Attachment A - Existing Approval · 132008.1128.02

Attached to the e-mail Change to DA (Report, Existing Approval, Bushfire Technical Note, DA Form, Owners consent) - 132008.1128.02.

of 50

Text shows just the words. Original shows the document exactly as it was published.

Noosa Council documents




                                                                                                    132008.1128.01

               76.    The level of the existing sewer access chambers within the development site must be
                      adjusted to suit the proposed finished surface levels. Work must be undertaken by
                      Unitywater at the applicants cost.
               77.    Stormwater retention systems and gross pollutant traps must maintain a minimum
                      clearance of 1.5 metres from Unitywater water supply and sewerage infrastructure.
               78.    Tree plantings must maintain a minimum horizontal clearance of 1.0 metre from
                      Unitywater water mains and 1.5 metres from Unitywater sewerage mains. Landscaping
                      plants within these clearances must be low growing when mature and suitable
                      Unitywater approved varieties.
               79.    Construction works undertaken in the vicinity of Unitywater water supply or sewerage
                      infrastructure must not adversely affect the integrity of the infrastructure. All costs
                      associated with repair, replacement or alteration of infrastructure must be met by the
                      applicant.
               80.    Prior to the issue of any Development Permit for Operational Works amended plans for
                      the development must be submitted to and approved by Council, the amended plans
                      must be consistent with the ‘Masterplan’ prepared by RPS dated 18 October 2017, Plan
                      Ref: 132938-01D.
                    DEVELOPMENT PERMIT CONDITIONS FOR RECONFIGURING A LOT (1 LOT INTO 2)
               General
               1.     Development undertaken in accordance with this approval must generally comply with
                      the approved plans of development.
               2.     The development must be undertaken and operated in a manner that causes no
                      detrimental effect upon the amenity of the neighbourhood by reason of the creation of
                      excessive noise, lighting nuisance or other emissions.
               Relevant Period
               3.     The relevant period is four (4) years from the day this permit takes effect and ends on 14
                      December 2015, during which time all conditions must have been complied with, and
                      the Plan of Survey lodged with Council for endorsement, unless an application to extend
                      the relevant period is approved by Council.
               Nature Refuge Dedication
               4.     In accordance with former Noosa Shire Council resolution of its Ordinary Meeting of 29
                      March 2007, the balance undeveloped Open Space conservation portion of Lot 1
                      SP177650 must be gazetted a Nature Refuge under the Queensland Nature
                      Conservation Act. Evidence of the initiation of the gazettal process must be provided to
                      Council within 3 months of sealing of the plan of survey associated with this approval.
               Water & Sewage
               5.     Reticulated water must be provided to each lot in the development (excluding balance
                      Lot 1). This must include:
                         5.1.     Works in accordance with the approved findings of the water supply network
                                  analysis by Worley Parsons, dated 30 July 2008.
                         5.2.     Construction of a new 150mm diameter watermain to Unitywater standards
                                  from the existing 200mm watermain in Ben Lexcen Drive to the existing 100mm
                                  diameter watermain in the Culdesac of Grasstree Court.
                         5.3.     A water service and approved water meter for each lot in accordance with
                                  Unitywater Standard Drawings SCW 350,355 and 360.
                         5.4.     Water meters located on alternative boundaries to electrical pillars.

                                                                                                    Page 13 of 21


Document Set ID: 20451866
Version: 1, Version Date: 14/11/2017                                                              Print Date: 16 November 2017, 8:52 AM

Used in these records

About this file

File size
3.8 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Attachment A - Existing Approval.pdf · 3.8 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.