Response to Info Request - Attachment 5 - Geotechnical Report MCU18-0015 & RAL18-0001 · MCU18/0015
J000635-002-R-Rev1 November 2018
6.3.2 Piles
Where loose sand is present (i.e. Proposed lots 1 and 2), structures should be supported on the underlying
medium dense (or denser) sand. Grout-injected CFA or bored piles are considered suitable. Bored piles may
encounter significant fall-in of loose sand unless a casing/liner is used during construction.
Drilling spoil or fluid should not be stockpiled or discharged on site.
Table 4 shows representative values of ultimate (unfactored) geotechnical parameters for bored/CFA pile
design. A sensitivity analysis should be undertaken to assess effects for the range of parameters.
Table 4: Pile Design Parameters.
Ultimate skin Ultimate base
Material type
friction (kPa) resistance (kPa)
Loose sand 10 NR
Medium dense sand 20 NR
Dense sand 40 NR
Very dense sand 60 1800
Stiff clay 30 500
Very stiff or hard clay 50 1300
Low strength (or
100 2200
stronger) rock
Notes:
1) NR – Not recommended
2) Skin friction should be discounted for sections of pile shafts where liners are in place
Piles should be designed to resist lateral loads from the movement of loose sand, in the event of localised
slope instability. Lateral forces should be estimated on the assumption that lateral movement occurs along
the interface between loose and medium dense sand, using an assumed depth of 3 m. Calculation of lateral
forces on piles may be carried out in accordance with the method outlined below:
Ultimate geotechnical capacities (Rd,ug) determined from the parameters provided must be multiplied by a
geotechnical strength reduction factor (øgb) in accordance with Section 4 of AS 2159-2009 Piling – Design
and installation to determine the design geotechnical strength (Rd,g). The geotechnical strength reduction
factor should be determined in accordance with AS 2159-2009 and is expected to be in the range of 0.45 to
8
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Response to Info Request - Attachment 5 - Geotechnical Report MCU18-0015 & RAL18-0001.pdfRelated documentApplication case desk ↗
About this file
- File size
- 8.0 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.