Figure 4.1: Modelled Downwash Structures
4.8 Summary of Modelling Assumptions
As noted above, several assumptions were adopted for the purposes of estimating emissions from
the service station. Overall, these assumptions represent a conservative approach and are consistent
with recommendations made by overseas regulatory authorities. The assumptions adopted are as
follows:
⚫ all fuel handling is considered to be petrol providing a conservative emissions generation
procedure (i.e., petrol has a higher volatility than diesel);
⚫ a minimum efflux velocity was adopted for the vent stack emissions of 0.1 m.s -1. This allows
modelling of these as point sources;
⚫ to ensure worst case meteorological conditions are considered, it is assumed that bulk tanker
deliveries occur continuously throughout the year (day and night);
⚫ for tank filling, a fuel delivery of 40,000 L/hour for the E10 tank has been considered;
⚫ all fugitive emissions were assumed to occur in the working area of the service station (i.e. a
rectangular volume source located around the petrol bowsers) below the roofed area;
⚫ an average filling and transaction time of 4 minutes per vehicle;
⚫ an average 40 L of fuel per vehicle refuelling.
Page 22 of 30
Synergy Property Partners Pty Ltd- Air Quality Assessment - Proposed Service Station, 123 Eumundi-Noosa Road, Noosaville
/Network/Projects/4484/Reporting/4484 Report03.odt
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalSearchable page text hides email addresses. Original files are unchanged and may show email addresses.