                                                                                                                 Bushfire Hazard Assessment and Management Plan




Performance Outcomes                   Acceptable Outcomes                                           Compliance Assessment

                                                                                                     adjoining the dwelling is wide enough and of a suitable
                                                                                                     grade to allow for an emergency vehicle (rural fire
                                                                                                     appliance) to stop and turn around safely.

Lot design

PO7   Lot design and building siting   AO7   Each                 residential                 lot:   Not applicable – the development proposal is not for a
      minimises   bushfire   hazard                                                                  subdivision
      risk to people and property.
                                                a. includes a building envelope, identified
                                                     on a plan of subdivision;

                                                b. is of sufficient size and shape to allow
                                                     for efficient emergency access to
                                                     buildings for fire fighting appliances (e.g.
                                                     by avoiding battle-axe/hatchet lots and
                                                     long narrow lots with long access
                                                     driveways to buildings);

                                                c.   where more than 2500m², achieves
                                                     setbacks from hazardous vegetation in
                                                     line with Bushfire Attack Level 29
                                                     requirements as per AS3959; and

                                                d. is designed so that buildings and
                                                     structures are sited in locations of
                                                     lowest hazard within the lot and
                                                     elements of the development least
                                                     susceptible to fire are closest to the fire
                                                     hazard.




                                                                                                           PR22116_BHAMP_178 Davis Rd, Cootharaba      Page 35
Log in to download the original file

RFI - Bushfire Hazard Assessment and Management Plan.pdf · 8.7 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.