Bushfire Hazard Assessment & Management Plan v4 - 7 Triller Court, Pomona
Attached to the e-mail RAL21/0022 - 7 Triller Court_ Pomona - Response to Further Advice Matters & Change to app (1 Lot into 4).
Plans and drawings: the text below has words only, no drawings.
Rationale:
Firefighters need to quickly locate water supplies in emergencies. Hydrant indicators need to be visually
identifiable from both directions by the approaching fire truck crews and must identify the location of
the hydrant.
Figure 3 – Hydrant Markers Figure 5 – Marker/directional arrow spacing detail
INDICATOR PLATES
• 254 x 76 aluminium
indicator plate.
• Fix top and bottom with
galvanised clouts.
• HP indicates hydrant
located in footpath.
• HR indicate hyrdant
located in road
carriageway.
Figure 4 – Hydrant marker posts Figure 6 – Location of cats eyes on a sealed roadway
4.3 Hydrant Location
Hydrant Location
Expectation Acceptable Outcomes
Hydrants are located in Residential Streets and Accessways
positions that will enable Above or below ground fire hydrants should be provided at not more
firefighters to access water than 120m intervals along residential streets and at each street
safely, effectively and intersection. Above ground fire hydrants may be single outlet.
efficiently.
Commercial and Industrial Streets and Accessways
Within streets serving commercial properties such as factories,
warehouses and offices (building classes 2-9 not requiring hydrants by
NCC), above or below ground fire hydrants should be provided at not
more than 90m intervals and at each street intersection. Above ground
fire hydrants should have dual valved outlets.
Rationale:
Upon arriving at a structure fire, firefighters site the fire truck with considerations to safety, access to the
fire, other responding trucks and accessible water supply for fire fighting purposes. Firefighters have an
expectation that fire hydrants will be located on reticulated water systems no more than 120m apart as
per AS 2419.1 2005, Appendix B. QFES equipment, procedures and the training of personnel is based
on this preferred standard of fire hydrant placement and associated access requirements.
Fire Hydrant Guidelines (Effective: 03/2019) - Public - 5