Bushfire Hazard Statement
Attached to the e-mail Further information (Plans, Fauna Flora Ass, Carparking, Road design, traffic mgmt, bushfire, Plans) - MCU18/0009.
[7]
Table 2 – Fireline Intensity Model data for Subject Site and Waterway Corridor
Characteristic Input/output value
Vegetation hazard class 22.1 Melaleuca open forests on seasonally inundated lowland coastal
swamps1
Potential fuel load (t/ha) 28.42
FFDI 473
Slope (degrees) 2
Potential fireline intensity (kW/m) 26,981
Potential Bushfire Hazard Class High
1 – the VHC 22.1-Melaleuca open forests on seasonally inundated lowland coastal swamps was used because
2 – the Potential fuel load is attributed with a potential fuel load by the State Government as part of the Leonard et. al.
(2014) methodology.
3 – the FFDI for the area is determined by the State Government as part of the Leonard et. al. (2014) methodology.
We also acknowledge that while the Lomandra Place Bushland Reserve is an area of low bushfire
hazard, it may become involved in a bushfire event and as such needs to achieve a separation from that
vegetation necessary to achieve the radiant heat flux of 19kW/m2.
Table 3 provides the outputs for potential setbacks from the retained vegetation. We acknowledge the
age and vulnerability of the residents using the proposed development and recommend that the setback
should achieve a lower radiant heat level than necessary for the residents.
Table 3 – Minimum Distance Calculations
186 Cooroy Noosa Road, Tewantin - Minimum Distance Calculator - AS3959-2009 (Method 2)
Inputs Outputs
Fire Danger Index 42 Rate of spread 0.81 km/h
Vegetation classification Woodland Flame length 8.62 m
Surface fuel load 15 t/ha Flame angle 54 °, 65 °, 74 ° & 79 °
Overall fuel load 28 t/ha Elevation of receiver 3.24 m, 3.57 m, 3.65 m &
3.51 m
Vegetation height n/a Fire intensity 11,718 kW/m
Effective slope 1° Transmissivity 0.863, 0.849, 0.827 & 0.803
Site slope 2° Viewfactor 0.6056, 0.447, 0.3007 &
0.2043
Flame width 100 m Minimum distance to < 40 kW/m² 7m
Windspeed 35 km/h Minimum distance to < 29 kW/m² 9.5 m
Heat of combustion 18,600 kJ/kg Minimum distance to < 19 kW/m² 14.1 m
Flame temperature 1,090 K Minimum distance to < 12.5 kW/m² 20.5 m
Rate of Spread - Mcarthur, 1973 & Noble et al., 1980
Flame length - NSW Rural Fire Service, 2001 & Noble et al., 1980
Elevation of receiver - Douglas & Tan, 2005
Flame angle - Douglas & Tan, 2005
Radiant heat flux - Drysdale, 1999, Sullivan et al., 2003, Douglas & Tan, 2005
Emergency Management plan
Noosa Care – Carramar has two Emergency Response documents which informs and guide the management’s
response in the advent of an emergency within and around the Carrama Care facility and which includes a
bushfire event. These documents are: -
1. Natural Disaster Response Plan (Carramar/Kabara WHS Coordinator, June 2016), and