33522 MCU 18-0001 information response cover letter · MCU18/0001

Attached to the e-mail Response to information request - MCU18/0001.

of 4

Text shows just the words. Original shows the document exactly as it was published.

The proposal includes relocating the existing sewer manhole and mains but the applicant has not provided
approval for the asset owner.
Information Required
     4.   Provide written confirmation from the asset owner (Unitywater) for the proposed relocation of the
          sewer manhole and mains.
Information Provided
         Attached Unity Water Service Advice Notice.




Issue - Stormwater
The proposal includes significant changes to the existing stormwater drainage system for the site constructed
as part of the prior reconfiguration of a lot (REC14/0007 and OPW14/0253) and encroaches into the existing
easement. The submitted material does not include sufficient information to demonstrate that the
development of the site will not adversely impact upon the adjoining properties.


Information Required
     5.   Provide a preliminary stormwater management plan for the proposed development. The plan must
          be prepared by a suitably qualified person (RPEQ or similar) and include but not be limited to:
a.        collection and discharge/infiltration of stormwater runoff from the proposed development (roof and
          hardstand areas). Please note that the system must be a gravity system and pumps are not acceptable;
b.        sufficient detail to demonstrate that the existing infiltration system has the capacity to cater for the
          runoff from the proposed development;
c.        demonstrate that the existing stormwater easement is no longer required in either part or whole.
Information Provided
Attached BAX Engineering report 018-001 dated 26.6.2018


Issue - Overlay
The site is mapped as being in a Landslide Hazard Area and the proposed development includes significant
earthworks in close proximity to the boundaries. The submitted material does not in a geotechnical
investigation and/or report.


Information Required
6. Provide a site specific geotechnical investigation and/or report that is prepared by a suitably qualified
     person (RPEQ). The report must include recommendations for the works to ensure the stability of the
     subject development and the adjoining properties in the long term.


Information Provided
Attached SCG Engineering report 28050(S).




Issue – Building Height and cut and fill

Used in these records

About this file

File size
213 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

33522 MCU 18-0001 information response cover letter.pdf · 213 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.