22441 DA - Response to Information Request [As Published] · 132001.210331.2

of 58

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

5.0

a)

b)

°)

 

Job No. CE07/044

Where y = Sand Bulk Density ©
B = Pile Diameter
D = Pile Depth .
Kp = Coefficient of Passive Resistance = 5.0 (0-—3m)
= 10.0 (> 3m)

LONG TERM EFFECTS

The Residence .
The residence may be supported on stee! screw piles, for which an allowable base

resistance may be taken as a minimum of 500 kPa in medium dense sand, provided
that:-

« The piles are hot dip galvanized to protect against corrosion
¢ The minimum pile depth is 4.5m below the present ground level

A further requirement is that the residence is braced or stiffened in the east-west
direction at least at floor level. It would be prudent also to provide lateral restraint at
ground ‘evel to overcome a potential sand.slip or downslope creep. This matter is
discussed further in (b) below. '

Slope Stability

The concept of a garage structure at the foot of the slope removes most of the slope
stability risk, but the site above the garage remains at a slope exceeding the natural .
angle of repose for dry running sand.

Over the residence footprint area, the dune slope is about 32 degrees, which could
slump to 30 degrees under dry conditions and loss of vegetation. If this was the case,
a break in the slope of 600-700mm could occur at the rear wall of the residence, with
a rise of the same amount as slip debris at the rear garage wall. A low retaining
structure should be considered at least at the line of the rear of the residence.

Design Parameters

Sand Density = 17 kNim*
Active Pressure Coefficient Kg = 0.9
Passive Pressure Coefficient Ky = = 0.9

Sand anchors could be used for horizontal (and moment) restraint. Anchors should
continue into the medium dense sand below a depth of 2.5 metres, where a pull out
resistance of 300 kPa is available as end bearing or 15 kPa as allowable friction.

Disposal of Wastewater and Stormwater

It is understoad that the residential wastewater and stormwater are to be taken to
discharge points in Park Road. This is acceptable provided that the same parameters
are used to provide a safe slope, which have been given for the residence. It may be
necessary to support the conduits on drilled piers aver the very steep slope area.

00979 Kidds & Co Designers MORRISON GEOTECHNIC

Used in these records

About this file

File size
4.3 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

22441 DA - Response to Information Request [As Published].pdf · 4.3 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.