              3.4      Setback Distances
              The Queensland Plumbing and Wastewater Code V1:2024 Appendix 1 outlines minimum setback
              separation distances required for on-site wastewater management facilities. This design complies with
              the relevant setbacks.

              The ‘Land Application Area Setback Distances’ (QPWC Table T2) are presented in Table 6.

              Table 6: Separation Distances: Subsurface land application areas
                                                                                                     Separation Distance
                                               Feature
                                                                                          Upslope           Downslope               Level
                Property boundaries, pedestrian paths, walkways,
                recreation areas, retaining wall, and footings for buildings                2m                  4m                  2m
                and other structures
                Inground swimming pools                                                     6m                  6m                  6m
                Inground potable water tank not exposed to primary
                                                                                            6m                  6m                  6m
                effluent
                Inground potable water tank exposed to primary effluent                    15 m                15 m                 15 m
              *Distances are given in meters and are measured from the edge of trench/bed excavation or subsurface irrigation distribution
              pipework to the nearest point of the feature

              The ‘Protection of Surface Water and Groundwater Setback Distances’ (QPWC Table T5) are presented
              in Table 7.

              Table 7: Separation Distances: Protection of Surface Water and Groundwater
                                               Feature                                               Separation Distance
                Effluent Quality                                                         Adv. Sec.         Secondary            Primary
                Top of bank of permanent water course                                      10 m               30 m                50m
                Top of bank of intermittent water course                                   10 m               30 m                50m
                Top of bank of a lake, bay or estuary                                      10 m               30 m                50m
                Top water level of a surface water source used for
                                                                                           10 m               30 m                50m
                agriculture, aquaculture or stock purposes
                Open stormwater drainage channel or drain                                  10 m               30 m                50m
                Bore or dam                                                                10 m               30 m                50m
                Unsaturated depth to a permanent water table (vertical)                    0.3 m              0.6 m               1.2m
              *Distances are given in meters and are measured from,
                       - any part of the on-site sewage facility (including pipes and fittings) and,
                       - the edge of irrigated wetted area of the Land Application Area to the feature as listed.

              Where ‘on-site sewage facility’ is defined as:
                       a facility, other than an environmentally relevant on-site sewage facility, installed on premises, that includes:
                                   (i) an on-site sewage treatment plant on the premises for treating sewage produced on the premises; and
                                   (ii) either
                                               a. a land application area on the premises for disposal of the effluent produced by the on-site
                                               sewage treatment plant; or
                                               b. a tank for storing on the premises the effluent produced by the on-site sewage treatment plant
                                               for later disposal off the premises by collection from the tank; or

              The sewage pump stations are not formal parts of the ‘on-site sewage facility’.




              Site and Soil Evaluation                                              Proposed Cabins - 486 Tablelands Road, Cooran Qld 4569
              Taylor Environmental (Australia) Pty Ltd                                                                         Page 8 of 22



Document Set ID: 23040840
Version: 1, Version Date: 31/05/2024
Log in to download the original file

Referenced Doc - Effluent - MCU24_0071.pdf · 4.0 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.