Original source · versioned page text
Minor Change Existing Approval 132002.220285.I (As Published)
10 pm - 7 am Background noise level plus 3 dB (A)
Period
Noise Level at a Commercial Place measured as the Adjusted
Maximum Sound Pressure Level
LAmax adj, T
7 am - 10pm Background noise level plus 10 db(A)
10 pm - 7 am Background noise level plus 8 db (A)
Air
2. Where Petroleum products are to be transferred from a delivery vehicle to an underground
fuel storage tank, and where an installation receives collectively more than 520 kilolitres of
petroleum product during a twelve (12) month period, then the underground fuel tank and
delivery vehicle shall be fitted with “Vapour Recovery System” equipment. Such equipment
shall be installed in accordance with Australian Standard (AS) 1940, Australian Institute of
Petroleum (AIP) CP6-1986 and AIP CP4-1993.
3. The aboveground tank shall be fitted with a “pressure vacuum valve” on the atmospheric
vent. The pressure vacuum valve shall be set to closed when the pressure in the tank is
between the design operating maximum pressure and the design operating maximum
vacuum in accordance with AS 1692.
Wastewater and other Liquid Waste
4. Wastewater and other liquid waste shall be discharged to sewer or transported to an
approved hazardous waste facility. The licensee must comply with the conditions of a current
trade waste permit issued of the site and/or conditions of an approval to transport to an
approved hazardous waste facility.
5. Vehicle or equipment wash down shall not be conducted in a manner which may cause the
contamination of surface stormwater run-off.
6. Wastewater from car washing must not be directed to the stormwater and can only be
directed to sewer under the conditions of a trade waste permit.
7. Drainage from paved forecourt and areas on which a vehicle can stand while being fuelled
or transferring petroleum products, shall be directed by appropriate surface grading into
grated sumps, floor silt arrestors, floor basket arrestors, gutters and/or grated drains leading
to underground drainage systems dedicated only to stormwater runoff, which finally
discharge into stormwater drainage systems as approved by the local authority.
8. Uncontaminated stormwater from roofed areas and uncontaminated ground areas shall be
directed away from petroleum loading and dispensing areas.
9. Wastewater and other liquid waste shall not be discharged or released to waters.
10. Provision shall be made to contain any leakage/spillage and contaminated waste water from
above ground petroleum product storage tanks and package storage areas, and to prevent
it from contaminating surrounding soil and stormwater. As a minimum, spill control measure
shall be in accordance with AS 1940.
11. Drainage from tank and package store bunds and compounds must be manually controlled
so that all wastewater passes through treatment facilities before release to the environment.
Any valve controlling the drainage from a compound shall be located outside the bund. The
valve shall be of a type in which the distinction between open and closed positions is obvious
and shall be closed and locked at all times except when flow to the treatment facility is
authorised by management.
12. Provide a notice adjacent to the bund valve displaying the following: