Original source · versioned page text
EGX_PROD_n5390549_28_Eenie_Creek_Road,_Noosaville_Part_of_L3_on_SP246584
Attached to the e-mail MCU16/0081 - Energex advice agency response - 28 Eenie Creek Road Noosaville.
4
Standard Guidelines MD-03/12
When considering Works, either on Energex easements or in the vicinity of Energex
assets, please be aware of the following general conditions:
Satisfactory clearance from your proposed structure to the existing (and/or future)
electricity wires must be maintained in accordance with the Electrical Safety
Regulations 2013.
All previous conditions must be adhered to and Energex may, at its discretion, audit
the finished development to check that it conforms to the conditions of the
development.
Detailed civil design drawings showing any proposed cut and fill levels on the
easement and the location of the Energex assets in relation to the proposed
development must be approved by Energex before any works can commence on
site.
No civil works are to occur within 5 metres of any part of an Energex Structure
(e.g.- tower base, pole or stay) without Energex approval.
If the minimum 5m horizontal separation to the Energex structure cannot be
achieved, the Developer must consult Energex with regards to allowable
construction methods. This may include full depth shoring of the excavation sides
for a minimum of 5 metres either side of the structure.
Any excavations deeper than 5m must have a minimum horizontal separation from
the excavation to any tower, base or pole at least equal to the excavation depth.
The excavation is not to be left open overnight and backfill is to be compacted in
150mm layers in the immediate vicinity of the structure.
10 metres clear access must be provided around all towers and pole structures
after the completion of any works on the easement.
Natural ground level on the easement should not be disturbed without Energex
approval.
Final ground levels should slope gently to the edge of the easement, surrounding
area or kerb such that pooling of water on the easement is avoided and conductor
ground clearances are not decreased.
Stockpiling of spoil on the easement is prohibited.
Lighting structures are not permitted in the easement without prior written consent
of Energex. Lighting designs for proposed developments (e.g. road, carparks etc)
on the easement are likely to require reduced height structures. Please submit
detailed design to Energex for approval. These drawings must clearly show the
following;
Proposed height of the lighting structures and the ground level at the structure
base,
Relative (to lighting structures) ground levels at Energex structures (towers,
pole etc) either side of the lighting structures, and
The location of the Energex structures in relation to the proposed lighting
Reference: HBD 5390549 346062
Did you know Energex has a referral website?
https://www.energex.com.au/home/our-services/connections/development-application-referrals
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalSearchable page text hides email addresses. Original files are unchanged and may show email addresses.