4. Water Supply Specification
    Installed reticulated hydrant systems are to be located on roadways or access ways for all material
    change of use and reconfigured lots for fire fighting purposes as per AS 2419.1 2005 Appendix B that
    provides a minimum standard for hydrant intervals. In a Local Government Authority where a local
    water authority specifies a design and performance criteria above the requirements of AS 2419.1 2005
    Appendix B, the local water authority requirements will be adopted.

    For the installed reticulated hydrant systems the minimum water flow rate and pressure is to be 10
    L/S @ 200 Kpa as per AS 2419.1 2005 Table 2.2 (for building Class 2-9 only). In a Local Government
    Authority where a local water authority specifies a flow rate and pressure above the requirements of AS
    2419.1 2005 Table 2.2, the local water authority requirements will be adopted.


4.1 Hydrant Provision:
                                            Hydrant Provision
             Expectation                                 Acceptable Outcomes
    Where reticulated water is   Hydrants above or below ground should be provided and maintained to
    available, operable hydrants the minimum required performance standard as per AS 2419.1 2005.
    are to be provided.
    Rationale:
    Firefighters use water as a prime extinguishing medium for structure fires. Reticulated water mains have
    hydrants placed at regular intervals to enable firefighters to connect into the reticulated system. The
    water is pressurised by pumps in the fire truck and delivered via hoses to the fire.

    Figure 1 illustrates hydrant locations on reticulated water mains.




     Figure 1 – Reticulated Hydrant System                     Figure 2 – Use of Hydrant System



4.2 Hydrant Markers
                                                Hydrant Markers
             Expectation                                      Acceptable Outcomes
    Hydrants are suitably           Blue cats eyes are preferred for sealed roads. Marker posts at the fence
    identified so that firefighters line should be used to identify hydrants where there is an unsealed
    can locate them at all hours. road as road (HR) or path (HP) hydrants. The Figures 3-6 are examples
                                    of marker locations.



4                                                 - Public -                                      Fire Hydrant Guidelines (Effective: 03/2019)
Log in to download the original file

Bushfire Hazard Assessment & Management Plan v4 - 7 Triller Court, Pomona.pdf · 4.1 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.