Unit Building, Sunshine Beach

Foundation Design Certification

3.0 DESIGN CONSIDERATIONS AND RECOMMENDATIONS

Soil reactivity was assessed to be minimal in the sandy upper soils on the site. Some miner elastic
settlements can be anticipated. These are likely to be some 10 to 20 mm depending on loads and
location.

The allowable bearing capacity is a function of depth and location on the site. For high level footings
founded at depths greater than 0.3 metres near the front of the site in the vicinity of boreholes BH1 and
BH2, an allowable. bearing capacity of 100 kPa was recommended for design. For the rear of the site in
the vicinity of boreholes BH3, BH4 and BH5, the sands were loose to depths of 1.4, 0.9 and 1.1 metres
respectively. Founding at shallow depth in this area was not recommended. Deeper footings founded
at depths between 1.1 and 1.6 metres were recommended. The founding strata at these depths were
medium dense sands with an allowable bearing capacity of 100 kPa.

Basement design parameters and piled footing considerations were provided.

4.0 FOUNDATION DESIGN AND CERTIFICATION

The engineering design was undertaken by Contour Consulting Engineers. The design is set out ina
series of drawings prefixed 5083. The footing designs are set'out in Drawings S 2.0, S 2.1 and S 2.2.
The design shows a full piled footing system with strip footing beams. Pile depths are not specified but
pile ‘axial load capacities are set out in the drawings. The design meets the requirements of our design
recommendations.

It is hereby certified that the foundation type and design for the structure, retaining walls and swimming
pool .are in accordance'with the design requirements of our geotechnical report. This certification is
subject to the achievement of the pile load capacities specified in the drawings. The capacity of all piles
should be certified by the piling contractor.

Should you wish to. discuss any aspect of this certification, please contact Ron McMahon at Coffey’s
Kunda Park office.

For and on behalf of

COFFEY GEOTECHNICS PTY LTD
—_ ”

RON MCMAHON

ATTACHMENTS: Important information about your Coffey Report

Coffey Geotechnics 2
GEOTKPARI334AA/A
22 January 2008

Used in these records

About this file

File size
20.7 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

09_1382 - Operational Works - Landscaping & Civil Works [As Published].pdf · 20.7 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.