24-0523 Structural Issue A(1)(2)
FLOOR FRAMING SCHEDULE:
MARK SIZE DESCRIPTION
BR1 152x76x6.0 Rectangular Hollow Section Bearer (continuous span)
(Alloy & Temper - 6061/T6)
DJ1 200x50x3.0 Rectangular Hollow Section Deck Joist (single span)
(Alloy & Temper - 6060/T5 or 6106/T6)
SJ1 200x50x3.0 Rectangular Hollow Section Structural Joist (single span)
(Alloy & Temper - 6060/T5 or 6106/T6)
TR1 200x50x3.0 Rectangular Hollow Section Trimmer (single span)
(Alloy & Temper - 6060/T5 or 6106/T6)
ST1 80x50x6.0 Rectangular Hollow Section Strut
(Alloy & Temper - 6060/T5 or 6106/T6)
C1 315Ø Jetted Concrete Piles Column
NOTES:
1. All floor joists to be at 450mm crs UNO.
NOTE:
All fixings, connectors, plates and angles
to be Stainless Steel grade 316 or aluminium
315 outer diameter tube.
Filled with concrete, N50/20.
Provide 6/N12 bars
and R10 helix with 150mm pitch.
NOTE:
All Steel to be protected
as per AS/NZS 2312.1
Approx Broadwater Bottom
NOTE:
steps by others
All dissimilar metals to be
isolated to prevent corrosion TR1
BR1
Boundary
C1
Property
DJ1
SJ1
SJ1
(Typical) BR1
TBC by specilist contractor
C1
Hidden line indicates
location of ST1. Typical.
65mm
(Typical) 315 outer diameter tube.
cover
SJ1 Filled with concrete, N50/20.
Provide 6/N12 bars
BR1
and R10 helix with 150mm pitch.
BR
1
BR1
BR1
DJ1
C1
C1
C1
C1
TR1
315mm Ø
SJ1
Cantilevered framing must not
be fixed to revetment wall.
Aluminum plate to end of
(Typical)
framing as specified by builder.
Pile depth to be confirmed with
specilist contractor and install piles
achieve minimum working loads:
315mm Ø Vertical load capacity - 21kN
Horizontal load capacity - 4kN
Confirm depth with engineer prior to construction
C1 - 315Ø PILE REINFORCEMENT
FOR OVERALL DIMENSIONS OF SLAB AND FOOTINGS, REFER ARCHITECTURAL DRAWING
Issue Made By Date Description PROPOSED NEW JETTY Scale : 1:100 NOTES:
A LL 21/10/24 Issue for construction
at LOT 498 (#20) TOPSAILS PLACE, NOOSAVILLE
REVISION
Job No.: 24-0523 1. Do not scale drawings.
2. Scale is correct at A3.
BUILDER: PONTOON WORKS
Dwg No.: S02 3. Check and verify all dimensions
Designed By : L.LITTLE Drawn By : LL Date : 21/10/24 prior to commencement of work.
Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER Date : 21/10/24 Ph: (07) 5444 5578 Email: [email protected] FLOOR FRAMING LAYOUT