Log in to see the plans as drawn 4.0 Maintenance Procedures
The Maintenance Programme will be kept on the premises at all times, with a ledger recoding all
maintenance and inspection activities. This will provide a useful and efficient record for Inspection officers
to facilitate random verification. Maintenance is performed at a minimum of every six months or if the probe
alarm is activated, by eduction method (suction). The Inspection and Maintenance guideline in Appendix 5
better elaborates the procedures.
4.1 Coalescer Unit
Use the lifting handle or the chain and lift the Coalescer unit out of the tank and place it near the
Puraceptor™, in a retained area so pollutants do not escape.
4.2 Coalescer Foam
Remove the coalescer foam insert, and wash with normal water pressure ensuring the dirty water runs into
the SPEL Puraceptor™.
4.3 Sucking Out Fuel & Silt
Suck off the retained oil from both chambers of the SPEL Puraceptor™ and then the silt deposited on the
bottom, leaving sufficient water to ensure the (auto closure device) ACD remains floating.
4.4 Sucking Out Complete Contents (If Necessary)
If the quantity of pollutants exceeds recommended level, the complete contents of the Puraceptor™ may
need to be removed. After sucking out completely, remove the ACD. Using a pole with a hook, lift out the
ACD using the lifting eye on the float.
4.5 Re-insert Coalescer Unit and ACD
Re-insert the foam coalescer insert into the stainless steel Coalescer unit and re-insert the Coalescer
unit into the Puraceptor™ as provided with the SPEL lifting/location/locking system. Partially fill the
Puraceptor with clean water (if necessary) to ensure the ACD when re-inserted remains floating and then
re-insert the ACD. Finally check the ACD is floating and the retaining cap has been replaced to
safeguard against its removal by unauthorized persons, unless depth of tank precludes doing so from
HEAD OFFICE POSTAL EMAIL ABN spel.com.au
100 Silverwater Road PO BOX 7138 [email protected] 83 151 832 629
Silverwater NSW 2128 Silverwater NSW 2128
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalVery large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.