5
Proposed underground services such as stormwater, sewerage, water and the like
are to be kept to the outer edge of the easement. Services crossing the easement
should be as near as practicable to right angles to the overhead conductor direction
and not within 10 metres of any tower, pole or stay. Pipelines and crossings are
to be clearly marked. Please submit the relevant design drawings to the Energex
for review. The identification, assessment and mitigation of any possible hazards in
the service due to electromagnetically induced voltages, is the responsibility of the
Developer.
Any cut in the vicinity of a structure or between a structure and the road kerb will
need to be stabilised by a retaining wall. The retaining wall design and location is
to be submitted to Energex for approval.
Any costs incurred by Energex as a result of the works on the easement are to be
met by the property Developer / owner.
Access to the easement and access along the easement must be available to
Energex personnel and heavy equipment at all times. Energex will require the
Developer / owner to supply and install gates where fencing prohibits access to and
along the easement area. To enable travel along the easement at anytime the
gates must be series locked with an Energex padlock. Both the padlock and a
design drawing of an acceptable gate will be provided by Energex.
At all times the following clearance must be maintained from the top of any
machinery moving in the vicinity of energised conductors:
132kV and 110kV conductors – 4.5m minimum clearance
33kV and 11kV conductors – 3m minimum clearance
Should it be necessary to transport equipment or extend any equipment, such
that these clearances cannot be confidently maintained, you are required to
contact our office to ascertain whether a Safety Officer is required on–site. All
operators of machinery are to be made aware of the presence of high voltage
conductors.
Any proposal for landscaping on the easement must have prior approval from
Energex. Please submit the relevant landscaping design to Energex for approval.
When considering landscape designs the planting of trees must be kept to the
edges of the easement and not under any overhead conductors. When mature,
plants or trees must not grow in excess of 3.5meters in height. Please visit
https://www.energex.com.au/home/safety/safety-around-the-network/safetree-
plants for a full list of safetree plants.
Reference: HBD 5390549 346062