Bushfire Management Plan v1                                                                NCES REF: J000953
Lot 189 on MCH1261 – 64 Reserve St, Pomona




lots that are sited so that they are separated from the closest edge to the adjacent medium, high or
very high potential bushfire intensity area by a distance that achieves a radiant heat flux level of 29
kilowatt per square metre or less at:
1. The building envelope, if identified at RaL stage, or
2. Where a building envelope is not identified, at all the lot boundaries.
Compliance with Assessment Benchmark 4 can be attained where the proposed building envelope
is sufficiently separated from the nearby forest hazard so that a radiant heat flux level at any point
on the building envelope, does not exceed 29 kW/m². In this instance a specific building footprint is
proposed hence the limit of the building footprint can be used in lieu of a building envelope.
4.2.3    Radiant Heat Flux Setbacks (APZ)
Determination of the setbacks required to satisfy Assessment Benchmark 4 can be identified from
the quantitative modelling output presented in Section 3.2 herein. The output results from Plate 8 &
9 can be used to identify the setback requirements to achieve the <29 kW/m² radiant heat flux SPP
requirement. The required setbacks are shown in Table 4.
                    Table 4 – Radiant Heat Flux Minimum Setbacks to secure <29kW/m²
                           VHC                     Direction          <29 kW/m² Setback*
                                                                             (m)
                                                 and slope (º)

                            8.1              North, South, East (1)          17.9

                            9.1                     West (1)                 11.7

* Source – Flamesol Minimum Distance Calculator Plate 8 & 9

Table 4 identifies a minimum setback of 17.9m to the north, south, and east and 11.7m to the west
is required to expose the building to <29 kW/m² radiant heat flux.
It is therefore recommended the proposed works are provided with a minimum 17.9m setback to the
VHC 8.1 vegetation to the north, south and east, and a minimum 11.7m setback to the VHC 9.1 to
the west to achieve an acceptable level of risk under the SPP. The extent of the recommended APZ
is detailed in plan BAL02 – Separation Requirements.




© 2021                                               13
Log in to download the original file

MCU21-0134 - Approved Bushfire Management Plan.pdf · 4.3 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.