Council archive · source document
F0002-AA007595-AAR-09-SMP · MCU14/0102.05
Attached to the e-mail Updated SW management plan MCU14/0102.05.
1
2
Figure 14. Section through Puraceptor showing sample points.
Table 6. Water Quality Analysis results (values exceeding 10ppm highlighted in yellow)
LOR Unit Inlet (1) Outlet (2) Inlet (1) Outlet (2)
Report Reference 2/4/15 2/4/15 29/4/15 29/4/15
EP080/071: Total Petroleum Hydrocarbons
C6 - C9 Fraction 20 µg/L <20 <20 90 60
C10 - C14 Fraction 50 µg/L 220 <50 1890 110
C15 - C28 Fraction 100 µg/L 2540 500 11000 470
C29 - C36 Fraction 50 µg/L 380 100 200 70
C10 - C36 Fraction (sum) 50 µg/L 3140 600 13090 650
Anionic Surfactants as MBAS 0.5 µg/L 8 1 1 0.4
Non-ionic Surfactants as CTAS 0.5 µg/L <0.5 <0.5 <0.5 <0.5
Efficiency Ratio (%)
C6 - C9 Fraction 30%
C10 - C14 Fraction 94%
C15 - C28 Fraction 93%
C29 - C36 Fraction 71%
C10 - C36 Fraction (sum) 92%
Anionic Surfactants as MBAS 84%
Non-ionic Surfactants as CTAS ND
HEAD OFFICE POSTAL EMAIL ABN spel.com.au
100 Silverwater Road PO BOX 7138 [email protected] 83 151 832 629
Silverwater NSW 2128 Silverwater NSW 2128
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
F0002-AA007595-AAR-09-SMP.PDFRelated documentApplication case desk ↗
About this file
- File size
- 9.2 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.