PROPOSED COMMISSIONING PLAN
Proposed only and subjected to change by Energex.
LV SWITCHING SHEET:
1. INSTALL LV UG NETWORK AS PROPOSED, DO NOT
CONNECT NEW 16 LV UG TO 120 LV UG AT U5804 (STN 1)
2. OPEN SC21301-A/FS1 FUSE SWITCH AT SC21301
3. CONNECT NEW 16 LV UG TO 120 LV UG AT U5804 (STN 1)
4. CLOSE SC21301-A/FS1 FUSE SWITCH AT SC21301
5. TEST AND COMMISSION
6. CONDUCT POST COMMISSIONING CHECKS
Where interruptions are proposed, customers
shall be notified as per Energex requirements.