Attached to the e-mail MCU16/0081 - Energex advice agency response - 28 Eenie Creek Road Noosaville.

of 5

Page text shows just the words. Original shows the document exactly as it was published.

                                                 3


                   The location of the Energex structures in relation to the proposed
                    lighting

    7. Proposed underground services such as stormwater, sewerage, water and the
       like are to be kept to the outer edge of the easement. Services crossing the
       easement should be as near as practicable to right angles to the overhead
       conductor direction and not within 10 metres of any tower, pole or stay.
       Pipelines and crossings are to be clearly marked. Please submit the
       relevant design drawings to the Energex for review. The identification,
       assessment and mitigation of any possible hazards in the service due to
       electromagnetically induced voltages, is the responsibility of the Developer.

    8. At all times the following clearance must be maintained from the top of any
       machinery moving in the vicinity of energised conductors:

                   132kV and 110kV conductors – 4.5m minimum clearance

        Should it be necessary to transport equipment or extend any equipment, such
        that these clearances cannot be confidently maintained, you are required to
        contact our office to ascertain whether a Safety Officer is required on–site. All
        operators of machinery are to be made aware of the presence of high voltage
        conductors.

    9. Any proposal for landscaping on the easement must have prior approval from
       Energex. Please submit the relevant landscaping design to Energex for
       approval. When considering landscape designs the planting of trees must be
       kept to the edges of the easement and not under any overhead conductors.
       When mature, plants or trees must not grow in excess of 3.5meters in height.
       Please visit https://www.energex.com.au/home/safety/safety-around-the-
       network/safetree-plants for a full list of safetree plants.

Any further works should be in accordance with Energex Standard Guidelines MD-
03/12 for general conditions when considering works either on an Energex easement
or in the vicinity of Energex assets. These are attached for your reference.

ENERGEX Limited would like to advise that Noosa Council should treat this response
as a properly made submission, as per Section 292 (3) of the Sustainable Planning Act
2009.

Should you require any further information on the above matter, please contact Angela
Collins on (07) 3664 5766.

Yours faithfully,




Angela Collins
Town Planner
Property Services
Energex Limited




Reference:   HBD 5390549 346062

                         Did you know Energex has a referral website?
     https://www.energex.com.au/home/our-services/connections/development-application-referrals
Log in to download the original file

EGX_PROD_n5390549_28_Eenie_Creek_Road,_Noosaville_Part_of_L3_on_SP246584.pdf · 230 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.