Attached to the e-mail Updated SW management plan MCU14/0102.05.

of 92

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

            worldwide regard less than 10 ppm as being the benchmark for no visible trace or sheen. Table 1 shows that
            discharge water quality reduction remains constant at <0.1ppm of TPH translating to `no visible trace` from a
            constant inflow concentration of 5,000ppm. The detail of the testing can be reviewed in Appendix 3.

            The Hydrocarbon mix used for the University of South Australia testing program was formulated to replicate the
            carbon fraction breakdown that we see in the field on service stations all over Australia. The NATA detection
            instruments detect all forms of hydrocarbon as in free phase, emulisified and dissolved fractions. The C6 – C9
            fraction represents the BTEX (Benzene, Toluene, Ethylbenzene, and Xylene) constituent of the mix.

            Table 1. - Reduction of Total Petroleum Hydrocarbons, UniSA



                                        Inflow                Outlet Samples TPH Fraction Concentrations    Calculated
               Hydrocarbon
                                EQL*    Concentration                                                       Mean
               Fraction
                                        (Total 5699.0)                                                      Concentration
                                                              1         2        3         4        5

               C6-C9            0.02    0.15                  <0.02     <0.02    <0.02     <0.02    <0.02   <0.02

               C10-C14          0.04    125.43                <0.04     <0.04    <0.04     <0.04    <0.04   <0.04

               C15-C28          0.10    5570.62               <0.1      0.162    <0.1      <0.1     <0.1    < 0.032

               C29-C36          0.1     3.42                  <0.1      <0.1     <0.1      <0.1     <0.1    <0.1
               * Detection Limit: Estimated Quantitation Limit Results expressed in mg/l



            Results show below detection levels of hydrocarbons of all carbon fractions except for C15-C28 with the level
            just above the EQL at 0.162ppm. This is still less than the 10ppm target.

            Independent Standard and Validation

            The British Standard and the independent validation applied to the SPEL Puraceptor™ separators provides the
            council the appropriate latitude to assess the product and the catchment design unencumbered by commercial
            partiality. Please refer to the test data in Appendix 3.




HEAD OFFICE                  POSTAL                          EMAIL                             ABN                          spel.com.au
100 Silverwater Road         PO BOX 7138                     [email protected]                 83 151 832 629
Silverwater NSW 2128         Silverwater NSW 2128

Used in these records

About this file

File size
9.2 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

F0002-AA007595-AAR-09-SMP.PDF · 9.2 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.