Performance Outcomes Acceptable Outcomes
Editor's note—refer to Figure AP3-3B
Roof forms NA – no change to existing
PO19 AO19.1
Roof forms: With the exception of Noosa Heads and Coastal
Communities Local Areas, the main roof of the
1. contribute positively to the local building has a roof pitch no less than 5 degrees and
skyline; has minimum 600 millimetre eaves to at least 75% of
2. complement the character of the the perimeter of the building.
locality and the topography of the
site; AO19.2
3. avoid box profiles/parapets; and Development does not include rooftop terraces.
4. do not create opportunities for
overlooking the private open space AO19.3
or internal spaces of neighbouring The total width of any parapet wall does not exceed
properties. 50% of the width of the front facade of a building.
Safety and amenity Table 6.3.2.3 - Criteria for assessment (part)
Performance Outcomes Acceptable Outcomes
Safety and amenity Response
PO20 AO20.1 Complies
Development: Buildings and structures:
1. provides a high level of residential 1. are sited and orientated to minimise the
amenity to users of the subject site; likelihood of overlooking the private open
and space of adjacent residential uses;
2. does not unreasonably impact on the 2. avoid reduction of sunlight to at least 40% of
amenity enjoyed by users of adjoining the private open space areas of any adjoining
or nearby premises, including privacy residences to less than two hours
and access to sunlight. between 9:00am and 3:00pm on any day of
the year;
Editor's note—Provisions for sill height, 3. incorporate fencing, landscaping and
glazing, screening and window openings are screening to mitigate impacts on adjoining
to improve the residential amenity for residential uses.
occupants. Thermal performance
requirements are contained Editor's note— refer to figure AP3-1A and figure AP3-
in Queensland Development Code MP4.1 2A
Sustainable Buildings. Energy efficiency
requirements are contained in the National AO20.2
Construction Code. Transparent doors and windows are designed and
located so they do not directly face transparent doors
or windows or the private open space areas of other
dwellings within 10 metres;
AO20.3
Where windows, balconies, terraces, verandahs or
decks overlook or have the potential to overlook the
private open space of nearby properties or view into
habitable room windows within 10 metres:
1. windows have a sill height of not less than 1.7
metres above finished floor level;
2. windows and other openings are permanently
screened to a minimum height of 1.7 metres
to avoid overlooking;
3. windows and doors use translucent glazing to
obscure views; or
4. windows or balconies are offset by 45 degrees
or more.
Editor's note—refer to figure AP3-1A and figure AP3-