throughout the irrigation areas, pressure equalisation systems (i.e. pressure
compensating drip emitters) should be installed.
Surface diversion drainage shall be installed on the up-slope sides of the land application areas to
divert surface water and shallow subsurface seepage flows away. Such drainage should penetrate
to a minimum depth of 0.3 m BGL.
A low earthen bund shall be constructed, down slope of the effluent disposal areas up to 0.3 m high
to retain run-off and promote sheet flow.
Plant and maintain grasses, reeds and/or small shrubs within the land application areas. Preference
should be given to native plant species endemic to the local area, which are suitable for mostly wet
soils and are tolerant of nutrient loads (e.g. native riparian vegetation)
Erect signage at the boundaries of the area in at least two places in accordance with Council
requirements to warn people regarding the presence of wastewater pipes (e.g. “Sewage Effluent
Pipework Installed Below – DO NOT DIG” or “Recycled Water – Avoid Contact - DO NOT DRINK”).
Erect barriers where necessary to restrict access to public which may interfere or damage the
irrigation system.