every 6 months, and this will give a quick and obvious indication of the performance of the
GPT's. If there is evidence of significant gross pollutants and sediment accumulating at the
bioretention cell inlets then this would be an indication that the GPT's may not be
performing adequately. Records should be kept of visual assessment and corresponding
photographs taken.
5.2 General Performance of Bioretention Basin
Visual assessments of the basin should be carried out during routine maintenance, but not
less than every 6 months. Figure 1 below gives guidance on indications of problems, their
I
likely causes and rectification measures.
Parameter Indicator of Possible Cause Possible Management Action(s)
I
Plant health Too much System undersized Replace filter media with that of a
water higher infiltration capacity
Poor infiltration capacity (water As above
I Too little
water
lo¢ai ng)
System oversized (eg. plants
further from inlet are drier)
Consider Installing a choke on outlet
OR
Replant with dry tolerant plants
Inlet levels wrong (system is Reset inlet levels
bypassing too early)
Poor flow Excessive inflow velocities (at • Install/augment energy
control inlet) dissipation device
• Relocate inlet
Inadequate provision for bypass • Install/augment energy
of high flows (damage dissipation device
throughout system) Reconfigure inlet to prevent high
flows entering system
• Relocate inlet
Erosion Poor flow Excessive inflow velocities • Install/augment energy
control dissipation device
I
• Relocate inlet
Inadequate provision for bypass Reconfigure Inlet to prevent high
of high flows (damage flows entering system
throughout system)
Build-up of Clogging Excessive loads of sediment • Install pre-treatment device (see
sediment on Chapter 3 for ideas)
filter surface • Scarify the filter surface
between plants and/or densely
System undersized
vegetate to break up the
Inadequate pre-treatment clogging layer
Figure 12
5.2.1 Additional advice on filter media performance
2 FAWB Stormwater Biofiltration Systems Adoption Guidelines Table 6.
I 12
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Request to Change Current ApplicationRelated documentApplication case desk ↗
About this file
- File size
- 10.6 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.