24191 S3100646 RevB

of 2

Page text shows just the words. Original shows the document exactly as it was published.

                                           Lot 362




                                                                                                                                                                             Lot 361




                                                                                                                                                                                                             C




·
·
·
·
·
·




                                                                                                                                203                       AS/NZS 3000:2018

                                                                              3.11.5      Spacing from other underground services

                                                                              All underground wiring systems shall be spacing not less than 100 mm from
                                                                              other underground services.

                                                                              Wiring systems shall be suitably marked with warning tape in accordance
    WHILE IT IS STRIVED TO ENSURE ACCURACY OF                                 with Clause 3.11.4.5 and maintain a separation from telecommunications,
    INFORMATION LISTED, ANY SITE SURVEY FIELD WORK IS                         gas and water services in accordance with Table 3.7.
    SOLELY BASED OFF ACCURACY OF ANY INFORMATION
    PROVIDED AT THE TIME, IT IS A VISUAL INSPECTION &                         Further requirements for the separation of telecommunications, gas and
    ASSESSMENT OF ABOVE GROUND NETWORK ASSETS                                 water systems from low voltage wiring systems are provided in
    ONLY WHICH EXCLUDES ANY ELECTRICAL TESTING,                               Clause 3.9.8.4.
    EXCAVATION FOR THE VALIDATION OF NETWORK                                                                               TABLE 3.7
    INTEGRITY.
                                                                                         MINIMUM SEPARATION OF UNDERGROUND SERVICES
                                                                                                                Minimum separation to low       Minimum separation
                                                                                                                 voltage electrical service         of conductive
                                                                                                               identified in accordance with      enclosures to low
                                                                                  Type of service            Clause 3.11.4.5 and mechanically     voltage electrical
                                                                                                                        protected (1)           earthing electrode (1)
                                                                                                                               mm                        mm
                                                                              Water service not
                                                                              greater than DN65 (2)                            100                       500

                                                                              Water service greater
                                                                              than DN65 (2)                                    300                       500

                                                                              Sanitary drainage                                100                       500
                                                                              Stormwater drainage                              100                       600
                                                                              Gas                                              100                       500
                                                                              Telecommunications                               100

                                                                             NOTES:
                                                                             1 Authorities, such as water and as suppliers and electricity distributors, may
                                                                               require their services to be spaced at a greater distance from underground wiring
                                                                               systems. Also see Figure 3.10.
                                                                             2 DN = internal diameter of pipe.




                                                     24191
                                                                                                                                                                                       Parth Patel
                                                                                                                                                                                       RPEQ 21483
                                                                                                                                                                                       2025.02.05 15:08:07
                                                                                                                                                                                       +10'00'




    ABN 12 115 160 748
    Phone (07) 5479 1368
    E-mail: [email protected]         PO Box 807
    Website: www.millwell.com.au    Maroochydore QLD 4558    ©   This design and drawing is copyright and is not to be used or reproduced
                                                                 wholly or in part without written permission of Millwell Services Pty Ltd
Log in to download the original file

24191 S3100646 RevB.pdf · 792 KB (small file)

Full text of the other 1 page

Page 2

                                                                                                                                        PROPOSED COMMISSIONING PLAN
                                                                                                                                         Proposed only and subjected to change by Energex.

                                                                                                                                                        LV SWITCHING SHEET:

                                                                                                                                    1.   INSTALL LV UG NETWORK AS PROPOSED, DO NOT
                                                                                                                                         CONNECT NEW 16 LV UG TO 120 LV UG AT U5804 (STN 1)
                                                                                                                                    2.   OPEN SC21301-A/FS1 FUSE SWITCH AT SC21301
                                                                                                                                    3.   CONNECT NEW 16 LV UG TO 120 LV UG AT U5804 (STN 1)
                                                                                                                                    4.   CLOSE SC21301-A/FS1 FUSE SWITCH AT SC21301
                                                                                                                                    5.   TEST AND COMMISSION
                                                                                                                                    6.   CONDUCT POST COMMISSIONING CHECKS


                                                                                                                                              Where interruptions are proposed, customers
                                                                                                                                              shall be notified as per Energex requirements.




                                               24191
                                                                                                                                                                                               Parth Patel
                                                                                                                                                                                               RPEQ 21483
                                                                                                                                                                                               2025.02.05 15:08:07
                                                                                                                                                                                               +10'00'




ABN 12 115 160 748
Phone (07) 5479 1368
E-mail: [email protected]         PO Box 807
Website: www.millwell.com.au    Maroochydore QLD 4558   ©   This design and drawing is copyright and is not to be used or reproduced
                                                            wholly or in part without written permission of Millwell Services Pty Ltd